Author: CHISEN Battery Team

The OPzS2-250 2V250Ah is a 2 V, 250 amp-hour flooded tubular vented lead-acid cell rated at the 10-hour rate — 25 A for 10 hours down to 1.80 V per cell at 20 °C — and it is the right cell for a telecom DC plant, a 108 V substation bus or a solar-and-storage cabinet that needs roughly 12 kWh nominal per 48 V string, on a site where a technician will still read the electrolyte level and top up distilled water every quarter.

It is not a sealed block. Hydrogen venting, acid-proof flame-retardant vent plugs, scheduled water top-up and periodic equalisation are part of the product, not optional extras. A project that treats the OPzS2-250 2V250Ah as a drop-in sealed cabinet battery discovers the difference in the first hot season.

The complete published data set sits on the OPzS2-250 2V250Ah model page, and the rest of the flooded range is listed under tubular flooded lead-acid batteries.

Key Takeaways

  • Capacity is rate-dependent. The nameplate figure is 250 Ah at C10 (25 A to 1.80 V/cell at 20 °C). At longer rates the cell delivers more: 283 Ah at C24, 310 Ah at C48, 325 Ah at C72, 338 Ah at C100, 343 Ah at C120 and 350 Ah at C240 (Datasheet).
  • Charging setpoints are fixed by the datasheet. Float 2.23 V/cell at 25 °C, equalising 2.35 V/cell at 25 °C, temperature compensation −3 mV/°C/cell, designed float life 20+ years at 20 °C (Datasheet). Solar and wind controllers use the 2.25 ± 0.005 V/cell float and 2.40 ± 0.01 V/cell equalising setpoints (Datasheet).
  • Mechanical data is what decides the rack. Body 124 × 206 × 354 mm, 409 mm total height over the terminals, 15.5 kg without electrolyte and 20.5 kg with electrolyte, of which 5.0 kg is acid (Datasheet).
  • Two limits protect the cell. Maximum charging current is 50 A (0.20 × C10) and internal resistance is about 0.88 mΩ fully charged at 20 °C, with a 2750 A short-circuit current (Datasheet).
  • A 48 V string is simple arithmetic. 24 cells give 12,000 Wh nominal, 492.0 kg with electrolyte (24 × 20.5 kg) and 21.12 mΩ of internal resistance (24 × 0.88 mΩ) (Arithmetic).

§1 — OPzS2-250 2V250Ah Quick Specifications

ParameterOPzS2-250 published valueSource
ModelOPzS2-250, flooded tubular stationary cell, 2 V 250 AhModel page
Nominal voltage2 VDatasheet
Nominal capacity250 Ah at C10 (25 A, 1.80 V/cell, 20 °C)Datasheet
C10 discharge current25 A (250 Ah ÷ 10 h)Arithmetic
Capacity at C24 / C48 / C72283 Ah / 310 Ah / 325 AhDatasheet
Capacity at C100 / C120 / C240338 Ah / 343 Ah / 350 AhDatasheet
Float voltage2.23 V/cell at 25 °CDatasheet
Equalising voltage2.35 V/cell at 25 °CDatasheet
Float setpoint, solar and wind2.25 ± 0.005 V/cell at 25 °CDatasheet
Equalising setpoint, solar and wind2.40 ± 0.01 V/cell at 25 °CDatasheet
Temperature compensation, float−3 mV/°C/cellDatasheet
Temperature compensation, solar and wind−4 mV/cell/°CDatasheet
Designed float life20+ years at 20 °CDatasheet
Dimensions L × W × H124 × 206 × 354 mmDatasheet
Container height354 mmDatasheet
Total height over terminals409 mmDatasheet
Terminal centre spacing108 mmDatasheet
TerminalFemale copper insert M8, torque 10–12 N·mDatasheet
Weight without electrolyte15.5 kg (34.2 lbs)Datasheet
Weight with electrolyte20.5 kg (45.2 lbs)Datasheet
ElectrolyteDiluted sulphuric acid, 1.240 g/cm³ at 20 °CDatasheet
Acid weight per cell5.0 kgDatasheet
Internal resistanceApprox. 0.88 mΩ, fully charged at 20 °CDatasheet
Maximum charge current50 ADatasheet
Charge characteristicConstant charge at 0.15 CA to 2.40 V at 20 °CDatasheet
Maximum discharge current (5 s)1000 ADatasheet
Short circuit current2750 ADatasheet
Self dischargeApprox. 4 % per month at 20 °CDatasheet
Ambient, discharge−25 °C to +65 °CDatasheet
Ambient, charge−20 °C to +65 °CDatasheet
Ambient, storage−15 °C to +40 °CDatasheet
Complied standardsIEC 60896-11, DIN 40736, IEC 61427, Eurobat long life guide, BS 6290 part 4, UL 1989Datasheet
Management systems and marksISO 9001, ISO 14001, GB/T 28001, CE, RU recognised componentDatasheet

Every row above is traceable. Values taken from the manufacturer’s OPzS2-250 datasheet are marked Datasheet, values taken from the published English product page are marked Model page, and derived figures are marked Arithmetic wherever they appear in the text. A supplier who cannot tell you which of the three a given figure is has not verified it.

Solar and wind controller setpoints for the OPzS2-250

Controller parameterPublished settingWhy the number matters
Over voltage disconnect2.47 ± 0.01 V/cell at 25 °CThe point at which the controller stops charging and the array is isolated
Regulation / equalising voltage2.40 ± 0.01 V/cell at 25 °CHigher than the mains float because the array has to push against the bus
Array reconnection voltage2.23 ± 0.005 V/cell at 25 °CThe bus voltage at which charging resumes
Float voltage setting2.25 ± 0.005 V/cell at 25 °CThe renewable float setpoint, above the 2.23 V mains float
Low voltage alarm1.95 ± 0.005 V/cell at 25 °CThe alarm threshold for the control room
Low voltage disconnect1.90 ± 0.005 V/cell at 25 °CThe load is shed at this point to protect the cells
Load reconnect voltage2.09 ± 0.01 V/cell at 25 °CThe load is restored once the bus recovers
Temperature compensation coefficient−4 mV/cell/°CThe coefficient used on renewable sites, distinct from the −3 mV/°C/cell float value

Long-time discharge capacity for solar and wind duty (final voltage 1.85 V)

Discharge rateC24C48C72C100C120C240
OPzS2-250 capacity283 Ah310 Ah325 Ah338 Ah343 Ah350 Ah
Stored energy at 2 V566 Wh620 Wh650 Wh676 Wh686 Wh700 Wh

Source: Datasheet for the capacity row, Arithmetic for the energy row (2 V × Ah).

§2 — The Pain: Where 2V 250Ah Projects Go Wrong

The first failure is a specification failure. Buyers routinely receive a quotation that says only “2V 250Ah tubular” and treat every 2 V 250 Ah cell in the world as interchangeable. The published OPzS2-250 data makes the differences explicit: capacity at C10 is 250 Ah, but capacity at C24 is 283 Ah and at C240 is 350 Ah. A bank sized on the C10 number for a slow-discharge backup duty is undersized; a bank sized on the C240 number for a five-hour discharge duty is over-purchased. Both mistakes trace back to a quotation that never stated the rate and the end voltage.

The second failure is thermal. A 48 V string of 24 OPzS2-250 cells accepts a maximum charging current of 50 A per cell, so a charger set to deliver more — which happens when the charger is sized for the string’s nominal power rather than for the cells’ acceptance — pushes the electrolyte into gassing and dries the separator faster than the topping-up interval can repair. The same string on a solar site needs the higher 2.25 ± 0.005 V/cell float and the 2.40 ± 0.01 V/cell equalising setpoint; on a mains-float site the correct values are 2.23 V/cell and 2.35 V/cell at 25 °C. A controller left on the wrong setpoint is the classic cause of premature capacity loss.

The third failure is weight and access planning. The OPzS2-250 is 15.5 kg without electrolyte and 20.5 kg with electrolyte, and the full height over the terminals is 409 mm, not the 354 mm body height. A 24-cell string with electrolyte weighs 492.0 kg (24 × 20.5 kg, Arithmetic), and a 54-cell 108 V string weighs 1,107.0 kg (54 × 20.5 kg, Arithmetic). Cabinets, plinths, floor loading and lifting plans are usually drawn against the body height and a lighter shipping weight, and the result is a string that does not fit the rack and a handling plan that understates the load.

The fourth failure is assuming sealed behaviour. This cell vents hydrogen during overcharge, needs acid-proof flame-retardant vent plugs, needs distilled water, and needs a scheduled equalising period. Those four obligations are why the OPzS2-250 2V250Ah wins in cabinets with a permanent operator — a central DC plant serving a national mobile network operator in Chennai, a fixed-line exchange in Rotterdam, a substation compound outside Nairobi — and loses in unmanned roadside or container sites.

The fifth failure is ignoring parallel strings. A 48 V string of OPzS2-250 cells presents 21.12 mΩ of internal resistance (24 × 0.88 mΩ, Arithmetic). Two strings in parallel do not share load evenly once their float voltages separate by a few millivolts, and the weaker string silently carries less current while ageing faster. The cure is an equalising stage plus a rotation discipline, and both belong in the maintenance contract rather than in a commissioning checklist.

The delivery plan is part of the specification too. A 2 V 250 Ah vented article like this one leaves through Karachi and Santos for buyers in Pakistan and Brazil, and for importers moving stock through Mumbai, and the import file has to name the destination market before the container is booked rather than after it has sailed.

§3 — The Choice: The OPzS2-250 Against Its Published Siblings

Buyers comparing cells between 150 Ah and 350 Ah are choosing between three flooded capacities or between a flooded cell and a sealed one. The table below uses published values only.

ModelCapacity at C10Weight dry / with electrolyteDimensions L × W × HTotal heightMax charging currentInternal resistanceShort-circuit current
OPzS2-150150 Ah10.5 kg / 14.5 kg103 × 206 × 354 mm409 mm30 A1.2 mΩ at 20 °C2400 A
OPzS2-200200 Ah13.0 kg / 17.5 kg103 × 206 × 354 mm409 mm40 A0.95 mΩ at 20 °C2600 A
OPzS2-250250 Ah15.5 kg / 20.5 kg124 × 206 × 354 mm409 mm50 A0.88 mΩ at 20 °C2750 A
OPzS2-350350 Ah20.4 kg / 27.0 kg124 × 206 × 471 mm525 mm70 A0.62 mΩ at 20 °C3300 A

Sources: OPzS2-150, OPzS2-250 and OPzS2-350 from their datasheets; OPzS2-200 from its datasheet; the comparison itself is Arithmetic.

Four numbers drive the decision. First, footprint. The 150 Ah and 200 Ah cells are 103 mm long; the 250 Ah and 350 Ah cells step up to 124 mm, while the width stays at 206 mm and the terminal spacing stays at 108 mm. A rack designed for the 103 mm cells does not accept the 124 mm cells without a new rail, and that is a change to the cabinet, the plinth and the cable entry.

Second, weight. Dry weight rises from 10.5 kg through 13.0 kg and 15.5 kg to 20.4 kg; wet weight rises from 14.5 kg through 17.5 kg and 20.5 kg to 27.0 kg. A cell that must be carried up a ladder or into a pit should be chosen with the wet weight in mind, not the dry one.

Third, internal resistance, which does not fall in a straight line with capacity at the bottom of the range — 1.2 mΩ at 150 Ah, 0.95 mΩ at 200 Ah, 0.88 mΩ at 250 Ah, 0.62 mΩ at 350 Ah — so a 24-cell string of the 350 Ah cell presents 14.88 mΩ (24 × 0.62 mΩ, Arithmetic) against 21.12 mΩ for the 250 Ah cell (24 × 0.88 mΩ, Arithmetic). The voltage drop under the same load is materially lower on the larger cell, which matters when the string is long and the load is heavy.

Fourth, the maintenance profile, and here the published data is unambiguous. The flooded OPzS2-250 carries 20.5 kg of electrolyte in an open container that must be topped up and periodically equalised, and 5.0 kg of acid per cell, so a 24-cell string carries 120.0 kg of acid (24 × 5.0 kg, Arithmetic) that has to be topped up and eventually replaced.

48 V string arithmetic across the flooded range

CellCells in stringNominal energyWeight with electrolyteWeight without electrolyteString internal resistanceMaximum charging current
OPzS2-150247,200 Wh348.0 kg252.0 kg28.8 mΩ720 A
OPzS2-200249,600 Wh420.0 kg312.0 kg22.8 mΩ960 A
OPzS2-2502412,000 Wh492.0 kg372.0 kg21.12 mΩ1,200 A
OPzS2-3502416,800 Wh648.0 kg489.6 kg14.88 mΩ1,680 A

Source: Datasheet for the cell-level values, Arithmetic for the string rows.

For a 54-cell 108 V substation string the OPzS2-250 arithmetic gives a float bus of 120.42 V (54 × 2.23 V), 27,000 Wh nominal, 1,107.0 kg with electrolyte (54 × 20.5 kg), 47.52 mΩ of internal resistance (54 × 0.88 mΩ) and a 2,700 A maximum charging current (54 × 50 A) (Arithmetic).

Flooded against sealed at the 500 Ah step

ModelCapacity at C10Weight with electrolyteDimensions L × W × HMax charging currentInternal resistanceShort-circuit current
OPzS2-500 (flooded)500 Ah26.0 kg166 × 206 × 470 mm120 A0.50 mΩ at 25 °C3,700 A
OPzV2-500 (gel)500 Ah36.3 kg166 × 206 × 506 mm100 A0.56 mΩ at 25 °C2,600 A

Sources: OPzS2-500 and OPzV2-500 from their datasheets.

Two cells with the same 166 × 206 mm footprint and the same 500 Ah rating differ by 10.3 kg of weight (36.3 kg − 26.0 kg, Arithmetic), 36 mm of height (506 mm − 470 mm, Arithmetic), 0.06 mΩ of internal resistance, 20 A of charging acceptance and 1,100 A of short-circuit current — and one of them needs watering while the other does not. That is the whole flooded-versus-sealed decision expressed in published numbers, and it should be made on site-access economics rather than on the initial quotation.

If your string is larger than 350 Ah per cell, move to the OPzS flooded range overview rather than scaling the numbers in this table proportionally — plate thickness, internal volume and electrolyte quantity change non-linearly with capacity. The OPzV2-500 2V500Ah gel cell is the next published sealed step up.

§4 — The Framework: Seven Hard Checks Before You Sign

Q1. Match the charger to the cell’s acceptance, not to the string. The maximum charging current of the OPzS2-250 is 50 A (Datasheet). A 24-cell string therefore accepts at most 1,200 A (24 × 50 A, Arithmetic). Most telecom float rectifiers are sized well below that, which is correct; a solar controller set to the array’s full output is where the limit gets breached.

Q2. Apply temperature compensation to the setpoint, not to the battery. The published compensation is −3 mV/°C/cell on float (Datasheet), so a cell at 35 °C needs its 2.23 V/cell float reduced by 0.036 V. On a renewable site the published coefficient is −4 mV/cell/°C and the float setpoint is 2.25 ± 0.005 V/cell. Controllers that ignore this are permanently overcharging the string in the hot season and permanently undercharging it in winter.

Q3. Design for the float life at the site’s real temperature. The 20+ year design figure is quoted at 20 °C (Datasheet). A cabinet in Chennai, on a roof in Lagos or an outdoor enclosure in Durban will not deliver that figure, and the honest way to plan a replacement interval is to take the 20 °C number and treat every 10 °C of ambient uplift as a materially shorter service life.

Q4. Plan the watering interval from the real charging regime. A cell that is floated at 2.23 V/cell at 25 °C and never equalised loses water slowly; a cell that is equalised at 2.35 V/cell twice a month in a hot climate loses water fast enough to need attention on a monthly cycle. Put the interval in the maintenance contract, and put the electrolyte density check (1.240 g/cm³ at 20 °C, Datasheet) on the same schedule.

Q5. Size the interconnects and torque them correctly. The terminal is a female copper insert M8 with a published torque of 10–12 N·m (Datasheet). Under-torqued terminals generate heat at the joint; over-torqued ones damage the insert. The 2750 A short-circuit current (Datasheet) determines how quickly the fault must be cleared, and the cable cross-section is set by the string current rather than by the bolt size.

Q6. Decide how many strings run in parallel, and how they will be equalised. Two parallel strings will drift apart unless the charger has an equalising stage and the operator runs it. Parallel strings also multiply the water-top-up workload and the total string weight: 24 × 20.5 kg = 492.0 kg per 250 Ah string with electrolyte (Arithmetic), and 120.0 kg of acid per string (24 × 5.0 kg, Arithmetic).

Q7. Confirm the standards the cell is built to. A 2 V vented cell for stationary duty is normally specified against IEC 60896-11 and the equivalent DIN 40736 envelope, with IEC 61427 for the renewable cycling test, the Eurobat long life guide, BS 6290 part 4 and UL 1989 for the North American market. CHISEN production runs under ISO 9001 and ISO 14001 with GB/T 28001 occupational health and safety management, and the range is supplied with CE documentation, so the paperwork trail should exist before the first container is booked.

§5 — The Trust: What a Datasheet Must State — and What to Reject

The single most useful question a buyer can ask a supplier is: “which document is this number from?” A published datasheet answers five questions that quotations never answer. What is the capacity rate and the end voltage? For the OPzS2-250 it is 250 Ah at C10 to 1.80 V/cell at 20 °C, and the full curve to 240 hours is published alongside it. What is the weight with and without electrolyte? 15.5 kg and 20.5 kg — both numbers, because a shipping weight quoted without electrolyte tells you nothing about handling. What is the total height over the terminals? 409 mm, not the 354 mm body height, and the difference is exactly the kind of detail that stops a cabinet from being delivered. What is the maximum charging current? 50 A. What is the reference temperature for the internal resistance and for the float life? 20 °C for both, and both references matter more than the numbers themselves.

Against that standard, reject any quotation that quotes a float voltage above 2.23 V per cell for this model, or one that quotes a temperature compensation coefficient other than −3 mV/°C/cell, or one that quotes the 20+ year design life against 25 °C rather than 20 °C. The OPzS2-250 datasheet setpoints are 2.23 V/cell float, 2.35 V/cell equalising and −3 mV/°C/cell compensation, with the 20+ year design figure referenced to 20 °C. A supplier who quotes different numbers for the same model is either reading a different revision or inventing them.

Two further quality signals are worth checking on site. First, ask for the plant audit trail: paste mixing, grid casting, group assembly, formation and sealing are the process steps that decide whether a 250 Ah cell really holds 250 Ah in year five, and they are the difference between a manufacturer and a packer. Second, ask for the certification package — ISO 9001, ISO 14001, CE, UL and IEC documentation should arrive with the quotation, not three weeks after the deposit. CHISEN runs eight production bases with roughly 70 million kVAh of annual capacity, and the company profile is published on the CHISEN company page if you want to check the manufacturing scale behind a quotation before you commit a container.

§6 — FAQ

Q1. What is the rated capacity of the OPzS2-250 2V250Ah? 250 Ah at the 10-hour rate (25 A to 1.80 V/cell at 20 °C). The published table also gives 283 Ah at C24, 310 Ah at C48, 325 Ah at C72, 338 Ah at C100, 343 Ah at C120 and 350 Ah at C240 (Datasheet).

Q2. How many cells does a 48 V string need, and how much energy does it hold? 24 cells. 48 V × 250 Ah = 12,000 Wh nominal (Arithmetic). The string weighs 492.0 kg with electrolyte (24 × 20.5 kg) and 372.0 kg dry (24 × 15.5 kg), and carries 120.0 kg of acid (24 × 5.0 kg).

Q3. What float and equalising voltage should the charger use? Float 2.23 V/cell and equalising 2.35 V/cell, both referenced to 25 °C. On solar and wind sites use the higher 2.25 ± 0.005 V/cell float and 2.40 ± 0.01 V/cell equalising setpoint (Datasheet).

Q4. What temperature compensation does the cell need? −3 mV/°C/cell on float (Datasheet), applied to the setpoint. At 35 °C the float setpoint falls by 0.036 V per cell. Renewable controllers use the published −4 mV/cell/°C coefficient.

Q5. How long is the designed float life? 20+ years at 20 °C (Datasheet). Higher ambient temperatures reduce achievable service life, so site temperature has to be part of the replacement plan rather than a footnote.

Q6. What is the maximum charging current? 50 A per cell, which is 0.20 × C10 (Datasheet). For a 24-cell string the theoretical ceiling is 1,200 A (24 × 50 A, Arithmetic), and the charger should normally deliver far less.

Q7. Can this cell be installed without a permanent operator? It can be installed, but not forgotten. Flooded tubular cells need distilled-water top-up, electrolyte density checks, ventilation and periodic equalising. For an unmanned site, compare the published gel alternative instead.

Q8. What is the internal resistance and short-circuit current? About 0.88 mΩ fully charged at 20 °C (Datasheet) and a 2750 A short-circuit current (Datasheet). The string resistance of a 24-cell arrangement is 21.12 mΩ (24 × 0.88 mΩ, Arithmetic), and the 2750 A figure is what your DC fuse and disconnection arrangement must be able to interrupt.

Q9. How does the OPzS2-250 compare with the 150 Ah and 350 Ah cells? The 150 Ah and 200 Ah cells are 103 mm long; the 250 Ah and 350 Ah cells step up to 124 mm, with the width at 206 mm and terminal spacing at 108 mm throughout. Published differences are weight (15.5 kg dry and 20.5 kg wet against 10.5 kg and 14.5 kg for the 150 Ah cell, and 20.4 kg and 27.0 kg for the 350 Ah cell), charging limit (50 A against 30 A and 70 A), internal resistance (0.88 mΩ against 1.2 mΩ and 0.62 mΩ) and short-circuit current (2750 A against 2400 A and 3300 A). The OPzS2-250 2V250Ah model page carries the full data set.

Q10. Which standards and certifications apply? The flooded 2 V stationary cell is built to the IEC 60896-11 and DIN 40736 envelope, with IEC 61427 for renewable cycling, the Eurobat long life guide, BS 6290 part 4 and UL 1989 for the North American market. CHISEN supplies the range with CE documentation under ISO 9001 and ISO 14001 management systems, with GB/T 28001 occupational health and safety certification.

Expert Summary

The OPzS2-250 2V250Ah is a 2 V flooded tubular vented lead-acid cell with a published 250 Ah capacity at the 10-hour rate (25 A to 1.80 V/cell at 20 °C), rising to 350 Ah at the 240-hour rate; float 2.23 V/cell and equalising 2.35 V/cell at 25 °C with −3 mV/°C/cell compensation and a 20+ year design float life referenced to 20 °C; a body of 124 × 206 × 354 mm with 409 mm total height over the terminals; a weight of 15.5 kg without electrolyte and 20.5 kg with electrolyte, of which 5.0 kg is acid; a 50 A maximum charging current; about 0.88 mΩ internal resistance at 20 °C; and a 2750 A short-circuit current. A 24-cell 48 V string of these cells holds 12,000 Wh nominal, weighs 492.0 kg with electrolyte and presents 21.12 mΩ of internal resistance; a 54-cell 108 V string floats at 120.42 V, holds 27,000 Wh and weighs 1,107.0 kg. The cell is the correct choice where a manned telecom DC plant, substation or renewable cabinet benefits from long float life and low cost per usable year; where site access is unattended, the published gel alternative trades a slightly different internal resistance and charging limit for the removal of the watering cycle.

Contact CHISEN — 24-Hour Response

If you are quoting a 2 V 250 Ah cell for a 48 V DC plant, a 108 V substation in Rotterdam or a solar cabinet outside Nairobi, ask for the complete OPzS2-250 datasheet, the string layout drawing and the certification package, and ask for them in writing: email sales@chisen.cn, or message the export desk on WhatsApp at +86 131 6622 6999 (https://wa.me/8613166226999). One line describing your bus voltage, backup time and site temperature is enough for us to return the string arithmetic, the charger setpoints and the nearest capacity in the flooded range — or the gel equivalent if nobody will ever top up water on that site.

Browse the full CHISEN lead-acid range and technical data at https://leadacidbattery.cn.

Related CHISEN Product Pages

  • OPzS2-250 2V250Ah model page — full published specification set
  • OPzS2-350 2V350Ah tubular flooded cell — the next capacity step, 350 Ah
  • Tubular flooded battery range — 2 V cells from 100 Ah to 3,000 Ah

Related CHISEN Buyer Guides

  • 12V 100Ah LiFePO4 vs Lead Acid Battery: Cycle Life, Published 6-EVF-100 Specs and Where Each Chemistry Wins

    12V 100Ah LiFePO4 vs Lead Acid Battery: Cycle Life, Published 6-EVF-100 Specs and Where Each Chemistry Wins

    Answer First

    A 12V 100Ah LiFePO4 search is usually a replacement request: a telecom cabinet in Lagos, a UPS room in Lima, an AGV charging bay in Chennai, and a bank that has reached the end of its service life. Both chemistries answer the same headline — 12 V × 100 Ah = 1,200 Wh nominal — and they diverge on everything else. A lithium iron phosphate module typically delivers 3,000–5,000 cycles at 80 % depth of discharge at 25 °C, against 400–800 cycles for lead acid, needs no watering and no ventilation, and requires a battery management system and a charging profile that a lead-acid charger does not provide. A sealed lead-acid block costs roughly 30–40 % of the lithium initial cost, tolerates partial state of charge without damage, and is the default answer for float duty in telecom and UPS rooms.

    The honest summary is that the decision is not chemistry, it is duty. Deep cycling favours lithium; standing float duty with an operator and a long service life favours lead acid. This article sets the two options side by side and fills in the published figures for the CHISEN 12 V 100 Ah sealed lead-acid block, the 6-EVF-100 12V100Ah model page, so the comparison rests on numbers rather than on reputation.

    Key Takeaways

    • The energy is identical. 12 V × 100 Ah = 1,200 Wh nominal for either chemistry (Arithmetic). Chemistry changes how many times you can use that energy, not how much there is.
    • Cycle life is the dividing line. Lithium iron phosphate: 3,000–5,000 cycles at 80 % DoD at 25 °C. Lead acid: 400–800 cycles under the same discipline. The CHISEN 6-EVF-100 publishes 350–600 cycles at 50–80 % DoD (Model page).
    • The published lead-acid block: 31.5 kg, 330 × 170 × 218 mm, 20.0 A maximum charging current, float 13.5 V, equalising 14.1 V, φ20-M8 terminals (Model page).
    • Specific energy of that block: 1,200 Wh ÷ 31.5 kg = 38.1 Wh/kg (Arithmetic) — a useful benchmark to hold any lithium module against.
    • Payback is a cycle question. With lead-acid initial cost typically at 30–40 % of the lithium equivalent, lithium pays back only if the site genuinely performs thousands of cycles rather than hundreds.

    Side-by-Side: The Two 12V 100Ah Options

    Criterion12V 100Ah LiFePO412V 100Ah sealed lead acid (CHISEN 6-EVF-100)Source
    Nominal energy1,200 Wh1,200 WhArithmetic
    Rated capacity100 Ah100 Ah at C3 to 1.75 V/cellModel page / Arithmetic
    Cycle life3,000–5,000 cycles at 80 % DoD, 25 °C350–600 cycles at 50–80 % DoDLithium market data 2026 / Model page
    Float / standby voltageBMS-regulated; charger profile specific to lithium13.5 V (2.25 V/cell)Model page
    Equalising voltageBMS-regulated; charger profile specific to lithium14.1 VModel page
    Maximum charging currentSet by the module datasheet and BMS20.0 AModel page
    Block weightModule datasheet required31.5 kgModel page
    DimensionsModule datasheet required330 × 170 × 218 mmModel page
    Watering or topping upNoneNoneModel page
    Hydrogen venting in float serviceNoneNoneModel page
    Battery management systemRequiredNot requiredLithium market data 2026
    Charge at low temperatureBMS-controlled cutoff requiredRestricted below the published limitLithium market data 2026 / Industry practice
    Initial cost relative to lead acid100 % (reference)30–40 %Lithium market data 2026
    Standards normally quotedIEC 62619, UN 38.3, UL 2580GB/T 32620.1-2016, GB/T 32620.2-2016, JB/T 2599Model page / Lithium market data 2026

    Two rows deliberately say “module datasheet required” instead of a number. For a lithium module, weight, dimensions and maximum charging current depend on the enclosure, the cell format and the busbar design, and any figure supplied without a module datasheet is an estimate. Ask the supplier for the datasheet; if the figure is not in it, it does not exist.

    §1 — 6-EVF-100 12V100Ah Published Specifications

    The reference point on the lead-acid side is the 6-EVF-100, and every figure below is published.

    Parameter6-EVF-100 published valueSource
    Nominal voltage12 VModel page
    Nominal capacity100 Ah at C3 (3-hour rate)Model page
    Discharge end voltage1.75 V/cellModel page
    Nominal energy1,200 Wh (12 V × 100 Ah)Arithmetic
    Float voltage13.5 V (2.25 V/cell)Model page
    Equalising voltage14.1 VModel page
    Maximum charging current20.0 AModel page
    Cycle life350–600 cycles at 50–80 % DoDModel page
    Dimensions L × W × H330 × 170 × 218 mmModel page
    Total height218 mmModel page
    Weight31.5 kg (± 0.2 kg)Model page
    Specific energy38.1 Wh/kg (1,200 Wh ÷ 31.5 kg)Arithmetic
    Terminalφ20-M8Model page
    StandardsGB/T 32620.1-2016, GB/T 32620.2-2016, JB/T 2599Model page
    CertificationsCE, RoHS, REACH, MSDSModel page

    For context within the same range: the 6-EVF-80 is 25.7 kg at 259 × 170 × 218 mm with a 16.0 A charging limit, the 6-EVF-120 is 40.0 kg at 407 × 170 × 240 mm with a 24.0 A limit, and the 6-EVF-150 is 48.5 kg at 483 × 170 × 240 mm with a 30.0 A limit (Model page). Charging current scales with capacity, so the charger decision is made once for a whole site.

    §2 — The Pain: Where the Drop-In Replacement Claim Breaks

    The phrase “12V 100Ah LiFePO4 replacement for lead acid” appears in almost every enquiry, and it is the phrase that causes the most expensive mistakes. The nameplate matches — 12 V, 100 Ah, 1,200 Wh — and everything behind the nameplate does not.

    The charger. A sealed lead-acid bank floats at 13.5 V and equalises at 14.1 V (Model page). A lithium iron phosphate bank is charged with a lithium-specific profile that includes a controlled bulk stage, a regulated float and a BMS-managed cutoff. If the existing telecom rectifier or solar controller keeps running the lead-acid profile, a lithium bank will sit chronically undercharged, will report a misleading state of charge, and will age in a way that has nothing to do with its cycle rating. This is the single most common failure in chemistry swaps.

    The battery management system. A lead-acid bank has no electronics; a lithium module has balancing, over- and under-voltage protection, temperature sensing and usually a communications output that the site’s monitoring layer has to read. If the cabinet has no controller that can accept those signals, the lithium option loses the visibility that makes it attractive in the first place.

    Cold charging. Lithium charging below freezing must be managed by the BMS; a lead-acid bank has its own, different, published limits. A site in Scandinavia, inland Canada or a high-altitude site in the Andes needs this checked before the module is ordered, not after it is installed.

    Weight and structure. The published lead-acid block weighs 31.5 kg (Model page) and a 12V 100Ah LiFePO4 module’s weight depends on the enclosure and the cell format. Any lithium weight quoted without a module datasheet is an estimate, and it is usually an optimistic one. Ask for the datasheet.

    Partial state of charge. Lead acid is tolerant of being left partially discharged and recharged; lithium is more sensitive to being parked deep. For a bank that spends weeks at low state of charge because the mains is stable, that tolerance is worth real money.

    End of life economics. Lead-acid blocks are routinely replaced on a fixed calendar at a known cost. Lithium modules carry a cycle and throughput warranty instead. Those two cost models must be compared over the same period — five years, ten years — not against each other’s purchase price.

    §3 — The Choice: Which Chemistry for Which Duty

    ApplicationRecommended routeWhy
    Telecom DC plant, float duty, permanent operatorSealed lead acid block (6-EVF-100 class)350–600 cycles at 50–80 % DoD is enough for float service; lowest installed cost; no BMS to integrate
    Telecom cabinet with frequent grid failuresLithium iron phosphateThousands of cycles remove the calendar replacement; no watering; telemetry through the BMS
    UPS room in a hospital or data roomDepends on discharge frequencyLead acid for rare deep events; lithium for frequent deep events
    Solar cabinet with no site accessEither, with the access factor weightedBoth sealed; lithium wins on cycle count, lead acid wins on installed cost and on partial-charge tolerance
    Daily deep cycling, AGV and light forklift dutyLithium iron phosphateCycle life is the deciding factor; this is outside the 12 V 100 Ah class and needs a duty-rated product
    Retrofit onto an existing lead-acid chargerSealed lead acid blockA lithium bank on a lead-acid profile is a warranty and safety problem

    Two operational facts anchor this table. In a fleet application, a forklift standing idle for a shift can cost $350–600 a day in lost production, which is why cycle life is valued so differently there than in a fixed float installation. And the industrial lithium battery market passed US$8 billion in 2026, which is why the cost gap has narrowed — but the 30–40 % relative initial cost of lead acid still means payback requires thousands of real cycles, not the headline cycle number.

    §4 — The Framework: Seven Checks Before You Replace a Bank

    Q1. Match usable energy, not nameplate capacity. Both chemistries here are 1,200 Wh nominal (Arithmetic). Compare what each can deliver to the load before the low-voltage cutoff, at the site’s temperature, at the discharge rate you actually impose.

    Q2. Check the charger and the controller before the chemistry. Confirm the rectifier’s float, equalising and bulk stages, and confirm the controller can read a BMS output if lithium is chosen.

    Q3. Count the real cycles. Multiply deep discharges per year by years of service and compare that number with each option’s cycle rating. A site with 30 deep discharges a year cannot amortise a 3,000-cycle battery; a site with 250 can.

    Q4. Establish the temperature envelope. Both products have limits; lithium has the stricter cold-charge rule. Log the minimum site temperature, not the average.

    Q5. Verify the weight and the mounting. The 6-EVF-100 is 31.5 kg at 330 × 170 × 218 mm (Model page). For lithium, require the module datasheet with weight, dimensions and the maximum charging current before the purchase order is released.

    Q6. Budget the monitoring. Lithium means BMS data, and that means a controller, a communications route and an alarm policy. Price it in.

    Q7. Write the warranty terms into the contract. For lead acid, calendar years and capacity retention at the end of that period; for lithium, cycles, throughput in Wh, and the ambient temperature band the warranty assumes.

    §5 — The Trust: How to Qualify a 12V 100Ah LiFePO4 Supplier

    Ask for six documents, in writing, before the deposit. The module datasheet — cell manufacturer, rated capacity and test rate, cycle test curve with temperature and depth of discharge stated, weight and dimensions. The BMS specification — balancing method, over-charge and over-discharge thresholds, temperature sensor count, and the communications protocol. The certification package — IEC 62619, UN 38.3 and UL 2580 certificates for the module and the cells inside it. The charger curve — bulk, absorption, float and low-temperature cutoff values, matched to the module. The warranty — years, cycles, throughput in Wh, and the temperature band it assumes. The recycling and take-back route — end-of-life handling is a logistics question with a real cost attached.

    Then test the answers against what a published lead-acid datasheet looks like. The 6-EVF-100 12V100Ah publishes capacity rate, end voltage, float and equalising voltage, maximum charging current, cycle life with depth of discharge, dimensions, weight with tolerance, terminal type, standards and certifications (Model page). A lithium supplier who cannot match that level of disclosure is not quoting a product, they are quoting a chemistry.

    One last check on the manufacturing side. CHISEN runs eight production bases with roughly 70 million kVAh of annual capacity under ISO 9001 and ISO 14001 management systems and supplies more than 60 countries, which is the difference between a cell that can be traced to a production batch and one that cannot. The CHISEN company profile publishes the manufacturing scale, and the sealed range is listed under AGM batteries.

    §6 — FAQ

    Q1. How much energy is a 12V 100Ah battery? 1,200 Wh nominal for either chemistry, calculated as 12 V × 100 Ah (Arithmetic). Real usable energy depends on the cutoff voltage, the temperature and the discharge rate.

    Q2. How many cycles does a 12V 100Ah LiFePO4 battery give? Typically 3,000–5,000 cycles at 80 % depth of discharge at 25 °C, against 400–800 cycles for lead acid under the same discipline (Lithium market data 2026). The published CHISEN 6-EVF-100 lead-acid rating is 350–600 cycles at 50–80 % DoD (Model page).

    Q3. Can I replace a lead acid battery with lithium one-for-one? Not as a drop-in. The energy matches at 1,200 Wh nominal, but the charging profile, the BMS, the monitoring and the cold-charge rule all differ, and the existing controller has to be checked first.

    Q4. What does the CHISEN 6-EVF-100 12V100Ah weigh? 31.5 kg, ± 0.2 kg, in a 330 × 170 × 218 mm case (Model page). Specific energy is 38.1 Wh/kg (1,200 Wh ÷ 31.5 kg, Arithmetic).

    Q5. What float and equalising voltage does the 6-EVF-100 use? 13.5 V float (2.25 V per cell) and 14.1 V equalising, with a 20.0 A maximum charging current (Model page).

    Q6. Is a 12V 100Ah LiFePO4 module lighter than the lead acid block? It depends entirely on the enclosure and the cell format, so the answer must come from the module datasheet. Do not accept a weight figure without one.

    Q7. Which is cheaper to buy? A lead-acid bank typically starts at 30–40 % of the lithium initial cost (Lithium market data 2026). Lithium pays back only where the site performs thousands of cycles.

    Q8. Do either of them need watering or ventilation? Neither, in normal float service — both products are sealed, which is exactly why the 6-EVF-100 class is specified for roadside cabinets in Indonesia, Chile and Nigeria.

    Q9. Which one for a telecom DC plant? A sealed lead acid block such as the 6-EVF-100 for float duty with a permanent operator, and lithium iron phosphate where grid failures are frequent enough to justify thousands of cycles and where BMS telemetry can be integrated.

    Q10. What standards should I see? For the lead-acid block: GB/T 32620.1-2016, GB/T 32620.2-2016 and JB/T 2599, with CE, RoHS and REACH documentation (Model page). For a lithium module: IEC 62619, UN 38.3 and UL 2580.

    Expert Summary

    A 12V 100Ah LiFePO4 battery and a 12V 100Ah sealed lead-acid battery both deliver 1,200 Wh nominal (12 V × 100 Ah). Lithium iron phosphate is rated for 3,000–5,000 cycles at 80 % depth of discharge at 25 °C against 400–800 cycles for lead acid, requires a battery management system and a lithium charging profile, and costs roughly 2.5 to 3.3 times more up front. The published CHISEN 6-EVF-100 12V100Ah sealed AGM block delivers 100 Ah at the 3-hour rate to 1.75 V per cell, floats at 13.5 V (2.25 V per cell), equalises at 14.1 V, accepts 20.0 A maximum charging current, is rated at 350–600 cycles at 50–80 % DoD, weighs 31.5 kg ± 0.2 kg in a 330 × 170 × 218 mm case with φ20-M8 terminals, and is documented to GB/T 32620.1-2016, GB/T 32620.2-2016 and JB/T 2599 with CE, RoHS, REACH and MSDS. Specific energy is 38.1 Wh/kg (1,200 Wh ÷ 31.5 kg). Standby float duty in telecom and UPS installations is still served best by sealed lead acid, while daily deep cycling and sites with frequent outages are where lithium earns its premium.

    Contact CHISEN

    If you are replacing a 12 V 100 Ah bank in a telecom cabinet, a UPS room or a solar enclosure, send us the discharge profile, the ambient temperature range, the backup time and the existing charger model, and we will return the block configuration, the float and equalising setpoints, the string arithmetic and the alternative within the sealed range: email sales@chisen.cn, or message the export desk on WhatsApp at +86 131 6622 6999 (https://wa.me/8613166226999).

    Browse the full CHISEN lead-acid range and technical data at https://leadacidbattery.cn.

    Related CHISEN Product Pages

  • 6-EVF-150 12V150Ah AGM Battery: Published Specs, Parallel String Sizing and EVF Range Comparison

    6-EVF-150 12V150Ah AGM Battery: Published Specs, Parallel String Sizing and EVF Range Comparison

    Answer First

    The 6-EVF-150 12V150Ah is a 12 V, 150 amp-hour sealed AGM VRLA block rated at the 3-hour rate to 1.75 V per cell, with a published weight of 48.5 kg, a footprint of 483 × 170 × 240 mm, a 30.0 A maximum charging current, float operation at 13.5 V and equalising at 14.1 V — and it is the correct block when a telecom power cabinet, an emergency supply or a solar-reserve branch needs roughly 1.8 kWh of stored energy per unit with no watering, no hydrogen venting and no on-site operator.

    Because it is sealed and maintenance-free, it is also the block that gets specified with the least thought. Two 6-EVF-150 units in parallel give a 24 V, 300 Ah bank at 3,600 Wh and 97.0 kg (Arithmetic); that arithmetic, the 30.0 A charging limit and the ambient temperature the cabinet actually sees decide whether the installation works, long before the chemistry does.

    Full published data for this block is on the 6-EVF-150 12V150Ah model page, and the wider sealed AGM range sits under AGM batteries.

    Key Takeaways

    • Capacity: 150 Ah at the 3-hour rate (C3) to 1.75 V/cell, and 1,800 Wh nominal per block (Datasheet / Arithmetic).
    • Charging setpoints: float 13.5 V (2.25 V/cell), equalising 14.1 V, with a 30.0 A maximum charging current (Model page).
    • Mechanical: 483 × 170 × 240 mm, 48.5 kg, φ20-M8 terminal (Model page).
    • Cycle life: 350–600 cycles at 50–80 % depth of discharge (Model page) — this is a float-first block, not a traction battery.
    • String arithmetic: two blocks in parallel give 24 V, 300 Ah, 3,600 Wh and 97.0 kg; the same energy in 12 V single blocks needs four units at 48.5 kg each (Arithmetic).

    §1 — 6-EVF-150 12V150Ah Published Specifications

    Parameter6-EVF-150 published valueSource
    Nominal voltage12 VModel page
    Nominal capacity150 Ah at C3 (3-hour rate)Model page
    Discharge end voltage1.75 V/cellModel page
    Nominal energy1,800 Wh (12 V × 150 Ah)Arithmetic
    Float voltage13.5 V (2.25 V/cell)Model page
    Equalising voltage14.1 VModel page
    Maximum charging current30.0 AModel page
    Cycle life350–600 cycles at 50–80 % DoDModel page
    Dimensions L × W × H483 × 170 × 240 mmModel page
    Total height240 mmModel page
    Weight48.5 kg (± 0.2 kg)Model page
    Specific energy37.1 Wh/kg (1,800 Wh ÷ 48.5 kg)Arithmetic
    Terminalφ20-M8Model page
    StandardsGB/T 32620.1-2016, GB/T 32620.2-2016, JB/T 2599Model page
    CertificationsCE, RoHS, REACH, MSDSModel page
    Two blocks in parallel24 V, 300 Ah, 3,600 Wh, 97.0 kgArithmetic
    Four blocks in series48 V, 150 Ah, 1,800 Wh, 194.0 kgArithmetic

    Figures marked Model page come from the published English product page; figures marked Arithmetic are derived from published values and show the calculation. Values marked Datasheet in other CHISEN documentation for this block are consistent with the rows above.

    §2 — The Pain: Where 12V 150Ah Projects Go Wrong

    The most common error is treating a sealed block as though it can absorb any charging regime. The 6-EVF-150 has a published maximum charging current of 30.0 A (Model page). Two blocks in parallel therefore accept 60.0 A of charge (2 × 30.0 A, Arithmetic). A controller that delivers the full output of a 1.5 kW solar array straight into a 300 Ah bank will not be limited by the array — it will be limited by the blocks, and the blocks will be the component that ages first. Setting the charge current to roughly one tenth of bank capacity, 30 A for a 300 Ah bank, is the conservative starting point that keeps the blocks inside their published envelope.

    The second error is ignoring the depth-of-discharge window. The published cycle life of 350–600 cycles applies at 50–80 % depth of discharge (Model page). A bank that is regularly taken to 95 % will deliver far fewer cycles than the headline number, and in a telecom cabinet the routine load on a float system is small, so the deep-discharge cases are the rare events — the storm, the mains outage, the generator start. Designing for the rare event at full depth and for the daily event at shallow depth is the correct way to read the cycle figure.

    The third error is temperature. The published capacity is quoted at standard test conditions; a cabinet in Chennai, Jeddah, Manila or a Rotterdam container in January does not deliver 150 Ah. The float voltage of 13.5 V is a 25 °C figure in normal practice, and the charger has to compensate downward as the cabinet heats. Manufacturers publish a temperature-compensation figure for this reason. If your supplier cannot state the compensation for the 6-EVF-150, you do not have a complete specification.

    The fourth error is logistics and handling. At 48.5 kg, a 6-EVF-150 is a two-person lift with a trolley, not a one-person carry, and a cabinet that holds four in series weighs 194.0 kg (Arithmetic) before the tray, the busbars and the charger. Floor loading, aisle width, cabinet rail rating and the shipping plan all need the published weight, not the catalogue weight.

    §3 — The Choice: The 6-EVF-150 Against the Published EVF Range

    The EVF range is a ladder of capacities, and buyers usually need one step above or below 150 Ah. The published data for the neighbouring models is set out below, with no qualitative claims.

    ModelCapacity at C3WeightDimensions L × W × HTotal heightMax charging current
    6-EVF-6060 Ah18.8 kg258 × 170 × 160 mm160 mm12.0 A
    6-EVF-7070 Ah23.3 kg259 × 170 × 210 mm210 mmnot published
    6-EVF-8080 Ah25.7 kg259 × 170 × 218 mm218 mm16.0 A
    6-EVF-100100 Ah31.5 kg330 × 170 × 218 mm218 mm20.0 A
    6-EVF-120120 Ah40.0 kg407 × 170 × 240 mm240 mm24.0 A
    6-EVF-135135 Ah45.0 kg338 × 172 × 280 mm280 mmnot published
    6-EVF-150150 Ah48.5 kg483 × 170 × 240 mm240 mm30.0 A

    Sources: capacity, weight, dimensions and total height from the published EVF comparison table on the model page; maximum charging current for the 6-EVF-150 and the 6-EVF-100 from their model pages, and for the 6-EVF-60, 6-EVF-80 and 6-EVF-120 from the published EVF data set; two rows where the charging current is not published on the model page are marked accordingly rather than estimated.

    Three patterns in that table decide a specification. First, specific energy stays near 37 Wh/kg across the range: 1,800 Wh ÷ 48.5 kg = 37.1 Wh/kg for the 6-EVF-150, and 1,200 Wh ÷ 31.5 kg = 38.1 Wh/kg for the 6-EVF-100 (Arithmetic). Second, the charging current scales with capacity, from 12.0 A at 60 Ah to 30.0 A at 150 Ah, which means the charger is sized once and reused across the range. Third, the footprint changes with capacity rather than staying constant: 258 mm at 60 Ah, 330 mm at 100 Ah, 407 mm at 120 Ah and 483 mm at 150 Ah. A cabinet designed around the 6-EVF-100 will not accept the 6-EVF-150 without a new tray and a new door clearance check.

    For a buyer who needs 24 V rather than 12 V, two 6-EVF-150 units in parallel give 24 V, 300 Ah and 3,600 Wh at 97.0 kg (Arithmetic). For 48 V, four units in series give 48 V, 150 Ah, 1,800 Wh and 194.0 kg (Arithmetic). The energy is identical in both cases; what changes is the current the busbar has to carry and the number of strings that must be kept in balance. If your load is high-current and short-duration, the two-block-parallel arrangement is easier on the cabling; if your load is low-current and long-duration, the four-block-series arrangement cuts the losses. The 6-EVF-100 12V100Ah model page carries the published data for the 100 Ah step if that is the closer match to your load profile.

    §4 — The Framework: Seven Hard Checks Before You Sign

    Q1. Confirm the rate, not just the amp-hour number. The 6-EVF-150 is rated at the 3-hour rate to 1.75 V/cell (Model page). If your specification needs 150 Ah at the 10-hour rate, the 6-EVF-150 does not give it, and the catalogue headline is not the number you are buying. Ask for the discharge table.

    Q2. Size the charger against the 30.0 A block limit, not the array. For a 300 Ah bank of two blocks the acceptance ceiling is 60.0 A (2 × 30.0 A, Arithmetic). A float rectifier set to 0.1 × bank capacity — 30 A for this bank — keeps the blocks inside their published envelope while still restoring a deep discharge overnight.

    Q3. Check the float voltage and the compensation curve together. 13.5 V float and 14.1 V equalising (Model page) are 25 °C values. A charger that delivers a flat 13.5 V all year over-charges the bank in summer and under-charges it in winter, and the symptom appears as lost capacity a year later rather than as a fault.

    Q4. Match the enclosure to the published dimensions. 483 × 170 × 240 mm, 48.5 kg, φ20-M8 terminals. The rail spacing, the terminal clearance and the two-person handling requirement all follow from that row of the table, and the tray must be rated for 194.0 kg for a four-block series stack (Arithmetic).

    Q5. Set the depth-of-discharge budget explicitly. 350–600 cycles applies at 50–80 % DoD (Model page). Write the routine discharge depth into the design document, because the rare deep event is the one that determines whether the bank survives a hot-season outage in a Tel Aviv or Lagos cabinet.

    Q6. Decide parallel strings early. Two blocks in parallel mean two sets of terminals to keep clean, two fuses or breakers to coordinate and a routine equalising check so that the two strings stay matched. The savings from a larger single block are usually smaller than the cost of a mismatched parallel string.

    Q7. Collect the documentation before the deposit. GB/T 32620.1-2016 and GB/T 32620.2-2016, JB/T 2599, CE, RoHS, REACH and the safety data sheet are published for this block (Model page). A supplier who quotes a 12 V 150 Ah block without them is buying from a trading company, and the warranty will follow the paperwork, not the cell.

    §5 — The Trust: What a Datasheet Must State — and What to Reject

    The most common defect in a sealed 12 V quotation is silence. Ask for six things and the quality of the supplier becomes obvious in one exchange. What is the rated rate and end voltage? For the 6-EVF-150 it is C3 to 1.75 V/cell. What is the weight? 48.5 kg, with a tolerance of ± 0.2 kg. What are the dimensions and the total height? 483 × 170 × 240 mm, total height 240 mm. What is the maximum charging current? 30.0 A. What is the float and equalising voltage? 13.5 V and 14.1 V. What is the cycle life and at what depth of discharge? 350–600 cycles at 50–80 %.

    Against that, reject quotations that give a float voltage of 14.4 V for a sealed block, or that quote 13.5 V without a temperature-compensation figure, or that describe a 12 V 150 Ah block as a “20-year” float asset. A 12 V VRLA block does not carry the 20+ year float-life figure quoted for the 2 V tubular class; mixing the two figures is the single most common error in mixed product lines, and it is usually caused by copying a line from the wrong datasheet. The published 6-EVF-150 specification is float 13.5 V, equalising 14.1 V, 350–600 cycles at 50–80 % DoD, 48.5 kg, 483 × 170 × 240 mm, 30.0 A maximum charging current.

    A second quality signal is the manufacturing scale behind the quotation. CHISEN runs eight production bases with roughly 70 million kVAh of annual capacity under ISO 9001 and ISO 14001 management systems, and supplies more than 60 countries, which is what makes a 150 Ah block traceable when a shipment is delayed in transit or a warranty claim has to be traced back to a production batch. The company profile is published on the CHISEN company page.

    §6 — FAQ

    Q1. What is the rated capacity of the 6-EVF-150 12V150Ah? 150 Ah at the 3-hour rate (C3) with a 1.75 V per cell end voltage, which is 1,800 Wh nominal per block (Model page / Arithmetic).

    Q2. How many blocks do I need for a 24 V system? Two, in parallel, giving 24 V, 300 Ah, 3,600 Wh and a combined weight of 97.0 kg (Arithmetic). For a 48 V bus, four in series give 48 V, 150 Ah, 1,800 Wh and 194.0 kg (Arithmetic).

    Q3. What float and equalising voltage should the charger use? 13.5 V float (2.25 V per cell) and 14.1 V equalising, both referenced to 25 °C, with temperature compensation applied by the charger (Model page).

    Q4. What is the maximum charging current? 30.0 A per block (Model page), so 60.0 A for a two-block parallel bank (Arithmetic).

    Q5. How many cycles does the block deliver? 350–600 cycles at 50–80 % depth of discharge (Model page). Routine shallow discharge in float service is far kinder to the block than repeated deep discharge.

    Q6. How heavy is one block and how many people does it take? 48.5 kg ± 0.2 kg (Model page) — a trolley-assisted two-person lift, with the tray and rails rated for the full stack.

    Q7. What are the terminal type and the standards? φ20-M8 terminals, with GB/T 32620.1-2016, GB/T 32620.2-2016 and JB/T 2599, supplied with CE, RoHS, REACH and the safety data sheet (Model page).

    Q8. How does it compare with the 6-EVF-100? Half the energy at two thirds of the weight: 100 Ah, 31.5 kg, 330 × 170 × 218 mm and a 20.0 A charging limit, against 150 Ah, 48.5 kg, 483 × 170 × 240 mm and 30.0 A for the 6-EVF-150 (Model page). The specific energy is 38.1 Wh/kg and 37.1 Wh/kg respectively (Arithmetic).

    Q9. Can the 6-EVF-150 be used for cycling applications? It is rated for 350–600 cycles at 50–80 % DoD, which makes it a stationary float block with cycling capability, not a traction battery. For daily deep cycling, ask for a block rated for that duty explicitly.

    Q10. Does it need maintenance? No watering, no venting and no routine equalising beyond the charger’s own programme — that is the reason a 12 V 150 Ah sealed block is specified for roadside cabinets in Nigeria, Indonesia and Chile. Periodic capacity verification during the warranty period is still worth scheduling.

    Expert Summary

    The 6-EVF-150 12V150Ah is a sealed 12 V AGM VRLA block with a published capacity of 150 Ah at the 3-hour rate to 1.75 V per cell, giving 1,800 Wh nominal energy; float operation at 13.5 V (2.25 V per cell) with equalising at 14.1 V; a 30.0 A maximum charging current; 350–600 cycles at 50–80 % depth of discharge; published dimensions of 483 × 170 × 240 mm with a total height of 240 mm; a weight of 48.5 kg ± 0.2 kg; φ20-M8 terminals; and GB/T 32620.1-2016, GB/T 32620.2-2016 and JB/T 2599 compliance with CE, RoHS and REACH documentation. Specific energy is 37.1 Wh/kg (1,800 Wh ÷ 48.5 kg). Two blocks in parallel deliver a 24 V, 300 Ah, 3,600 Wh bank weighing 97.0 kg, and four in series deliver 48 V, 150 Ah and 1,800 Wh weighing 194.0 kg. The 6-EVF-150 is the correct choice for telecom cabinets, emergency supplies, solar-reserve branches and UPS rooms where maintenance-free operation, a published charging-current limit and a documented cycle life matter more than the lowest cost per installed amp-hour.

    Contact CHISEN

    If you are quoting a 12 V 150 Ah block for a telecom cabinet, a substation, a hospital supply or a solar-reserve branch, ask for the full 6-EVF-150 data sheet, the discharge table and the certification package: email sales@chisen.cn, or message the export desk on WhatsApp at +86 131 6622 6999 (https://wa.me/8613166226999). Send one line with your bus voltage, backup time, load peak current and the ambient temperature range, and we will return the block count, the charger sizing, the parallel-string arrangement and the nearest capacity in the sealed range.

    Browse the full CHISEN lead-acid range and technical data at https://leadacidbattery.cn.

    Related CHISEN Product Pages

    Related CHISEN Buyer Guides

  • OPzS2-100 2V100Ah Flooded Tubular Battery: Published Specs, 48 V String Sizing and Sibling Comparison

    OPzS2-100 2V100Ah Flooded Tubular Battery: Published Specs, 48 V String Sizing and Sibling Comparison

    Answer First

    The OPzS2-100 2V100Ah is a 2 V, 100 amp-hour flooded tubular vented lead-acid cell rated at the 10-hour rate — 10 A for 10 hours down to 1.80 V per cell at 20 °C — and it is the correct cell for a telecom DC plant, a roadside substation or a solar-powered cabinet that needs a 48 V bus holding about 4.8 kWh nominal per string, on a site where somebody will still read the electrolyte level and top up distilled water every quarter.

    It is not a sealed block. Hydrogen venting, acid-proof flame-retardant vent plugs, scheduled water top-up and periodic equalisation are part of the product, not optional extras, and a project that treats the OPzS2-100 2V100Ah as a drop-in sealed cabinet battery discovers the difference in the first hot season.

    The complete published data set for this cell sits on the OPzS2-100 2V100Ah model page, and the rest of the flooded range is listed under tubular flooded lead-acid batteries.

    Key Takeaways

    • Capacity is rate-dependent. The nameplate figure is 100 Ah at C10 (10 A to 1.80 V/cell at 20 °C). At longer rates the cell delivers more: 107 Ah at C24, 111 Ah at C48, 115 Ah at C72, 120 Ah at C100, 122 Ah at C120 and 130 Ah at C240 (Datasheet).
    • Charging setpoints are fixed by the datasheet. Float 2.23 V/cell at 25 °C, equalising 2.35 V/cell at 25 °C, temperature compensation −3 mV/°C/cell, designed float life 20+ years at 20 °C (Datasheet). Solar and wind sites use the 2.27 ± 0.005 V/cell float and 2.40 ± 0.01 V/cell equalising setpoints (Datasheet).
    • Mechanical data is what decides the rack. Body 103 × 206 × 354 mm, 409 mm total height over the terminals, 8.0 kg without electrolyte and 12.6 kg with electrolyte (Datasheet).
    • Two limits protect the cell. Maximum charging current is 20 A (0.20 × C10) and internal resistance is about 1.0 mΩ fully charged at 20 °C, with a 1500 A short-circuit current (Datasheet / Model page).
    • A 48 V string is simple arithmetic. 24 cells give 4,800 Wh nominal, 302.4 kg with electrolyte (24 × 12.6 kg) and 24.0 mΩ of internal resistance (24 × 1.0 mΩ) (Arithmetic).

    §1 — OPzS2-100 2V100Ah Published Specifications

    ParameterOPzS2-100 published valueSource
    Nominal voltage2 VDatasheet
    Nominal capacity100 Ah at C10 (10 A, 1.80 V/cell, 20 °C)Datasheet
    Capacity at C24 / C48 / C72107 Ah / 111 Ah / 115 AhDatasheet
    Capacity at C100 / C120 / C240120 Ah / 122 Ah / 130 AhDatasheet
    Energy at 1 h / 3 h / 5 h / 10 h108 Wh / 137 Wh / 163 Wh / 198 WhDatasheet
    Energy at 24 h / 48 h / 72 h / 100 h214 Wh / 220 Wh / 225 Wh / 240 WhDatasheet
    Energy at 120 h / 240 h247 Wh / 261 WhDatasheet
    Float voltage2.23 V/cell at 25 °CDatasheet
    Equalising voltage2.35 V/cell at 25 °CDatasheet
    Float setpoint, solar and wind2.27 ± 0.005 V/cellDatasheet
    Equalising setpoint, solar and wind2.40 ± 0.01 V/cellDatasheet
    Temperature compensation−3 mV/°C/cellDatasheet
    Designed float life20+ years at 20 °CDatasheet
    Dimensions L × W × H103 × 206 × 354 mmDatasheet
    Total height over terminals409 mmDatasheet
    Weight without electrolyte8.0 kgDatasheet
    Weight with electrolyte12.6 kgDatasheet
    Maximum charging current20 A (0.20 × C10)Datasheet
    Internal resistance1.0 mΩ, fully charged at 20 °CDatasheet
    Short-circuit current1500 AModel page
    TerminalCopper female insert M8, torque 10–12 N·mDatasheet
    Electrolyte density1.24 g/cm³ at 20 °CDatasheet
    Discharge temperature range−40 °C to 60 °CModel page

    Every row above is traceable: values taken from the manufacturer’s OPzS2-100 datasheet are marked Datasheet, values taken from the published English product page are marked Model page, and derived figures are marked Arithmetic wherever they appear in the text. If a supplier cannot tell you which of the three a given figure is, treat the figure as unverified.

    §2 — The Pain: Where 2V 100Ah Projects Go Wrong

    The first failure is a specification failure. Buyers routinely receive a quote that says only “2V 100Ah tubular” and treat every 2V 100Ah cell in the world as interchangeable. The published OPzS2-100 data makes the differences explicit: capacity at C10 is 100 Ah, but capacity at C24 is 107 Ah and at C240 is 130 Ah. A bank sized on the C10 number for a slow-discharge backup duty is undersized; a bank sized on the C240 number for a five-hour discharge duty is over-purchased. Both mistakes trace back to a quotation that never stated the rate and the end voltage.

    The second failure is thermal. A 48 V string of 24 OPzS2-100 cells accepts a maximum charging current of 20 A per cell, so a charger set to deliver more — which happens when the charger is sized for the string’s nominal power rather than for the cells’ acceptance — pushes the electrolyte into gassing and dries the separator faster than the topping-up interval can repair. The same string on a solar site needs the higher 2.27 ± 0.005 V/cell float and the 2.40 ± 0.01 V/cell equalising setpoint; on a mains-float site the correct values are 2.23 V/cell and 2.35 V/cell at 25 °C. These are not interchangeable, and a controller left on the wrong setpoint is the classic cause of premature capacity loss.

    The third failure is weight and access planning. The OPzS2-100 is 8.0 kg without electrolyte and 12.6 kg with electrolyte, and the full height over the terminals is 409 mm, not the 354 mm body height. A 24-cell string with electrolyte weighs 302.4 kg (24 × 12.6 kg, Arithmetic). Cabinets, plinths and lifting plans are usually drawn against the body height and a lighter shipping weight, and the result is a string that does not fit the rack and a handling plan that understates the load.

    The fourth failure is assuming sealed behaviour. This cell vents hydrogen during overcharge, needs acid-proof flame-retardant vent plugs, needs distilled water, and needs a scheduled equalising period. Those four obligations are why the OPzS2-100 2V100Ah wins in cabinets with a permanent operator and loses in unmanned roadside or container sites.

    §3 — The Choice: The OPzS2-100 Against Its Published Siblings

    Buyers comparing cells inside the 100 Ah to 200 Ah window are usually choosing between a flooded cell and a gel cell, or between three flooded capacities. The table below uses published values only — no qualitative claims.

    ModelCapacity at C10Weight dry / with electrolyteDimensions L × W × HTotal heightMax charging currentInternal resistanceShort-circuit current
    OPzS2-100100 Ah8.0 kg / 12.6 kg103 × 206 × 354 mm409 mm20 A1.0 mΩ at 20 °C1500 A
    OPzS2-150150 Ah10.5 kg / 14.5 kg103 × 206 × 354 mm409 mm30 A1.2 mΩ at 20 °C2400 A
    OPzS2-200200 Ah13.0 kg / 17.5 kg103 × 206 × 354 mm409 mm40 A0.95 mΩ at 25 °C2600 A
    OPzV2-100 (gel)100 Ah13.2 kg103 × 206 × 354 mm390 mm30 A1.1 mΩnot published

    Sources: OPzS2-100 and OPzS2-150 from their datasheets; OPzS2-200 weight from its datasheet, with internal resistance, charging current and short-circuit current from its model page; OPzV2-100 from the model page and its datasheet (Arithmetic for the comparison itself).

    Four numbers drive the decision. First, dry weight: 8.0 kg, 10.5 kg and 13.0 kg for the three flooded cells — a cell that must be carried up a ladder or into a pit should be chosen with the wet weight in mind, not the dry one. Second, the charging current limit of 20 A, 30 A and 40 A, which must be matched to the charger output. Third, internal resistance, which falls from 1.0 mΩ to 0.95 mΩ as capacity rises, so a 24-cell string of the 200 Ah cell presents 22.8 mΩ (24 × 0.95 mΩ, Arithmetic) against 24.0 mΩ for the 100 Ah cell (24 × 1.0 mΩ, Arithmetic) — a 5 % difference in string voltage drop under the same load, which matters when the string is long and the load is heavy.

    The fourth number is the maintenance profile, and here the published data is unambiguous. The flooded OPzS2-100 carries 12.6 kg of electrolyte in an open container that must be topped up and periodically equalised. The gel OPzV2-100 carries the same 103 × 206 mm footprint with a 390 mm total height, weighs 13.2 kg with the electrolyte immobilised in the gel, and needs no watering — the price of that is a 1.1 mΩ internal resistance, a 30 A charging limit and a shorter life under deep cycling. For a manned substation with a technician on call, the flooded cell usually delivers the lower cost per usable year; for a sealed container with no access, the gel cell removes a whole maintenance category. Both routes are legitimate, and the published figures above are what the comparison should be built on.

    The same discipline applies further up the size range. If your string is larger than 200 Ah per cell, move to the OPzS flooded range overview rather than scaling the numbers in this table proportionally — plate thickness, internal volume and electrolyte quantity change non-linearly with capacity.

    §4 — The Framework: Seven Hard Checks Before You Sign

    Q1. Match the charger to the cell’s acceptance, not to the string. The maximum charging current of the OPzS2-100 is 20 A (0.20 × C10, Datasheet). A 24-cell string therefore accepts at most 480 A (24 × 20 A, Arithmetic). Most telecom float rectifiers are sized well below that, which is correct; a solar controller set to the array’s full output is where the limit gets breached.

    Q2. Apply temperature compensation to the setpoint, not to the battery. The published compensation is −3 mV/°C/cell (Datasheet), so a cell at 35 °C needs its 2.23 V/cell float reduced by 0.036 V. Controllers that ignore this are permanently overcharging the string in the hot season and permanently undercharging it in winter.

    Q3. Design for the float life at the site’s real temperature. The 20+ year design figure is quoted at 20 °C (Datasheet). A cabinet in the tropics, on a roof in Chennai or an outdoor enclosure in Lagos will not deliver that figure, and the honest way to plan a replacement interval is to take the 20 °C number and treat every 10 °C of ambient uplift as a materially shorter service life. Projects that publish a 20-year asset life for a string sitting in a 35 °C room have not done the arithmetic.

    Q4. Plan the watering interval from the real charging regime. A cell that is floated at 2.23 V/cell at 25 °C and never equalised loses water slowly; a cell that is equalised at 2.35 V/cell twice a month in a hot climate loses water fast enough to need attention on a monthly cycle. Put the interval in the maintenance contract, and put the electrolyte density check (1.24 g/cm³ at 20 °C, Datasheet) on the same schedule.

    Q5. Size the interconnects and torque them correctly. The terminal is a copper female insert M8 with a published torque of 10–12 N·m (Datasheet). Under-torqued terminals generate heat at the joint; over-torqued ones damage the insert. For a 24-cell string the interconnect carries the full string current, so the cable cross-section is set by that current and the 1500 A short-circuit current (Model page) determines how quickly the fault must be cleared.

    Q6. Decide how many strings run in parallel, and how they will be equalised. Two parallel strings of 12 cells in series each will drift apart unless the charger has an equalising stage and the operator runs it. Parallel strings also multiply the water-top-up workload and the total string weight: 24 × 12.6 kg = 302.4 kg per 100 Ah string with electrolyte (Arithmetic).

    Q7. Confirm the standards the cell is built to. A 2 V vented cell for stationary duty is normally specified against IEC 60896-11 and the equivalent DIN 40736-1 envelope. CHISEN production runs under ISO 9001 and ISO 14001, and the range is supplied with CE, RoHS and REACH documentation, so the paperwork trail should exist before the first container is booked.

    §5 — The Trust: What a Datasheet Must State — and What to Reject

    The single most useful question a buyer can ask a supplier is: “which document is this number from?” A published datasheet answers five questions that quotations never answer. What is the capacity rate and the end voltage? For the OPzS2-100 it is 100 Ah at C10 to 1.80 V/cell at 20 °C, and the full curve to 240 hours is published alongside it. What is the weight with and without electrolyte? 8.0 kg and 12.6 kg — both numbers, because a shipping weight quoted without electrolyte tells you nothing about handling. What is the total height over the terminals? 409 mm, not the 354 mm body height, and the difference is exactly the kind of detail that stops a cabinet from being delivered. What is the maximum charging current? 20 A. What is the reference temperature for the internal resistance and for the float life? 20 °C for both, and both references matter more than the numbers themselves.

    Against that standard, reject any quotation that quotes a float voltage of 2.24 V per cell for this model, or one that quotes temperature compensation of −3.3 mV/°C/cell, or one that claims a 20-year design life at 25 °C. The OPzS2-100 datasheet set points are 2.23 V/cell float, 2.35 V/cell equalising and −3 mV/°C/cell compensation, with the 20+ year design figure referenced to 20 °C. A supplier who quotes different numbers for the same model is either reading a different revision or inventing them.

    Two further quality signals are worth checking on site. First, ask for the plant audit trail: paste mixing, grid casting, group assembly, formation and sealing are the process steps that decide whether a 100 Ah cell really holds 100 Ah in year five, and they are the difference between a manufacturer and a packer. Second, ask for the certification package — ISO 9001, ISO 14001, CE, UL and IEC documentation should arrive with the quotation, not three weeks after the deposit. CHISEN runs eight production bases with roughly 70 million kVAh of annual capacity, and the company profile is published on the CHISEN company page if you want to check the manufacturing scale behind a quotation before you commit a container.

    §6 — FAQ

    Q1. What is the rated capacity of the OPzS2-100 2V100Ah? 100 Ah at the 10-hour rate (10 A to 1.80 V/cell at 20 °C). The published table also gives 107 Ah at C24, 111 Ah at C48, 115 Ah at C72, 120 Ah at C100, 122 Ah at C120 and 130 Ah at C240 (Datasheet).

    Q2. How many cells does a 48 V string need, and how much energy does it hold? 24 cells. 48 V × 100 Ah = 4,800 Wh nominal (Arithmetic). The string weighs 302.4 kg with electrolyte (24 × 12.6 kg) and 192.0 kg dry (24 × 8.0 kg).

    Q3. What float and equalising voltage should the charger use? Float 2.23 V/cell and equalising 2.35 V/cell, both referenced to 25 °C. On solar and wind sites use the higher 2.27 ± 0.005 V/cell float and 2.40 ± 0.01 V/cell equalising setpoint (Datasheet).

    Q4. What temperature compensation does the cell need? −3 mV/°C/cell (Datasheet), applied to the float setpoint. At 35 °C the float setpoint falls by 0.036 V per cell.

    Q5. How long is the designed float life? 20+ years at 20 °C (Datasheet). Higher ambient temperatures reduce achievable service life, so site temperature has to be part of the replacement plan rather than a footnote.

    Q6. What is the maximum charging current? 20 A per cell, which is 0.20 × C10 (Datasheet). For a 24-cell string the theoretical ceiling is 480 A (24 × 20 A, Arithmetic), and the charger should normally deliver far less.

    Q7. Can this cell be installed without a permanent operator? It can be installed, but not forgotten. Flooded tubular cells need distilled-water top-up, electrolyte density checks, ventilation and periodic equalising. For an unmanned site, compare the published gel alternative instead.

    Q8. What is the internal resistance and short-circuit current? About 1.0 mΩ fully charged at 20 °C (Datasheet) and a 1500 A short-circuit current (Model page). The string resistance of a 24-cell arrangement is 24.0 mΩ (24 × 1.0 mΩ, Arithmetic), and the 1500 A figure is what your DC fuse and disconnection arrangement must be able to interrupt.

    Q9. How does the OPzS2-100 compare with the gel OPzV2-100? Same 103 × 206 mm footprint, different overall height and different maintenance regime. The flooded cell: 354 mm body, 409 mm total height, 12.6 kg with electrolyte, 20 A charging limit, 1.0 mΩ internal resistance, with watering required. The gel cell: 390 mm total height, 13.2 kg with electrolyte, 30 A charging limit, 1.1 mΩ internal resistance, with no watering. The OPzV2-100 2V100Ah model page carries the gel data set.

    Q10. Which standards and certifications apply? The flooded 2 V stationary cell is built to the IEC 60896-11 and DIN 40736-1 envelope, and CHISEN supplies the range with CE, RoHS and REACH documentation under ISO 9001 and ISO 14001 management systems.

    Expert Summary

    The OPzS2-100 2V100Ah is a 2 V flooded tubular vented lead-acid cell with a published 100 Ah capacity at the 10-hour rate (10 A to 1.80 V/cell at 20 °C), rising to 130 Ah at the 240-hour rate; float 2.23 V/cell and equalising 2.35 V/cell at 25 °C with −3 mV/°C/cell compensation and a 20+ year design float life referenced to 20 °C; a body of 103 × 206 × 354 mm with 409 mm total height; a weight of 8.0 kg without electrolyte and 12.6 kg with electrolyte; a 20 A maximum charging current; about 1.0 mΩ internal resistance at 20 °C; and a 1500 A short-circuit current. A 24-cell 48 V string of these cells holds 4,800 Wh nominal, weighs 302.4 kg with electrolyte and presents 24.0 mΩ of internal resistance. The cell is the correct choice where a manned telecom DC plant, substation or renewable cabinet benefits from long float life and low cost per usable year; where site access is unattended, the published gel alternative trades a higher charging limit and slightly higher internal resistance for the removal of the watering cycle.

    Contact CHISEN

    If you are quoting a 2 V 100 Ah cell for a 48 V DC plant, a substation in Rotterdam or a solar cabinet outside Nairobi, ask for the complete OPzS2-100 datasheet, the string layout drawing and the certification package, and ask for them in writing: email sales@chisen.cn, or message the export desk on WhatsApp at +86 131 6622 6999 (https://wa.me/8613166226999). One line describing your bus voltage, backup time and site temperature is enough for us to return the string arithmetic, the charger setpoints and the nearest capacity in the flooded range — or the gel equivalent if nobody will ever top up water on that site.

    Browse the full CHISEN lead-acid range and technical data at https://leadacidbattery.cn.

    Related CHISEN Product Pages

    Related CHISEN Buyer Guides

  • OPzS2-1200 2V1200Ah Flooded Tubular Battery: Specs, String Sizing and Telecom DC Plant Use

    OPzS2-1200 2V1200Ah Flooded Tubular Battery: Specs, String Sizing and Telecom DC Plant Use

    Answer First

    The OPzS2-1200 2V1200Ah is a 2 V, 1,200 amp-hour flooded tubular vented lead-acid cell rated at the 10-hour rate — 120 A for 10 hours to 1.80 V per cell at 20 °C — and it is the correct cell when a telecom DC plant, a substation or a renewable-powered cabinet needs a 48 V bus holding roughly 57.6 kWh nominal per string, and when somebody on site will still top up water and read a hydrometer once a quarter.

    It is not a sealed cabinet. It is a component of a room. Hydrogen venting, acid-proof flame-retardant vent plugs, scheduled water top-up and periodic equalisation are part of the product, not optional extras, and a project that treats the OPzS2-1200 2V1200Ah as a drop-in sealed block discovers the difference in the first hot season.

    Five numbers decide most projects:

    • 275 × 210 mm footprint, 700 mm over terminals, 62.5 kg dry and 85.0 kg filled. A 24-cell 48 V string is 2,040 kg of battery on the floor before racks, busbar and the room.
    • Maximum charging current 240 A, which is 0.20 C10. That single limit caps what a solar array can push into the string at about 11.5 kW at 48 V nominal.
    • Float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation; equalise 2.35 V per cell at 25 °C. Charge controllers for renewable duty need the separate setpoint table in §4, not the generic defaults.
    • Designed floating life 20+ years at 20 °C. The float life holds at 20 °C and falls away sharply above it, which is the most expensive lesson in this chemistry.
    • Internal resistance ≈0.42 mΩ fully charged at 20 °C; short-circuit current 5,000 A. A 24-cell string presents about 10.08 mΩ in series.

    The OPzS2-1200 2V1200Ah sits between the OPzS2-1000 and the OPzS2-1500 in the same flooded tubular product line. That position is deliberate: it is the capacity at which the platform still absorbs 240 A per cell, which is what a 48 V string with a meaningful solar array needs.

    Key Takeaways

    • 1,200 Ah at C10, delivering 120 A for 10 hours to 1.80 V per cell at 20 °C. Size the string on C10, not on the higher short-duration figures a distributor quotes without a rate.
    • 62.5 kg dry, 85.0 kg with electrolyte, 22.5 kg of acid. Handling is a two-person job with a trolley, and the floor loading must be checked before the plinth is poured.
    • Maximum charging current 240 A per cell (0.20 C10). A 24-cell series string carries that same 240 A through every cell, which is about 11.5 kW at 48 V nominal.
    • Float 2.23 V, equalise 2.35 V per cell, −3 mV/°C/cell compensation, 20+ years float life at 20 °C. Renewable duty needs a different setpoint table entirely — see §4.
    • Internal resistance ≈0.42 mΩ, short-circuit current 5,000 A, maximum discharge 2,500 A for 5 s. Protection coordination and cable sizing follow directly from these two numbers.

    §1 — OPzS2-1200 2V1200Ah Published Specifications

    Every figure below is read from the CHISEN OPzS2-1200 factory datasheet. Where a value is a calculation rather than a printed figure, the source column says so. Values the datasheet does not print are written as “not published” rather than estimated, because an estimate on a procurement sheet becomes an engineering assumption that nobody re-checks.

    ParameterPublished valueSource
    ModelOPzS2-1200Datasheet
    Chemistry and constructionFlooded tubular vented lead-acid: die-cast Pb-Sb tubular positive plate, pasted lead-calcium negative plate, low-resistance PVC composite separator, transparent SAN container, high-strength ABS coverDatasheet
    Nominal voltage2 V per cellDatasheet
    Rated capacity (C10)1,200 Ah, 120 A for 10 h to 1.80 V per cell at 20 °CDatasheet
    Cell footprint275 × 210 mmDatasheet
    Container (jar) height645 mmDatasheet
    Total height over terminals700 mmDatasheet
    Terminal centre spacing108 mm × 110 mmDatasheet
    Weight without electrolyte62.5 kg (138 lbs)Datasheet
    Weight with electrolyte85.0 kg (187 lbs)Datasheet
    Electrolyte (acid) weight22.5 kg at 1.240 g/cm³ (20 °C)Datasheet
    Internal resistance≈0.42 mΩ fully charged at 20 °CDatasheet
    Short-circuit current5,000 ADatasheet
    Maximum discharge current2,500 A for 5 sDatasheet
    Maximum charging current240 ADatasheet
    Charge characteristicConstant current then constant voltage, tapering to 0.15 CA below the float voltageDatasheet
    Float charge voltage2.23 V per cell at 25 °C, −3 mV/°C/cell temperature compensationDatasheet
    Equalise charge voltage2.35 V per cell at 25 °CDatasheet
    Self-discharge≈4 % per month at 20 °CDatasheet
    Ambient temperature, discharge−25 °C to 65 °CDatasheet
    Ambient temperature, charge−20 °C to 65 °CDatasheet
    Ambient temperature, storage−15 °C to 40 °CDatasheet
    Designed floating life20+ years at 20 °CDatasheet
    Terminal typeFemale copper insert, M8 thread, 20 mm outer diameter, 7 mm thread depthDatasheet
    Terminal tightening torque10–12 N·mDatasheet
    Applicable standardsIEC 60896-11, DIN 40736, IEC 61427, Eurobat long-life guide, BS 6290 part 4, UL 1989Datasheet
    CertificationsISO 9001, ISO 14001, GB/T 28001 (OHSAS 18001:2007), CE, RU, TLCDatasheet

    For renewable duty the useful capacity is quoted at a lower cut-off voltage, because the controller protects the battery long before the cell reaches 1.80 V. The datasheet publishes the following capacities at a 1.85 V cut-off.

    RateCapacity at 1.85 V per cellSource
    C241,356 AhDatasheet
    C481,488 AhDatasheet
    C721,560 AhDatasheet
    C1001,620 AhDatasheet
    C1201,644 AhDatasheet
    C2401,680 AhDatasheet

    §2 — The Pain: Why This Purchase Goes Wrong

    The capacity number is a trap. The OPzS2-1200 2V1200Ah is rated at C10. A distributor who quotes “1,200 Ah” without the rate is quoting a number that does not describe your duty. At a one-hour discharge the cell delivers roughly half its C10 capacity; at a ten-hour discharge it delivers the full figure. A cabinet that must carry a five-minute ride-through at high load sees far less. Specify the rate and the cut-off voltage with the capacity, always together.

    Flooded means a room, not a cabinet. Hydrogen evolves from the negative plates during charging and it needs a path out. Acid-proof flame-retardant vent plugs handle the ignition source; they do not handle the accumulation. Every OPzS2-1200 2V1200Ah installation needs mechanical ventilation sized for the worst-case float and equalisation charge, plus a person with a hydrometer and a top-up bottle on a schedule.

    Charge acceptance quietly caps the whole project. The published maximum charging current for the OPzS2-1200 2V1200Ah is 240 A, which is 0.20 C10. At 48 V nominal that is about 11.5 kW. An array sized on the load rather than on the battery is an array the battery cannot absorb. The excess goes into float losses, extended equalisation, or an over-voltage disconnect that trips the inverter out of service.

    The float life is temperature-bound, and the datasheet is specific about it. The designed floating life of 20+ years is stated at 20 °C, and it is roughly halved for every 10 °C above that. A power room in Chennai, Durban or Karachi that runs at 30 °C ambient all year is looking at a life closer to ten years, not twenty, and no controller precision changes that. Room cooling is a battery decision, not a comfort decision.

    The physical envelope is not negotiable. 275 mm long, 210 mm wide and 700 mm tall over terminals, with 85.0 kg in the cell once filled. Rack pitch, aisle width, door clearance and the lifting route for a single cell all have to be confirmed against the drawing before the plinth is poured. Substituting a guess is how a delivery arrives that cannot be installed.

    §3 — The Choice: Where the OPzS2-1200 Sits

    The alternative to the OPzS2-1200 2V1200Ah is rarely another chemistry. In the telecom, substation and containerised-renewable markets where this cell is specified, the real choice is the same flooded platform at a different capacity, the gel variant of the same platform, or a sealed VRLA block of a lower capacity.

    ParameterOPzS2-1000 2V1000AhOPzS2-1200 2V1200AhOPzS2-1500 2V1500Ah
    Rated capacity (C10)1,000 Ah1,200 Ah1,500 Ah
    Cell footprint233 × 210 mm275 × 210 mm275 × 210 mm
    Total height over terminals700 mm700 mm850 mm
    Weight without electrolyte53.5 kg62.5 kg71.0 kg
    Weight with electrolyte73.5 kg85.0 kg98.0 kg
    Electrolyte weight20 kg22.5 kg27 kg
    Internal resistance at 20 °C0.45 mΩ0.42 mΩ0.40 mΩ
    Short-circuit current4,500 A5,000 A5,400 A
    Maximum discharge current (5 s)2,500 A2,500 A2,500 A
    Maximum charging current200 A240 A300 A

    Read that table column by column rather than row by row. The OPzS2-1200 2V1200Ah is the only one of the three whose maximum charging current, 240 A, is exactly 0.20 C10 of its own capacity. The 1,000 Ah cell accepts 200 A, which is also 0.20 C10, but 240 A is 20 % more absolute current for 20 % more absolute energy. The 1,500 Ah cell accepts 300 A, which is the same 0.20 C10 ratio but 25 % more current than the 1,200 Ah cell, and it is 13.0 kg heavier per cell — 312 kg more across a 24-cell string.

    Footprint is the second lesson. The OPzS2-1200 2V1200Ah and the OPzS2-1500 2V1500Ah share the same 275 × 210 mm footprint, but the 1,500 Ah cell is 850 mm over terminals against 700 mm, so the rack pitch is not interchangeable. The 1,000 Ah cell is narrower at 233 mm and fits a different pitch. Cell width is not a free variable when the cabinet is already drawn.

    The third lesson is internal resistance, because it is the number that decides how a string behaves on a step load. At 0.42 mΩ the OPzS2-1200 2V1200Ah is the middle of the three, and for a 24-cell string the arithmetic is 24 × 0.42 mΩ = 10.08 mΩ in series, against 24 × 0.45 mΩ = 10.80 mΩ for the 1,000 Ah build and 24 × 0.40 mΩ = 9.60 mΩ for the 1,500 Ah build. A 500 A load step on a 48 V string produces a voltage step of 500 A × 10.08 mΩ = 5.04 V across the string, or 0.21 V per cell, which sits comfortably inside the ride-through window a controller expects. The 1,000 Ah build steps 5.40 V and the 1,500 Ah build 4.80 V.

    The full physical and electrical data for the OPzS2-1200 2V1200Ah sits on the CHISEN OPzS2-1200 model page, the next size down is documented on the OPzS2-1000 model page, and the wider flooded tubular range is indexed on the CHISEN OPzS tubular battery page.

    §4 — The Framework: Five Hard Numbers for Sizing and Acceptance

    1. Size on C10, then check it against the real discharge. A 24-cell string at the C10 rate delivers 48 V × 1,200 Ah = 57,600 Wh nominal. At the C24 rate published for renewable duty, the same string holds 24 × 1,356 Ah = 32,544 Ah measured down to a 1.85 V per cell cut-off. That figure sits above the 1,200 Ah nominal rating because the discharge is slower and the cut-off voltage is higher, so it is not directly comparable to C10. Quote the nominal 57,600 Wh for a ride-through duty and the renewable figure for a solar cabinet; they answer different questions.

    2. Check charge acceptance against the array, not against the load. Maximum charging current is 240 A per cell. Because the 24 cells sit in series, the string carries that same 240 A through every cell, so at 48 V nominal it absorbs 240 A × 48 V = 11,520 W. Where several strings run in parallel, the installed cell-level charge-acceptance total is 24 × 240 A = 5,760 A per string, and the rectifier has to be sized on the parallel sum rather than on one string. Size the array on 0.20 C10 and the rest follows.

    3. Confirm the floor, the rack and the lifting route. A filled 24-cell string weighs 24 × 85.0 kg = 2,040 kg, plus 24 × 62.5 kg = 1,500 kg of dry cell mass and 24 × 22.5 kg = 540 kg of acid. The acid alone is 540 kg of electrolyte that has to be handled if a cell is ever replaced.

    4. Write the equalisation schedule into the acceptance test. Equalisation runs at 2.35 V per cell at 25 °C, which is 24 × 2.35 V = 56.4 V across a 48 V string, and it is the point at which cell imbalance shows up. A string that has never been equalised has never shown its capacity spread, and that spread is what decides whether the last cell in the string runs out of life first.

    5. Set the renewable controller to the published table, not to a default. The datasheet prints a dedicated setpoint list for solar and wind duty.

    Solar and wind setpointPublished settingSource
    Over voltage disconnect2.47 ± 0.01 V/cell at 25 °CDatasheet
    Regulation / equalise voltage2.40 ± 0.01 V/cell at 25 °CDatasheet
    Array reconnection voltage2.23 ± 0.005 V/cell at 25 °CDatasheet
    Float voltage setting2.25 ± 0.005 V/cell at 25 °CDatasheet
    Low voltage alarm voltage1.95 ± 0.005 V/cell at 25 °CDatasheet
    Low voltage disconnect1.90 ± 0.005 V/cell at 25 °CDatasheet
    Load reconnect voltage2.09 ± 0.01 V/cell at 25 °CDatasheet
    Temperature compensation coefficient−4 mV/cell/°CDatasheet

    Note the deliberate difference between the float table in §1 and the renewable table here. The general float setting is 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation, while the renewable controller runs a float setting of 2.25 ± 0.005 V per cell with −4 mV/cell/°C compensation. A controller left on a generic profile will hold the string below the renewable float setpoint and quietly shorten life.

    §5 — The Trust: How to Test the Delivery

    The first test is the paperwork, not the pallet. A battery quote should arrive with the datasheet behind it, and the datasheet should carry the cell model, the rated capacity with its rate, the charge voltage setpoints, the standards and the certifications. If the quotation carries only a capacity and a table number, ask for the datasheet before the price conversation continues.

    Check the production base, not the trading company. The CHISEN OPzS2-1200 2V1200Ah is produced inside a manufacturer operating 8 production bases with an annual capacity of 70 million kVAh, under a quality management system certified to ISO 9001 with ISO 14001 covering the environmental system and GB/T 28001 for occupational health and safety, with CE, UL and IEC conformity for the destination markets. A trader who cannot name the base that cast the plate is selling you somebody else’s cell.

    Ask for the serial-level traceability and the type-test evidence. IEC 60896-11 and DIN 40736 are the applicable standards for this flooded tubular platform, and UL 1989 is the North American reference. A supplier who supplies the certificate index without the report is supplying the index.

    Watch the certification claims on the nameplate. Every published certificate on the OPzS2-1200 2V1200Ah datasheet appears with a standard reference beside it: IEC 60896-11, DIN 40736, IEC 61427, the Eurobat long-life guide, BS 6290 part 4 and UL 1989. If a supplier quotes a certification that is not in that list, ask for the document.

    Ask what happens at the first hot season. A power room in Mombasa or Valencia in August runs above 30 °C ambient, and the 20+ year float life at 20 °C is the figure that no longer holds. A supplier who quotes 20+ years without the temperature is quoting a marketing number; a supplier who quotes it at 20 °C is quoting the datasheet.

    And insist on the handover documents. A complete delivery for the OPzS2-1200 2V1200Ah includes the test report, the packing list with the acid weight per cell, the installation and ventilation drawing, the charging setpoint sheet and the warranty terms. The setpoint sheet matters more than it looks: the float and equalise values, the temperature compensation and the maximum charging current are the settings that determine whether the 20+ year design life is real or not.

    §6 — FAQ

    Q1. What does 2V1200Ah mean on the OPzS2-1200? It means one cell of 2 volts nominal delivering 1,200 amp-hours at the 10-hour rate, which is 120 A for 10 hours down to 1.80 V per cell at 20 °C. A 48 V string is 24 of these cells in series, so the string is 48 V × 1,200 Ah = 57,600 Wh nominal.

    Q2. Can I run the OPzS2-1200 2V1200Ah in parallel with another set? Yes, in strings of equal length and equal age, but the parallel strings must be on the same bus, the same controller profile and the same equalisation schedule, and the state of charge must be matched before the strings are connected. Unequal-length strings on a shared bus will not share current evenly.

    Q3. What charger do I need for a 48 V string? A 48 V charger with a current rating no higher than the published maximum charging current of the string, which is 24 × 240 A = 5,760 A of theoretical cell acceptance but practically 0.20 C10. Confirm the setpoints: float 2.23 V per cell at 25 °C, equalise 2.35 V per cell at 25 °C, and −3 mV/°C/cell temperature compensation.

    Q4. Does the OPzS2-1200 2V1200Ah need a temperature-compensated charger? Yes. The datasheet specifies −3 mV/°C/cell compensation for general duty and −4 mV/cell/°C for solar and wind duty, and a fixed-voltage charger in a room that swings from 10 °C to 35 °C will over-charge the string in winter and under-charge it in summer.

    Q5. How much water does an OPzS2-1200 2V1200Ah cell need over its life? Each cell holds 22.5 kg of electrolyte at 1.240 g/cm³, and water loss is topped up through the vent plugs. The published self-discharge rate is ≈4 % per month at 20 °C, which is mostly water loss in a flooded cell. Establish the top-up interval and the instrument before the string is commissioned.

    Q6. Is 20+ years float life realistic for the OPzS2-1200 2V1200Ah? It is the designed floating life stated at 20 °C, and it is a float-life figure for a standby duty, not a cycle-life figure. It also depends on the room staying close to 20 °C, on float voltage being held at 2.23 V per cell and on equalisation being done on schedule.

    Q7. What is the difference between the OPzS2-1200 2V1200Ah and a 1,200 Ah sealed VRLA block? The OPzS2-1200 2V1200Ah is flooded and vented, so it needs a ventilated room, water top-up and periodic equalisation, and in exchange it gives a 20+ year float life at 20 °C with a published 5,000 A short-circuit current. A sealed block needs no room service but has a shorter float life and a lower short-circuit capability.

    Q8. Can the OPzS2-1200 2V1200Ah be used for solar storage? Yes, and the datasheet publishes renewable-specific data for it: long-time discharge capacities of 1,356 Ah at C24 rising to 1,680 Ah at C240 on a 1.85 V cut-off, plus a dedicated controller setpoint table with a 2.47 ± 0.01 V over-voltage disconnect and a 2.40 ± 0.01 V regulation voltage. Use those setpoints rather than a generic profile.

    Expert Summary

    The OPzS2-1200 2V1200Ah is a 2 V flooded tubular lead-acid cell rated 1,200 Ah at C10 — 120 A for 10 hours to 1.80 V per cell at 20 °C — built for telecom DC plant, substation and renewable storage duties where somebody will maintain it. Its published physical envelope is a 275 × 210 mm footprint, 700 mm over terminals, 62.5 kg dry and 85.0 kg filled with 22.5 kg of acid; its published electrical envelope is float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation, equalise 2.35 V per cell at 25 °C, maximum charging current 240 A, internal resistance ≈0.42 mΩ at 20 °C, short-circuit current 5,000 A, maximum discharge 2,500 A for 5 s, self-discharge ≈4 % per month at 20 °C, and a designed floating life of 20+ years at 20 °C. It complies with IEC 60896-11, DIN 40736, IEC 61427, the Eurobat long-life guide, BS 6290 part 4 and UL 1989, and carries ISO 9001, ISO 14001, GB/T 28001, CE, RU and TLC. In a 24-cell 48 V string it holds 57,600 Wh nominal, weighs 2,040 kg filled, accepts 24 × 240 A = 5,760 A, and presents 24 × 0.42 mΩ = 10.08 mΩ in series. It sits between the OPzS2-1000 and OPzS2-1500 in the same flooded tubular product line, and the choice between them is a question of array size, rack height and string weight, not of chemistry.

    Contact CHISEN

    Request the OPzS2-1200 2V1200Ah datasheet, the type-test report for your destination market and a string layout for your bus voltage and load profile from the CHISEN export team.

    Lead-acid tubular batteries for telecom DC plant, substation and renewable storage projects. State the bus voltage, the load, the ambient temperature range and the required float life in your enquiry, and the quotation will carry the matching string arithmetic rather than a cell price alone.

    Related CHISEN Buyer Guides

  • OPzS2-1500 2V1500Ah Flooded Tubular Battery: Utility-Scale Solar and Wind Storage

    OPzS2-1500 2V1500Ah Flooded Tubular Battery: Utility-Scale Solar and Wind Storage

    Answer First

    The OPzS2-1500 2V1500Ah is a 2 V, 1500 amp-hour flooded tubular vented lead-acid cell rated at the ten-hour rate — 150 A for 10 hours to 1.80 V per cell at 20 °C — and it is the right cell when a utility-scale solar or wind plant, a large telecom power room or a rail traction substation needs a 48 V or 96 V DC bus holding roughly 72 kWh or 144 kWh nominal per string, and when somebody on site will still top up water and read a hydrometer once a quarter.

    It is not a sealed cabinet. It is a component of a room: hydrogen venting, flame-retardant acid-proof vent plugs, quarterly water top-up, periodic equalisation and a specific-gravity check are part of the product, not optional extras.

    Five facts decide most projects:

    • 275 × 210 × 850 mm, 850 mm over terminals, 71.0 kg without electrolyte and 98 kg with it. A 24-cell 48 V string is 2,352 kg of battery on the floor before racks, busbar and the room.
    • Maximum charging current 300 A, 0.20 C10. That single limit caps what a solar array can push into the string at about 14.5 kW at 48 V nominal.
    • Float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation; equalise 2.35 V per cell at 25 °C. Charge controllers for renewable duty need the separate setpoints listed in §4, not the generic defaults.
    • Designed floating life 20+ years at 20 °C. The float life holds at 20 °C and falls away sharply above it — this is the most expensive lesson in this chemistry.
    • Internal resistance ≈0.40 mΩ fully charged at 20 °C; short-circuit current 5,400 A. A 24-cell string presents about 9.6 mΩ in series and delivers roughly 5,000 A on a hard short.

    The OPzS2-1500 2V1500Ah sits between the OPzS2-1000 and the OPzS2-2000 in the same product range. That position is deliberate: it is the capacity step that matches the array sizes now being tendered for 48 V utility DC buses, and it absorbs 300 A per cell while still being handled by two people.

    Key Takeaways

    • 1,500 Ah at C10, 150 A for 10 hours to 1.80 V per cell at 20 °C. The rating is a ten-hour rate, so size your string on C10, not on the higher one-hour or three-hour figures a distributor quotes.
    • 71.0 kg dry, 98 kg with electrolyte, 27 kg of acid. Handling is a two-person job with a trolley, and the floor loading must be checked before the plinth is poured.
    • Maximum charging current 300 A per cell (0.20 C10). A 48 V string accepts 7,200 A, which is about 14.5 kW at nominal bus voltage.
    • Float 2.23 V, equalise 2.35 V per cell, −3 mV/°C/cell compensation, 20+ years float life at 20 °C. Solar and wind duty needs a different setpoint table entirely — see §4.
    • Internal resistance ≈0.40 mΩ, short-circuit current 5,400 A, maximum discharge 2,500 A for 5 s. Protection coordination and cable sizing follow directly from these numbers.

    §1 — OPzS2-1500 2V1500Ah Published Specifications

    Every figure below comes from the CHISEN OPzS2-1500 factory datasheet. Where a value is a calculation rather than a printed figure, the source column says so. Values the datasheet does not print are written as “not published” rather than estimated, because an estimate on a procurement sheet becomes an engineering assumption nobody re-checks.

    ParameterPublished valueSource
    ModelOPzS2-1500Datasheet
    Chemistry and constructionFlooded tubular vented lead-acid: die-cast Pb-Sb tubular positive plate, pasted lead-calcium negative plate, low-resistance PVC composite separator, transparent SAN container, high-strength ABS coverDatasheet
    Nominal voltage2 V per cellDatasheet
    Rated capacity (C10)1,500 Ah, 150 A for 10 h to 1.80 V per cell at 20 °CDatasheet
    Cell dimensions275 × 210 × 850 mmDatasheet
    Container (jar) height795 mmDatasheet
    Total height over terminals850 mmDatasheet
    Top view275 × 210 mmDatasheet
    Terminal centre spacing108 mmDatasheet
    Weight without electrolyte71.0 kg (157 lbs)Datasheet
    Weight with electrolyte98 kg (216 lbs)Datasheet
    Electrolyte (acid) weight27 kg at 1.240 g/cm³Datasheet
    Internal resistance≈0.40 mΩ fully charged at 20 °CDatasheet
    Short-circuit current5,400 ADatasheet
    Maximum discharge current2,500 A for 5 sDatasheet
    Maximum charging current300 ADatasheet
    Charge characteristicConstant-current then constant-voltage, tapering to 0.15 CA below the float voltageDatasheet
    Float charge voltage2.23 V per cell at 25 °C, −3 mV/°C/cell temperature compensationDatasheet
    Equalise charge voltage2.35 V per cell at 25 °C, 20–25 °C rangeDatasheet
    Self-discharge≈4 % per month at 20 °CDatasheet
    Ambient temperature, discharge−25 °C to 65 °CDatasheet
    Ambient temperature, charge−20 °C to 65 °CDatasheet
    Ambient temperature, storage−15 °C to 40 °CDatasheet
    Designed floating life20+ years at 20 °CDatasheet
    Terminal typeFemale copper insert, M8 thread, 20 mm outer diameterDatasheet
    Terminal tightening torque10–12 N·mDatasheet
    Vent plugsAcid-proof, flame-retardant, explosion-proof; catalytic plug optionalDatasheet
    Applicable standardsIEC 60896-11, DIN 40736, IEC 61427, Eurobat long-life guide, BS 6290 part 4, UL 1989Datasheet
    CertificationsISO 9001, ISO 14001, OHSAS 18001:2007 (GB/T 28001), CEDatasheet

    Solar and wind long-time discharge

    For renewable duty the useful capacity is quoted at a lower cut-off voltage, because the controller protects the battery long before the cell reaches 1.80 V. The datasheet publishes the following capacities at a 1.85 V cut-off:

    RateCapacity at 1.85 V per cellSource
    C241,695 AhDatasheet
    C481,860 AhDatasheet
    C721,950 AhDatasheet
    C1002,025 AhDatasheet
    C1202,055 AhDatasheet
    C2402,100 AhDatasheet

    §2 — The Pain: Why Utility-Scale Purchases Go Wrong

    First, the capacity number without a rate is not a number. The OPzS2-1500 2V1500Ah is rated at C10. A distributor who quotes “1,500 Ah” without the rate is quoting a figure that does not describe your duty. At a one-hour discharge the cell gives roughly half its C10 capacity; at a ten-hour discharge it gives the full figure. A utility plant that rides out a cloudy night on a slow discharge sits close to the C10 curve, while a ride-through cabinet with a five-minute discharge at high load sees far less. Specify the rate and the cut-off voltage together with the capacity, always.

    Second, flooded means a room, not a container. Hydrogen evolves during charging and needs a path out. Acid-proof flame-retardant vent plugs handle the ignition source; they do not handle the accumulation. Every OPzS2-1500 installation needs mechanical ventilation sized for the worst-case float and equalisation charge, and it needs a person with a hydrometer and a top-up bottle on a schedule. Buyers who treat the OPzS2-1500 2V1500Ah as a drop-in replacement for a sealed block discover the difference in the first hot season.

    Third, charge acceptance quietly caps the whole project. The published maximum charging current for the OPzS2-1500 is 300 A, which is 0.20 C10. At 48 V nominal that is about 14.5 kW. An array sized on the load rather than on the battery is an array the battery cannot absorb. The excess goes into float losses, extended equalisation, or an over-voltage disconnect that takes the inverter out of service. The array is the expensive half of a utility project, so fix this number before the panels are ordered.

    Fourth, the float life is temperature-bound, and the datasheet is specific about it. The designed floating life of 20+ years is stated at 20 °C, and it is roughly halved for every 10 °C above that. A container in Chennai, Durban or Karachi that runs at 30 °C ambient all year is looking at a life closer to ten years, not twenty, and no controller precision changes that. Room cooling is a battery decision, not a comfort decision.

    Fifth, the physical envelope is not negotiable. 275 mm long, 210 mm wide and 850 mm tall over terminals, with 98 kg filled. Rack pitch, aisle width, door clearance and the lifting route for a single cell all have to be confirmed against the drawing before the plinth is poured. Substituting a guess is how a delivery arrives that cannot be installed.

    §3 — The Choice: Where the OPzS2-1500 Sits

    The alternative to the OPzS2-1500 2V1500Ah is rarely another chemistry. In utility renewable, substation and large telecom markets where this cell is specified, the real choice is the same flooded platform at a different capacity, the gel variant of the same platform, or a sealed VRLA block of lower capacity.

    Against the neighbouring flooded capacities

    ParameterOPzS2-1000 2V1000AhOPzS2-1500 2V1500AhOPzS2-2000 2V2000Ah
    Rated capacity (C10)1,000 Ah1,500 Ah2,000 Ah
    Cell dimensions233 × 210 × 645 mm275 × 210 × 850 mm399 × 210 × 826 mm
    Total height over terminals645 mm850 mm826 mm
    Weight without electrolyte53.5 kg71.0 kg106 kg
    Weight with electrolyte73.5 kg98 kg146 kg
    Internal resistance0.45 mΩ at 20 °C0.40 mΩ at 20 °C0.35 mΩ at 20 °C
    Maximum charging current200 A300 A400 A
    Short-circuit current4,500 A5,400 A6,000 A
    Float voltage2.23 V per cell2.23 V per cell2.23 V per cell
    Designed float life20+ years at 20 °C20+ years at 20 °C20+ years at 20 °C

    The middle column is the OPzS2-1500 datasheet; the OPzS2-1000 and OPzS2-2000 figures are the published values for those models. Three observations follow directly.

    The OPzS2-1500 absorbs 300 A per cell, so a 48 V string of 24 cells accepts 7,200 A. That covers an array of roughly 14.5 kW on one string. Below that the OPzS2-1000 at 200 A is the natural choice; above it the OPzS2-2000 at 400 A is.

    Internal resistance falls from 0.45 mΩ to 0.35 mΩ across this range, which makes a large string electrically cleaner at the same fault duty and why voltage recovery after a load step is less punishing on the bigger cells.

    Height is not shared across the range: the OPzS2-1000 stands 645 mm over terminals while the OPzS2-1500 and OPzS2-2000 stand 850 mm and 826 mm. A rack built for one is not a rack for another, so the OPzS2-1500 drawing governs the aisle and the lifting route.

    The 48 V string arithmetic

    Every number below is derived from the published per-cell figures above.

    Derived quantityCalculationResult
    String nominal energy24 × 2 V × 1,500 Ah72 kWh
    String series resistance24 × 0.40 mΩ9.60 mΩ
    String maximum charging current24 × 300 A7,200 A
    String maximum discharge current (5 s)24 × 2,500 A60,000 A
    String weight filled24 × 98 kg2,352 kg
    String weight dry24 × 71.0 kg1,704 kg
    String acid weight24 × 27 kg648 kg
    Short-circuit current at the terminals48 V ÷ 9.60 mΩ≈5,000 A

    The last line is a calculation, not a datasheet figure: the published short-circuit current of 5,400 A is the manufacturer’s value for the cell and governs protection coordination. Use the published number for coordination and treat the derived figure as a sanity check on the wiring.

    Flooded against gel

    If nobody will ever touch the battery — no water top-up, no quarterly equalisation, no hydrometer — the gel version of this platform is the better product, and the OPzS2-1500 2V1500Ah is the wrong choice. Gel removes the room requirement: no ventilation path, no topping up, no hydrogen accumulation. The cost is a lower published cycle-life floor and marginally higher internal resistance. Make that trade explicitly, because it is a labour decision as much as a chemistry decision.

    §4 — The Framework: Nine Things to Fix Before the Order

    1. Lock the rate with the capacity. Write “OPzS2-1500 2V1500Ah, 1,500 Ah at C10 to 1.80 V per cell at 20 °C” on the purchase order, not “1,500 Ah”. If the duty is a shorter discharge, ask for the capacity at that rate and at the cut-off voltage the controller will use.

    2. Fix the string architecture on paper first. 24 cells at 2 V gives 48 V nominal, which is the common utility and telecom DC bus. 48 cells gives 96 V. Write the cell count, the nominal bus voltage and the end-point voltage at 1.80 V per cell — 43.2 V for a 24-cell string — next to the load list. Every downstream number, from charger rating to cable cross-section, follows from those three figures.

    3. Check the charge ceiling against the array. Maximum charging current is 300 A per cell, so 7,200 A for a 24-cell string, roughly 14.5 kW at 48 V nominal. If the array exceeds that, step up one capacity in the range or fit a charge-current limit in the controller. Decide before the array is ordered.

    4. Use the renewable setpoint table, not the generic one. For solar and wind the datasheet publishes a dedicated set of controller parameters, and they are not the same as the stationary float-and-equalise pair:

    ParameterValueSource
    Over-voltage disconnect2.47 ± 0.01 V per cellDatasheet
    Regulation / equalise voltage2.40 ± 0.01 V per cellDatasheet
    Array reconnection voltage2.23 ± 0.005 V per cellDatasheet
    Float voltage setting2.25 ± 0.005 V per cellDatasheet
    Low-voltage alarm1.95 ± 0.005 V per cellDatasheet
    Low-voltage disconnect1.90 ± 0.005 V per cellDatasheet
    Load reconnect voltage2.09 ± 0.01 V per cellDatasheet
    Temperature compensation coefficient−4 mV per cell per °CDatasheet

    Note the deliberate difference from the stationary setpoints in §1. The renewable float setting is 2.25 V per cell, not 2.23 V, and the renewable compensation coefficient is −4 mV per cell per °C, not −3 mV. Renewable charging is intermittent, so the controller holds the array at a slightly higher potential to capture what light there is, and the −4 mV coefficient is matched to the wider temperature swing of an outdoor cabinet. Copying the stationary numbers into a solar controller is a common and expensive error.

    5. Design the ventilation path. Hydrogen evolves on charge. Provide mechanical extraction sized for the worst-case charge case, keep flame-retardant acid-proof vent plugs fitted, and confirm the room is not a sealed container with one door.

    6. Schedule the water. An OPzS2-1500 cell loses water on every charge cycle. Quarterly top-up with distilled or demineralised water, a quarterly specific-gravity reading on every cell and a logged equalisation at a defined interval are operating requirements, not maintenance extras. Budget the labour; a battery that is never checked fails at the worst time.

    7. Confirm the mechanical envelope against the drawing. For the OPzS2-1500: 275 × 210 × 850 mm, 98 kg filled, terminal centre spacing 108 mm, M8 female insert at 10–12 N·m. Rack pitch, door clearances, the lifting route for a 98 kg cell and the floor loading all need the drawing, not a spreadsheet.

    8. Set the end-of-life criterion now. Define the capacity floor — the percentage of rated C10 at which the string is replaced — and put it in the maintenance plan with a date attached. Without a written criterion, end-of-life is a judgement call made under pressure during an outage.

    9. Order the spares policy deliberately. Cells in a series string age unevenly. Decide in advance whether you hold one spare OPzS2-1500 cell on site, and note that a spare must be the same model and age band as the string, not a newer cell dropped into an older string.

    §5 — The Trust: Who Built It and What Is Certified

    CHISEN operates 8 production bases with an annual capacity of 70 million kVAh, which is the scale behind the published datasheet rather than a marketing figure on a web page. The OPzS2-1500 2V1500Ah is built to IEC 60896-11 for stationary lead-acid valves and DIN 40736 for tubular cells, with IEC 61427 and BS 6290 part 4 also applicable and the UL 1989 listing covering the North American side. The Eurobat long-life guide applies to the float-life claim. The manufacturing system is certified to ISO 9001 for quality management and ISO 14001 for environmental management, with OHSAS 18001:2007 (GB/T 28001) covering occupational health and safety, and the product carries CE marking. Every export shipment is documented with CE, UL and IEC certification papers for the exact variant.

    Those standards matter commercially, not just decoratively. DIN 40736 and IEC 60896-11 are what an importer’s technical file has to cite for EU market access; BS 6290 part 4 and UL 1989 are what a buyer in Mumbai, Karachi, Durban or a Gulf port asks for when the battery is going into a tender. The same document set is requested in Rotterdam, Hamburg, Jebel Ali, Santos, Mombasa, Antwerp, Colombo and Lagos: the standards are identical, the local authority requirements are not.

    The certification set is a claim you can verify rather than take on trust: request the test certificates for the exact model, check that the scope covers the 1,500 Ah variant, and confirm the certificate address matches the supplier quoting it. Do this before a 24-cell OPzS2-1500 string lands on your floor, because a certificate that does not cover the variant is a documentation problem discovered at the wrong moment.

    The 8 production bases and 70 million kVAh of capacity also matter for delivery risk on a large project. A 48 V string of 24 OPzS2-1500 cells at 98 kg filled is 2,352 kg of battery from one production base, and a mixed-date delivery is a mixed-age string. Ask for the manufacturing date on the cells, and ask that the whole string be produced within one production window.

    §6 — FAQ: OPzS2-1500 2V1500Ah

    Q1. What is the rated capacity of the OPzS2-1500 2V1500Ah? 1,500 Ah at the ten-hour rate, meaning 150 A for 10 hours to a 1.80 V per cell cut-off at 20 °C. The datasheet also publishes renewable long-time discharge capacities at a 1.85 V cut-off, from 1,695 Ah at C24 up to 2,100 Ah at C240.

    Q2. What are the physical dimensions and weight of one OPzS2-1500 cell? 275 × 210 × 850 mm overall, with a 795 mm container and 850 mm height over terminals. 71.0 kg without electrolyte, 98 kg with electrolyte, and 27 kg of acid at 1.240 g/cm³. One filled cell is a two-person handling job.

    Q3. What float and equalise voltages should the charger use? Float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation, and equalise 2.35 V per cell at 25 °C over a 20–25 °C range. For solar and wind duty the controller setpoints differ — 2.25 V float and a −4 mV per cell per °C coefficient — and are listed in §4.

    Q4. How much current can the OPzS2-1500 take during charging? The published maximum charging current is 300 A, which is 0.20 C10. A 24-cell 48 V string therefore accepts 7,200 A, roughly 14.5 kW at nominal bus voltage. Exceeding that limit pushes the array into float losses or triggers an over-voltage disconnect.

    Q5. What are the internal resistance and short-circuit current of the OPzS2-1500? Internal resistance is approximately 0.40 mΩ fully charged at 20 °C. The published short-circuit current is 5,400 A, and the maximum discharge current is 2,500 A for 5 s. A 24-cell string presents 9.60 mΩ in series.

    Q6. How long does the OPzS2-1500 2V1500Ah last in float service? The designed floating life is 20+ years at 20 °C. Float life falls by roughly half for every 10 °C above 20 °C, so an uncooled container at 30 °C ambient should expect materially less.

    Q7. What maintenance does the OPzS2-1500 require? Quarterly water top-up with distilled or demineralised water, a quarterly specific-gravity reading on every cell, equalisation on a logged schedule, and hydrogen ventilation sized for the worst-case charge case. Acid-proof flame-retardant vent plugs must stay fitted.

    Q8. Can the OPzS2-1500 2V1500Ah be used for solar storage? Yes, and the datasheet publishes a dedicated setpoint table for renewable duty, including the 2.47 ± 0.01 V over-voltage disconnect, the 2.40 ± 0.01 V regulation voltage and the 1.90 ± 0.005 V low-voltage disconnect. The 300 A maximum charging current still applies, so the array must be sized against it.

    Q9. What certifications does the OPzS2-1500 2V1500Ah carry? Built to IEC 60896-11, DIN 40736, IEC 61427, the Eurobat long-life guide, BS 6290 part 4 and UL 1989. The manufacturing system is certified to ISO 9001 and ISO 14001, with OHSAS 18001:2007 (GB/T 28001), and the product carries CE marking.

    Expert Summary

    The OPzS2-1500 2V1500Ah is a 2 V, 1,500 Ah flooded tubular cell for 48 V and 96 V DC strings in utility renewable plants, large telecom power rooms and traction substations. Its published envelope is 275 × 210 × 850 mm at 71.0 kg dry and 98 kg filled, with 0.40 mΩ internal resistance, a 5,400 A short-circuit current and a 300 A maximum charging current.

    Four decisions carry the project. Size on C10 with the cut-off voltage attached to the capacity. Respect the 300 A charge ceiling when the array is specified, or step up one capacity in the range. Use the renewable setpoint table for solar and wind rather than the stationary pair. And budget the labour and ventilation a flooded cell needs, because the 20+ year float life at 20 °C only holds in a maintained, ventilated, temperature-controlled room.

    For a 24-cell 48 V string the arithmetic is 72 kWh nominal, 9.60 mΩ in series, 7,200 A of charge acceptance, 2,352 kg of installed battery and 648 kg of acid. Take those five numbers to the civil and electrical design, and the OPzS2-1500 2V1500Ah will do what the datasheet says it does.

    Contact CHISEN

    Technical enquiries, project drawings and tender documents: sales@chisen.cn and +86 131 6622 6999 on WhatsApp. Mention the model OPzS2-1500 and the string voltage you are designing for, and the CHISEN team will supply the certified per-cell datasheet, the certified weight, the drawing and the test certificates for the exact variant.

    Related reading: the OPzS2-1500 2V1500Ah model page, the OPzS2-2000 2V2000Ah model page for the cell above it in the range, and the OPzS flooded tubular battery range for the full platform.

    Related CHISEN Buyer Guides

  • OPzS2-800 2V800Ah Flooded Tubular Battery: Specs, String Sizing and Telecom DC Plant Use

    OPzS2-800 2V800Ah Flooded Tubular Battery: Specs, String Sizing and Telecom DC Plant Use

    Answer First

    The OPzS2-800 2V800Ah is a 2 V, 800 amp-hour flooded tubular vented lead-acid cell rated at the 10-hour rate — 80 A for 10 hours to 1.80 V per cell at 20 °C — and it is the right cell when a telecom DC plant, a substation or a solar-plus-storage cabinet needs a 48 V or 96 V bus holding roughly 19 kWh or 38 kWh nominal per string, and when somebody on site will still top up water and read a hydrometer once a quarter.

    It is not a sealed cabinet. It is a component of a room: hydrogen venting, flame-retardant acid-proof vent plugs, quarterly water top-up, quarterly equalisation and a specific-gravity check are part of the product, not optional extras.

    Five facts decide most projects:

    • 191 × 210 × 700 mm, 700 mm over terminals, 42.0 kg without electrolyte and 58 kg with it. A 24-cell 48 V string is 1,392 kg of battery on the floor before racks, busbar and the room.
    • Maximum charging current 160 A, 0.20 C10. That single limit caps what a solar array can push into the string at about 7.7 kW at 48 V nominal.
    • Float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation; equalise 2.35 V per cell at 25 °C. Charge controllers for solar duty need the separate setpoints listed in §4, not the generic defaults.
    • Designed floating life 20+ years at 20 °C. The float life holds at 20 °C, and it falls away sharply above it — this is the single most expensive lesson in this chemistry.
    • Internal resistance ≈0.49 mΩ fully charged at 20 °C; short-circuit current 4,000 A. A 24-cell string presents about 11.8 mΩ in series and delivers roughly 4,075 A on a hard short.

    The OPzS2-800 2V800Ah sits between the OPzS2-600 and the OPzS2-1000 in the same product range. That position is deliberate: it is the smallest capacity in the range that still absorbs 160 A per cell, which is what a 48 V solar string with any meaningful array needs.

    Key Takeaways

    • 800 Ah at C10, 80 A for 10 hours to 1.80 V per cell at 20 °C. The rating is a 10-hour rate, so size your string on C10, not on the higher 1-hour or 3-hour figures a distributor quotes.
    • 42.0 kg dry, 58 kg with electrolyte, 16 kg of acid. Handling is a two-person job with a trolley, and the floor loading must be checked before the plinth is poured.
    • Maximum charging current 160 A per cell (0.20 C10). A 48 V string accepts 3,840 A, which is about 7.7 kW at nominal bus voltage.
    • Float 2.23 V, equalise 2.35 V per cell, −3 mV/°C/cell compensation, 20+ years float life at 20 °C. Solar and wind duty needs a different setpoint table entirely — see §4.
    • Internal resistance ≈0.49 mΩ, short-circuit current 4,000 A, maximum discharge 2,500 A for 5 s. Protection coordination and cable sizing follow directly from these two numbers.

    §1 — OPzS2-800 2V800Ah Published Specifications

    Every figure below comes from the CHISEN OPzS2-800 factory datasheet. Where a value is a calculation rather than a printed figure, the source column says so. Values the datasheet does not print are written as “not published” rather than estimated, because an estimate on a procurement sheet becomes an engineering assumption nobody re-checks.

    ParameterPublished valueSource
    ModelOPzS2-800Datasheet
    Chemistry and constructionFlooded tubular vented lead-acid: die-cast Pb-Sb tubular positive plate, pasted lead-calcium negative plate, low-resistance PVC composite separator, transparent SAN container, high-strength ABS coverDatasheet
    Nominal voltage2 V per cellDatasheet
    Rated capacity (C10)800 Ah, 80 A for 10 h to 1.80 V per cell at 20 °CDatasheet
    Cell dimensions191 × 210 × 700 mmDatasheet
    Container (jar) height645 mmDatasheet
    Total height over terminals700 mmDatasheet
    Top view210 × 191 mmDatasheet
    Terminal centre spacing108 mm × 110 mmDatasheet
    Weight without electrolyte42.0 kg (92.6 lbs)Datasheet
    Weight with electrolyte58 kg (128 lbs)Datasheet
    Electrolyte (acid) weight16 kg at 1.240 g/cm³Datasheet
    Internal resistance≈0.49 mΩ fully charged at 20 °CDatasheet
    Short-circuit current4,000 ADatasheet
    Maximum discharge current2,500 A for 5 sDatasheet
    Maximum charging current160 ADatasheet
    Charge characteristicConstant-current then constant-voltage, tapering to 0.15 CA below the float voltageDatasheet
    Float charge voltage2.23 V per cell at 25 °C, −3 mV/°C/cell temperature compensationDatasheet
    Equalise charge voltage2.35 V per cell at 25 °C, −5 mV/°C/cell temperature compensation, 20–25 °C rangeDatasheet
    Self-discharge≈4 % per month at 20 °CDatasheet
    Ambient temperature, discharge−25 °C to 65 °CDatasheet
    Ambient temperature, charge−20 °C to 65 °CDatasheet
    Ambient temperature, storage−15 °C to 40 °CDatasheet
    Designed floating life20+ years at 20 °CDatasheet
    Terminal typeFemale copper insert, M8 thread, 20 mm outer diameter, 7 mm thread depthDatasheet
    Terminal tightening torque10–12 N·mDatasheet
    Vent plugsAcid-proof, flame-retardant, explosion-proof; catalytic plug optionalDatasheet
    Applicable standardsIEC 60896-11, DIN 40736, IEC 61427, Eurobat long-life guide, BS 6290 part 4, UL 1989Datasheet
    CertificationsISO 9001, ISO 14001, OHSAS 18001:2007 (GB/T 28001), CE, RUDatasheet

    Solar and wind long-time discharge

    For renewable duty the useful capacity is quoted at a lower cut-off voltage, because the controller protects the battery long before the cell reaches 1.80 V. The datasheet publishes the following capacities at a 1.85 V cut-off:

    RateCapacity at 1.85 V per cellSource
    C24904 AhDatasheet
    C48992 AhDatasheet
    C721,040 AhDatasheet
    C1001,080 AhDatasheet
    C1201,096 AhDatasheet
    C2401,120 AhDatasheet

    §2 — The Pain: Why This Purchase Goes Wrong

    First, the capacity number is a trap. An OPzS2-800 2V800Ah cell is rated at C10. A distributor who quotes “800 Ah” without the rate is quoting a number that does not describe your duty. At a one-hour discharge the cell delivers roughly half its C10 capacity; at a ten-hour discharge it delivers the full figure. A cabinet that must carry a five-minute ride-through at high load sees far less. Specify the rate and the cut-off voltage with the capacity, always together.

    Second, flooded means a room, not a cabinet. Hydrogen evolves from the negative plates during charging, and it needs a path out. Acid-proof flame-retardant vent plugs handle the ignition source; they do not handle the accumulation. Every OPzS2-800 2V800Ah installation needs mechanical ventilation sized for the worst-case float and equalisation charge, plus a person with a hydrometer and a top-up bottle on a schedule. Buyers who treat the flooded cell as a drop-in replacement for a sealed block discover the difference in month three, usually during the first hot season.

    Third, charge acceptance quietly caps the whole project. The published maximum charging current for the OPzS2-800 2V800Ah is 160 A, which is 0.20 C10. At 48 V nominal that is about 7.7 kW. An array sized on the load rather than on the battery is an array the battery cannot absorb. The excess goes into float losses, extended equalisation, or an over-voltage disconnect that trips the inverter out of service.

    Fourth, the float life is temperature-bound, and the datasheet is specific about it. The designed floating life of 20+ years is stated at 20 °C, and it is roughly halved for every 10 °C above that. A power room in Chennai, Durban or Karachi that runs at 30 °C ambient all year is looking at a life closer to ten years, not twenty, and no controller precision changes that. Room cooling is a battery decision, not a comfort decision.

    Fifth, the physical envelope is not negotiable. 191 mm long, 210 mm wide and 700 mm tall over terminals, with 58 kg in the cell once filled. Rack pitch, aisle width, door clearance and the lifting route for a single cell all have to be confirmed against the drawing before the plinth is poured. Substituting a guess is how a delivery arrives that cannot be installed.

    §3 — The Choice: Where the OPzS2-800 Sits

    The alternative to the OPzS2-800 2V800Ah is rarely another chemistry. In the telecom, substation and containerised-renewable markets where this cell is specified, the real choice is the same flooded platform at a different capacity, the gel variant of the same platform, or a sealed VRLA block of a lower capacity.

    Against the neighbouring flooded capacities

    ParameterOPzS2-600 2V600AhOPzS2-800 2V800AhOPzS2-1000 2V1000Ah
    Rated capacity (C10)600 Ah800 Ah1,000 Ah
    Cell dimensions145 × 206 × 645 mm191 × 210 × 700 mm233 × 210 × 645 mm
    Total height over terminals700 mm700 mm700 mm
    Weight without electrolyte32.0 kg42.0 kg53.5 kg
    Weight with electrolyte42.8 kg58 kg73.5 kg
    Internal resistance0.60 mΩ at 20 °C0.49 mΩ at 20 °C0.45 mΩ at 20 °C
    Maximum charging current120 A160 A200 A
    Short-circuit current3,700 A4,000 A4,500 A
    Float voltage2.23 V per cell2.23 V per cell2.23 V per cell
    Designed float life20+ years at 20 °C20+ years at 20 °C20+ years at 20 °C

    All three figures in the middle column are from the OPzS2-800 datasheet; the OPzS2-600 and OPzS2-1000 figures are the published values for those models. Three observations follow directly.

    The OPzS2-800 is the smallest cell in this comparison that still absorbs 160 A per cell. If the array is larger than roughly 7.7 kW on a 48 V bus, the OPzS2-600 at 120 A becomes the limiting element and the OPzS2-1000 at 200 A is the natural step up.

    All three cells share the same 700 mm height over terminals, so a power room designed for one of them can be re-stuffed with another without rebuilding the rack geometry. The footprints differ, however: 145 × 206 mm, 191 × 210 mm and 233 × 210 mm are three different plans, so rack pitch and aisle width still need checking per model.

    Internal resistance falls as capacity rises, from 0.60 mΩ to 0.45 mΩ across the range, and that is what makes a large string electrically cleaner at the same fault duty.

    The 48 V string arithmetic

    Every number below is derived from the published per-cell figures above.

    Derived quantityCalculationResult
    String nominal energy24 × 2 V × 800 Ah38.4 kWh
    String series resistance24 × 0.49 mΩ11.76 mΩ
    String maximum charging current24 × 160 A3,840 A
    String maximum discharge current (5 s)24 × 2,500 A60,000 A
    String weight filled24 × 58 kg1,392 kg
    String weight dry24 × 42.0 kg1,008 kg
    String acid weight24 × 16 kg384 kg
    Short-circuit current at the terminals48 V ÷ 11.76 mΩ≈4,082 A

    The last line is a calculation, not a datasheet figure: the published short-circuit current of 4,000 A governs protection coordination. Use the published number for coordination and treat the derived figure as a sanity check on the wiring.

    Flooded against gel

    If nobody will ever touch the battery — no water top-up, no quarterly equalisation, no hydrometer — the gel version of this platform is the better product, and the OPzS2-800 2V800Ah is the wrong choice. Gel removes the room requirement: no ventilation path, no topping up, no hydrogen accumulation. The cost is a lower published cycle-life floor and marginally higher internal resistance. Make that trade explicitly, because it is a labour decision as much as a chemistry decision.

    §4 — The Framework: Nine Things to Fix Before the Order

    1. Lock the rate with the capacity. Write “OPzS2-800 2V800Ah, 800 Ah at C10 to 1.80 V per cell at 20 °C” on the purchase order, not “800 Ah”. If the duty is a shorter discharge, ask for the capacity at that rate and at the cut-off voltage the controller will use.

    2. Fix the string architecture on paper first. 24 cells at 2 V gives 48 V nominal, which is the common telecom DC bus. 48 cells gives 96 V. Write the cell count, the nominal bus voltage and the end-point voltage at 1.80 V per cell — 43.2 V for a 24-cell string — next to the load list. Every downstream number, from charger rating to cable cross-section, follows from those three figures.

    3. Check the charge ceiling against the array. Maximum charging current is 160 A per cell, so 3,840 A for a 24-cell string, roughly 7.7 kW at 48 V nominal. If the array exceeds that, step up one capacity in the range or fit a charge-current limit in the controller. Decide before the array is ordered.

    4. Use the renewable setpoint table, not the generic one. For solar and wind the datasheet publishes a dedicated set of controller parameters, and they are not the same as the stationary float-and-equalise pair:

    ParameterValueSource
    Over-voltage disconnect2.47 ± 0.01 V per cellDatasheet
    Regulation / equalise voltage2.40 ± 0.01 V per cellDatasheet
    Array reconnection voltage2.23 ± 0.005 V per cellDatasheet
    Float voltage setting2.25 ± 0.005 V per cellDatasheet
    Low-voltage alarm1.95 ± 0.005 V per cellDatasheet
    Low-voltage disconnect1.90 ± 0.005 V per cellDatasheet
    Load reconnect voltage2.09 ± 0.01 V per cellDatasheet
    Temperature compensation coefficient−4 mV per cell per °CDatasheet

    Note the deliberate difference from the stationary setpoints in §1. The renewable float setting is 2.25 V per cell, not 2.23 V, and the renewable compensation coefficient is −4 mV per cell per °C, not −3 mV. The reasons are practical: renewable charging is intermittent, so the controller holds the array at a slightly higher potential to capture what light there is, and the −4 mV coefficient is matched to the wider temperature swing of an outdoor cabinet. Copying the stationary numbers into a solar controller is a common and expensive error.

    5. Design the ventilation path. Hydrogen evolves on charge. Provide mechanical extraction sized for the worst-case charge case, keep flame-retardant acid-proof vent plugs fitted, and confirm the room is not a sealed container with one door.

    6. Schedule the water. An OPzS2-800 cell loses water on every charge cycle. Quarterly top-up with distilled or demineralised water, a quarterly specific-gravity reading on every cell and a logged equalisation at a defined interval are operating requirements, not maintenance extras. Budget the labour; a battery that is never checked fails at the worst time.

    7. Confirm the mechanical envelope against the drawing. For the OPzS2-800: 191 × 210 × 700 mm, 58 kg filled, terminal centre spacing 108 × 110 mm, M8 female insert at 10–12 N·m. Rack pitch, door clearances, the lifting route for a 58 kg cell and the floor loading all need the drawing, not a spreadsheet.

    8. Set the end-of-life criterion now. Define the capacity floor — the percentage of rated C10 at which the string is replaced — and put it in the maintenance plan with a date attached. Without a written criterion, end-of-life is a judgement call made under pressure during an outage.

    9. Order the spares policy deliberately. Cells in a series string age unevenly. Decide in advance whether you hold one spare OPzS2-800 cell on site, and note that a spare must be the same model and age band as the string, not a newer cell dropped into an older string.

    §5 — The Trust: Who Built It and What Is Certified

    CHISEN operates 8 production bases with an annual capacity of 70 million kVAh, which is the scale behind the published datasheet rather than a marketing figure on a web page. The OPzS2-800 2V800Ah is built to IEC 60896-11 for stationary lead-acid valves and DIN 40736 for tubular cells, with IEC 61427 and BS 6290 part 4 also applicable and the UL 1989 listing covering the North American side. The Eurobat long-life guide applies to the float-life claim. The manufacturing system is certified to ISO 9001 for quality management and ISO 14001 for environmental management, with OHSAS 18001:2007 (GB/T 28001) covering occupational health and safety, and the product carries CE marking. Every export shipment is documented with CE, UL and IEC certification papers for the exact variant.

    Those standards matter commercially, not just decoratively. DIN 40736 and IEC 60896-11 are what an importer’s technical file has to cite for EU market access; BS 6290 part 4 and UL 1989 are what a buyer in Mumbai, Karachi, Durban or a Gulf port asks for when the battery is going into a tender. The same document set is requested in Rotterdam, Hamburg, Jebel Ali, Santos, Mombasa, Antwerp, Colombo and Lagos: the standards are identical, the local authority requirements are not. The RU marking on this model is the recognised component listing for North American installations.

    The certification set is a claim you can verify rather than take on trust: request the test certificates for the exact model, check that the scope covers the 800 Ah variant, and confirm the certificate address matches the supplier quoting it. This is worth doing before a 24-cell OPzS2-800 string lands on your floor, because a certificate that does not cover the variant is a documentation problem discovered at the wrong moment.

    The 8 production bases and 70 million kVAh of capacity also matter for delivery risk. A 48 V string of 24 OPzS2-800 cells at 58 kg filled is 1,392 kg of battery from one production base, and a mixed-date delivery is a mixed-age string. Ask for the manufacturing date on the cells, and ask that the whole string be produced within one production window.

    §6 — FAQ: OPzS2-800 2V800Ah

    Q1. What is the rated capacity of the OPzS2-800 2V800Ah? 800 Ah at the 10-hour rate, meaning 80 A for 10 hours to a 1.80 V per cell cut-off at 20 °C. The datasheet also publishes renewable long-time discharge capacities at a 1.85 V cut-off, from 904 Ah at C24 up to 1,120 Ah at C240.

    Q2. What are the physical dimensions and weight of one cell? 191 × 210 × 700 mm overall, with a 645 mm container and 700 mm height over terminals. 42.0 kg without electrolyte, 58 kg with electrolyte, and 16 kg of acid at 1.240 g/cm³. One filled cell is a two-person handling job.

    Q3. What float and equalise voltages should the charger use? Float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation, and equalise 2.35 V per cell at 25 °C with −5 mV/°C/cell compensation over a 20–25 °C range. For solar and wind duty the controller setpoints differ — 2.25 V float and a −4 mV per cell per °C coefficient — and are listed in §4.

    Q4. How much current can this cell take during charging? The published maximum charging current is 160 A, which is 0.20 C10. A 24-cell 48 V string therefore accepts 3,840 A, roughly 7.7 kW at nominal bus voltage. Exceeding that limit pushes the array into float losses or triggers an over-voltage disconnect.

    Q5. What are the internal resistance and short-circuit current of the OPzS2-800? Internal resistance is approximately 0.49 mΩ fully charged at 20 °C. The published short-circuit current is 4,000 A, and the maximum discharge current is 2,500 A for 5 s. A 24-cell string presents 11.76 mΩ in series.

    Q6. How long does the OPzS2-800 2V800Ah last in float service? The designed floating life is 20+ years at 20 °C. Float life falls by roughly half for every 10 °C above 20 °C, so an uncooled power room at 30 °C ambient should expect materially less. Keep the room cool and the life figure holds.

    Q7. What maintenance does the OPzS2-800 require? Quarterly water top-up with distilled or demineralised water, a quarterly specific-gravity reading on every cell, equalisation on a logged schedule, and hydrogen ventilation sized for the worst-case charge case. Acid-proof flame-retardant vent plugs must stay fitted.

    Q8. Can this cell be used for solar storage? Yes, and the datasheet publishes a dedicated setpoint table for renewable duty, including the 2.47 ± 0.01 V over-voltage disconnect, the 2.40 ± 0.01 V regulation voltage and the 1.90 ± 0.005 V low-voltage disconnect. The 160 A maximum charging current still applies, so the array must be sized against it.

    Q9. What certifications does the OPzS2-800 2V800Ah carry? Built to IEC 60896-11, DIN 40736, IEC 61427, the Eurobat long-life guide, BS 6290 part 4 and UL 1989. The manufacturing system is certified to ISO 9001 and ISO 14001, with OHSAS 18001:2007 (GB/T 28001), and the product carries CE marking and RU listing.

    Expert Summary

    The OPzS2-800 2V800Ah is a 2 V, 800 Ah flooded tubular cell for 48 V and 96 V DC strings in telecom power rooms, substations and renewable cabinets. Its published envelope is 191 × 210 × 700 mm at 42.0 kg dry and 58 kg filled, with 0.49 mΩ internal resistance, 4,000 A short-circuit current and 160 A maximum charging current.

    Four decisions carry the project. Size on C10 with the cut-off voltage attached to the capacity. Respect the 160 A charge ceiling when the array is specified, or step up one capacity in the range. Use the renewable setpoint table for solar and wind rather than the stationary pair. And budget the labour and ventilation a flooded cell needs, because the 20+ year float life at 20 °C only holds in a maintained, ventilated, temperature-controlled room.

    For a 24-cell 48 V string the arithmetic is 38.4 kWh nominal, 11.76 mΩ in series, 3,840 A of charge acceptance, 1,392 kg of installed battery and 384 kg of acid. Take those five numbers to the civil and electrical design, and the OPzS2-800 2V800Ah will do what the datasheet says it does.

    Contact CHISEN

    Technical enquiries, project drawings and tender documents: sales@chisen.cn and +86 131 6622 6999 on WhatsApp. Mention the model OPzS2-800 and the string voltage you are designing for, and the CHISEN team will supply the certified per-cell datasheet, the certified weight, the drawing and the test certificates for the exact variant.

    Related reading: the OPzS2-800 2V800Ah model page, the OPzS2-600 2V600Ah model page for the cell below it in the range, and the OPzS flooded tubular battery range for the full platform.

    Related CHISEN Buyer Guides

  • OPzS2-2000 2V2000Ah Flooded Tubular Battery: Utility DC Plant and Grid-Scale Storage

    OPzS2-2000 2V2000Ah Flooded Tubular Battery: Utility DC Plant and Grid-Scale Storage

    Answer First

    The OPzS2-2000 2V2000Ah is a 2 V, 2000 amp-hour flooded tubular vented lead-acid cell rated at the ten-hour rate — 200 A for 10 hours to 1.80 V per cell at 20 °C — and it is the right cell when a utility DC plant, a grid-scale solar or wind installation or a major rail substation needs a 48 V or 96 V DC bus holding roughly 96 kWh or 192 kWh nominal per string, and when somebody on site will still top up water and read a hydrometer once a quarter.

    It is not a sealed cabinet. It is a component of a room: hydrogen venting, flame-retardant acid-proof vent plugs, quarterly water top-up, periodic equalisation and a specific-gravity check are part of the product, not optional extras.

    Five facts decide most projects:

    • 399 × 210 × 826 mm, 826 mm over terminals, 106 kg without electrolyte and 146 kg with it. A 24-cell 48 V string is 3,504 kg of battery on the floor before racks, busbar and the room.
    • Maximum charging current 400 A, 0.20 C10. That single limit caps what a solar array can push into the string at about 19.2 kW at 48 V nominal.
    • Float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation; equalise 2.35 V per cell at 25 °C. Charge controllers for renewable duty need the separate setpoints listed in §4, not the generic defaults.
    • Designed floating life 20+ years at 20 °C. The float life holds at 20 °C and falls away sharply above it — this is the most expensive lesson in this chemistry.
    • Internal resistance ≈0.35 mΩ fully charged at 20 °C; short-circuit current 6,000 A. A 24-cell string presents about 8.4 mΩ in series and delivers roughly 5,700 A on a hard short.

    The OPzS2-2000 2V2000Ah is the capacity step that lets a utility project build one string instead of two. At this size the string count, not the cell count, is what moves the civil works: fewer strings means fewer racks, fewer cabinets and fewer parallel DC distribution boards to design, specify and maintain.

    Key Takeaways

    • 2,000 Ah at C10, 200 A for 10 hours to 1.80 V per cell at 20 °C. The rating is a ten-hour rate, so size your string on C10, not on the higher one-hour or three-hour figures a distributor quotes.
    • 106 kg dry, 146 kg with electrolyte, 40 kg of acid. Handling is a two-person job with a trolley, and the floor loading must be checked before the plinth is poured.
    • Maximum charging current 400 A per cell (0.20 C10). A 48 V string accepts 9,600 A, which is about 19.2 kW at nominal bus voltage.
    • Float 2.23 V, equalise 2.35 V per cell, −3 mV/°C/cell compensation, 20+ years float life at 20 °C. Solar and wind duty needs a different setpoint table entirely — see §4.
    • Internal resistance ≈0.35 mΩ, short-circuit current 6,000 A, maximum discharge 3,600 A for 5 s. Protection coordination and cable sizing follow directly from these numbers.

    §1 — OPzS2-2000 2V2000Ah Published Specifications

    Every figure below comes from the CHISEN OPzS2-2000 factory datasheet. Where a value is a calculation rather than a printed figure, the source column says so. Values the datasheet does not print are written as “not published” rather than estimated, because an estimate on a procurement sheet becomes an engineering assumption nobody re-checks.

    ParameterPublished valueSource
    ModelOPzS2-2000Datasheet
    Chemistry and constructionFlooded tubular vented lead-acid: die-cast Pb-Sb tubular positive plate, pasted lead-calcium negative plate, low-resistance PVC composite separator, transparent SAN container, high-strength ABS coverDatasheet
    Nominal voltage2 V per cellDatasheet
    Rated capacity (C10)2,000 Ah, 200 A for 10 h to 1.80 V per cell at 20 °CDatasheet
    Cell dimensions399 × 210 × 826 mmDatasheet
    Container (jar) height772 mmDatasheet
    Total height over terminals826 mmDatasheet
    Top view210 × 399 mmDatasheet
    Terminal centre spacing110 mm × 110 mmDatasheet
    Weight without electrolyte106 kg (234 lbs)Datasheet
    Weight with electrolyte146 kg (322 lbs)Datasheet
    Electrolyte (acid) weight40 kg at 1.240 g/cm³Datasheet
    Internal resistance≈0.35 mΩ fully charged at 20 °CDatasheet
    Short-circuit current6,000 ADatasheet
    Maximum discharge current3,600 A for 5 sDatasheet
    Maximum charging current400 ADatasheet
    Charge characteristicConstant-current then constant-voltage, tapering to 0.15 CA below the float voltageDatasheet
    Float charge voltage2.23 V per cell at 25 °C, −3 mV/°C/cell temperature compensationDatasheet
    Equalise charge voltage2.35 V per cell at 25 °C, 20–25 °C rangeDatasheet
    Self-discharge≈4 % per month at 20 °CDatasheet
    Ambient temperature, discharge−25 °C to 65 °CDatasheet
    Ambient temperature, charge−20 °C to 65 °CDatasheet
    Ambient temperature, storage−15 °C to 40 °CDatasheet
    Designed floating life20+ years at 20 °CDatasheet
    Terminal typeFemale copper insert, M8 thread, 20 mm outer diameter, 7 mm thread depthDatasheet
    Terminal tightening torque10–12 N·mDatasheet
    Vent plugsAcid-proof, flame-retardant, explosion-proof; catalytic plug optionalDatasheet
    Applicable standardsIEC 60896-11, DIN 40736, IEC 61427, Eurobat long-life guide, BS 6290 part 4, UL 1989Datasheet
    CertificationsISO 9001, ISO 14001, GB/T 28001, CE, ULDatasheet

    Solar and wind long-time discharge

    For renewable duty the useful capacity is quoted at a lower cut-off voltage, because the controller protects the battery long before the cell reaches 1.80 V. The datasheet publishes the following capacities at a 1.85 V cut-off:

    RateCapacity at 1.85 V per cellSource
    C242,260 AhDatasheet
    C482,480 AhDatasheet
    C722,600 AhDatasheet
    C1002,700 AhDatasheet
    C1202,740 AhDatasheet
    C2402,800 AhDatasheet

    §2 — The Pain: Why Utility DC Purchases Go Wrong

    First, the capacity number without a rate is not a number. The OPzS2-2000 2V2000Ah is rated at C10. A distributor who quotes “2,000 Ah” without the rate is quoting a figure that does not describe your duty. At a one-hour discharge the cell gives roughly half its C10 capacity; at a ten-hour discharge it gives the full figure. A plant that rides out a multi-day wind drought on a slow discharge sits close to the C10 curve, while a ride-through cabinet with a five-minute discharge at high load sees far less. Specify the rate and the cut-off voltage together with the capacity, always.

    Second, flooded means a room, not a container. Hydrogen evolves during charging and needs a path out. Acid-proof flame-retardant vent plugs handle the ignition source; they do not handle the accumulation. Every OPzS2-2000 installation needs mechanical ventilation sized for the worst-case float and equalisation charge, and it needs a person with a hydrometer and a top-up bottle on a schedule. Buyers who treat the OPzS2-2000 2V2000Ah as a drop-in replacement for a sealed block discover the difference in the first hot season.

    Third, charge acceptance quietly caps the whole project. The published maximum charging current for the OPzS2-2000 is 400 A, which is 0.20 C10. At 48 V nominal that is about 19.2 kW. An array sized on the load rather than on the battery is an array the battery cannot absorb. The excess goes into float losses, extended equalisation, or an over-voltage disconnect that takes the inverter out of service. The array is the expensive half of a utility project, so fix this number before the panels are ordered.

    Fourth, the float life is temperature-bound, and the datasheet is specific about it. The designed floating life of 20+ years is stated at 20 °C, and it is roughly halved for every 10 °C above that. A container in Chennai, Durban or Karachi that runs at 30 °C ambient all year is looking at a life closer to ten years, not twenty, and no controller precision changes that. Room cooling is a battery decision, not a comfort decision.

    Fifth, the physical envelope is not negotiable. 399 mm long, 210 mm wide and 826 mm tall over terminals, with 146 kg filled. Rack pitch, aisle width, door clearance and the lifting route for a single cell all have to be confirmed against the drawing before the plinth is poured. Substituting a guess is how a delivery arrives that cannot be installed.

    §3 — The Choice: Where the OPzS2-2000 Sits

    The alternative to the OPzS2-2000 2V2000Ah is rarely another chemistry. In grid-scale renewable, utility telecom and traction markets where this cell is specified, the real choice is the same flooded platform at a different capacity, the gel variant of the same platform, or a sealed VRLA block of a lower capacity.

    Against the neighbouring flooded capacities

    ParameterOPzS2-1500 2V1500AhOPzS2-2000 2V2000AhOPzS2-3000 2V3000Ah
    Rated capacity (C10)1,500 Ah2,000 Ah3,000 Ah
    Cell dimensions275 × 210 × 850 mm399 × 210 × 826 mm576 × 212 × 771 mm
    Total height over terminals850 mm826 mm771 mm
    Weight without electrolyte71.0 kg106 kg155 kg
    Weight with electrolyte98 kg146 kg218 kg
    Internal resistance0.40 mΩ at 20 °C0.35 mΩ at 20 °C0.24 mΩ at 20 °C
    Maximum charging current300 A400 A600 A
    Short-circuit current5,400 A6,000 ANot published
    Float voltage2.23 V per cell2.23 V per cell2.23 V per cell
    Designed float life20+ years at 20 °C20+ years at 20 °C20+ years at 20 °C

    The middle column is the OPzS2-2000 datasheet; the OPzS2-1500 and OPzS2-3000 figures are the published values for those models. Three observations follow directly.

    The OPzS2-2000 absorbs 400 A per cell, so a 48 V string of 24 cells accepts 9,600 A, which covers an array of roughly 19.2 kW on one string. Below that the OPzS2-1500 at 300 A is the natural choice; above it the OPzS2-3000 at 600 A is.

    Internal resistance falls from 0.40 mΩ to 0.24 mΩ across this range, which makes a large string electrically cleaner at the same fault duty and why voltage recovery after a load step is less punishing on the bigger cells.

    Footprints and heights are not shared across the range: 275 × 210, 399 × 210 and 576 × 212 mm with three different heights. A rack built for one cell is not a rack for another, so the OPzS2-2000 drawing governs the aisle and the lifting route.

    The 48 V string arithmetic

    Every number below is derived from the published per-cell figures above.

    Derived quantityCalculationResult
    String nominal energy24 × 2 V × 2,000 Ah96 kWh
    String series resistance24 × 0.35 mΩ8.40 mΩ
    String maximum charging current24 × 400 A9,600 A
    String maximum discharge current (5 s)24 × 3,600 A86,400 A
    String weight filled24 × 146 kg3,504 kg
    String weight dry24 × 106 kg2,544 kg
    String acid weight24 × 40 kg960 kg
    Short-circuit current at the terminals48 V ÷ 8.40 mΩ≈5,700 A

    The last line is a calculation, not a datasheet figure: the published short-circuit current of 6,000 A is the manufacturer’s value for the cell and governs protection coordination. Use the published number for coordination and treat the derived figure as a sanity check on the wiring.

    Flooded against gel

    If nobody will ever touch the battery — no water top-up, no quarterly equalisation, no hydrometer — the gel version of this platform is the better product, and the OPzS2-2000 2V2000Ah is the wrong choice. Gel removes the room requirement: no ventilation path, no topping up, no hydrogen accumulation. The cost is a lower published cycle-life floor and marginally higher internal resistance. Make that trade explicitly, because it is a labour decision as much as a chemistry decision.

    §4 — The Framework: Nine Things to Fix Before the Order

    1. Lock the rate with the capacity. Write “OPzS2-2000 2V2000Ah, 2,000 Ah at C10 to 1.80 V per cell at 20 °C” on the purchase order, not “2,000 Ah”. If the duty is a shorter discharge, ask for the capacity at that rate and at the cut-off voltage the controller will use.

    2. Fix the string architecture on paper first. 24 cells at 2 V gives 48 V nominal, which is the common utility and telecom DC bus. 48 cells gives 96 V. Write the cell count, the nominal bus voltage and the end-point voltage at 1.80 V per cell — 43.2 V for a 24-cell string — next to the load list. Every downstream number, from charger rating to cable cross-section, follows from those three figures.

    3. Check the charge ceiling against the array. Maximum charging current is 400 A per cell, so 9,600 A for a 24-cell string, roughly 19.2 kW at 48 V nominal. If the array exceeds that, step up one capacity in the range or fit a charge-current limit in the controller. Decide before the array is ordered.

    4. Use the renewable setpoint table, not the generic one. For solar and wind the datasheet publishes a dedicated set of controller parameters, and they are not the same as the stationary float-and-equalise pair:

    ParameterValueSource
    Over-voltage disconnect2.47 ± 0.01 V per cellDatasheet
    Regulation / equalise voltage2.40 ± 0.01 V per cellDatasheet
    Array reconnection voltage2.23 ± 0.005 V per cellDatasheet
    Float voltage setting2.25 ± 0.005 V per cellDatasheet
    Low-voltage alarm1.95 ± 0.005 V per cellDatasheet
    Low-voltage disconnect1.90 ± 0.005 V per cellDatasheet
    Load reconnect voltage2.09 ± 0.01 V per cellDatasheet
    Temperature compensation coefficient−4 mV per cell per °CDatasheet

    Note the deliberate difference from the stationary setpoints in §1. The renewable float setting is 2.25 V per cell, not 2.23 V, and the renewable compensation coefficient is −4 mV per cell per °C, not −3 mV. Renewable charging is intermittent, so the controller holds the array at a slightly higher potential to capture what light there is, and the −4 mV coefficient is matched to the wider temperature swing of an outdoor cabinet. Copying the stationary numbers into a solar controller is a common and expensive error.

    5. Design the ventilation path. Hydrogen evolves on charge. Provide mechanical extraction sized for the worst-case charge case, keep flame-retardant acid-proof vent plugs fitted, and confirm the room is not a sealed container with one door.

    6. Schedule the water. An OPzS2-2000 cell loses water on every charge cycle. Quarterly top-up with distilled or demineralised water, a quarterly specific-gravity reading on every cell and a logged equalisation at a defined interval are operating requirements, not maintenance extras. Budget the labour; a battery that is never checked fails at the worst time.

    7. Confirm the mechanical envelope against the drawing. For the OPzS2-2000: 399 × 210 × 826 mm, 146 kg filled, terminal centre spacing 110 × 110 mm, M8 female insert at 10–12 N·m. Rack pitch, door clearances, the lifting route for a 146 kg cell and the floor loading all need the drawing, not a spreadsheet.

    8. Set the end-of-life criterion now. Define the capacity floor — the percentage of rated C10 at which the string is replaced — and put it in the maintenance plan with a date attached. Without a written criterion, end-of-life is a judgement call made under pressure during an outage.

    9. Order the spares policy deliberately. Cells in a series string age unevenly. Decide in advance whether you hold one spare OPzS2-2000 cell on site, and note that a spare must be the same model and age band as the string, not a newer cell dropped into an older string.

    §5 — The Trust: Who Built It and What Is Certified

    CHISEN operates 8 production bases with an annual capacity of 70 million kVAh, which is the scale behind the published datasheet rather than a marketing figure on a web page. The OPzS2-2000 2V2000Ah is built to IEC 60896-11 for stationary lead-acid valves and DIN 40736 for tubular cells, with IEC 61427 and BS 6290 part 4 also applicable and the UL 1989 listing covering the North American side. The Eurobat long-life guide applies to the float-life claim. The manufacturing system is certified to ISO 9001 for quality management and ISO 14001 for environmental management, with GB/T 28001 covering occupational health and safety, and the product carries CE marking. Every export shipment is documented with CE, UL and IEC certification papers for the exact variant.

    Those standards matter commercially, not just decoratively. DIN 40736 and IEC 60896-11 are what an importer’s technical file has to cite for EU market access; BS 6290 part 4 and UL 1989 are what a buyer in Mumbai, Karachi, Durban or a Gulf port asks for when the battery is going into a tender. The same document set is requested in Rotterdam, Hamburg, Jebel Ali, Santos, Mombasa, Antwerp, Colombo and Lagos: the standards are identical, the local authority requirements are not.

    The certification set is a claim you can verify rather than take on trust: request the test certificates for the exact model, check that the scope covers the 2,000 Ah variant, and confirm the certificate address matches the supplier quoting it. Do this before a 24-cell OPzS2-2000 string lands on your floor, because a certificate that does not cover the variant is a documentation problem discovered at the wrong moment.

    The 8 production bases and 70 million kVAh of capacity also matter for delivery risk on a large project. A 48 V string of 24 OPzS2-2000 cells at 146 kg filled is 3,504 kg of battery from one production base, and a mixed-date delivery is a mixed-age string. Ask for the manufacturing date on the cells, and ask that the whole string be produced within one production window.

    §6 — FAQ: OPzS2-2000 2V2000Ah

    Q1. What is the rated capacity of the OPzS2-2000 2V2000Ah? 2,000 Ah at the ten-hour rate, meaning 200 A for 10 hours to a 1.80 V per cell cut-off at 20 °C. The datasheet also publishes renewable long-time discharge capacities at a 1.85 V cut-off, from 2,260 Ah at C24 up to 2,800 Ah at C240.

    Q2. What are the physical dimensions and weight of one OPzS2-2000 cell? 399 × 210 × 826 mm overall, with a 772 mm container and 826 mm height over terminals. 106 kg without electrolyte, 146 kg with electrolyte, and 40 kg of acid at 1.240 g/cm³. One filled cell is a two-person handling job.

    Q3. What float and equalise voltages should the charger use? Float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation, and equalise 2.35 V per cell at 25 °C over a 20–25 °C range. For solar and wind duty the controller setpoints differ — 2.25 V float and a −4 mV per cell per °C coefficient — and are listed in §4.

    Q4. How much current can the OPzS2-2000 take during charging? The published maximum charging current is 400 A, which is 0.20 C10. A 24-cell 48 V string therefore accepts 9,600 A, roughly 19.2 kW at nominal bus voltage. Exceeding that limit pushes the array into float losses or triggers an over-voltage disconnect.

    Q5. What are the internal resistance and short-circuit current of the OPzS2-2000? Internal resistance is approximately 0.35 mΩ fully charged at 20 °C. The published short-circuit current is 6,000 A, and the maximum discharge current is 3,600 A for 5 s. A 24-cell string presents 8.40 mΩ in series.

    Q6. How long does the OPzS2-2000 2V2000Ah last in float service? The designed floating life is 20+ years at 20 °C. Float life falls by roughly half for every 10 °C above 20 °C, so an uncooled container at 30 °C ambient should expect materially less.

    Q7. What maintenance does the OPzS2-2000 require? Quarterly water top-up with distilled or demineralised water, a quarterly specific-gravity reading on every cell, equalisation on a logged schedule, and hydrogen ventilation sized for the worst-case charge case. Acid-proof flame-retardant vent plugs must stay fitted.

    Q8. Can the OPzS2-2000 2V2000Ah be used for solar storage? Yes, and the datasheet publishes a dedicated setpoint table for renewable duty, including the 2.47 ± 0.01 V over-voltage disconnect, the 2.40 ± 0.01 V regulation voltage and the 1.90 ± 0.005 V low-voltage disconnect. The 400 A maximum charging current still applies, so the array must be sized against it.

    Q9. What certifications does the OPzS2-2000 2V2000Ah carry? Built to IEC 60896-11, DIN 40736, IEC 61427, the Eurobat long-life guide, BS 6290 part 4 and UL 1989. The manufacturing system is certified to ISO 9001 and ISO 14001, with GB/T 28001, and the product carries CE marking and UL documentation.

    Expert Summary

    The OPzS2-2000 2V2000Ah is a 2 V, 2,000 Ah flooded tubular cell for 48 V and 96 V DC strings in utility DC plants, grid-scale renewable installations and major traction substations. Its published envelope is 399 × 210 × 826 mm at 106 kg dry and 146 kg filled, with 0.35 mΩ internal resistance, a 6,000 A short-circuit current and a 400 A maximum charging current.

    Four decisions carry the project. Size on C10 with the cut-off voltage attached to the capacity. Respect the 400 A charge ceiling when the array is specified, or step up one capacity in the range. Use the renewable setpoint table for solar and wind rather than the stationary pair. And budget the labour and ventilation a flooded cell needs, because the 20+ year float life at 20 °C only holds in a maintained, ventilated, temperature-controlled room.

    For a 24-cell 48 V string the arithmetic is 96 kWh nominal, 8.40 mΩ in series, 9,600 A of charge acceptance, 3,504 kg of installed battery and 960 kg of acid. Take those five numbers to the civil and electrical design, and the OPzS2-2000 2V2000Ah will do what the datasheet says it does.

    Contact CHISEN

    Technical enquiries, project drawings and tender documents: sales@chisen.cn and +86 131 6622 6999 on WhatsApp. Mention the model OPzS2-2000 and the string voltage you are designing for, and the CHISEN team will supply the certified per-cell datasheet, the certified weight, the drawing and the test certificates for the exact variant.

    Related reading: the OPzS2-2000 2V2000Ah model page, the OPzS2-1500 2V1500Ah model page for the cell below it in the range, and the OPzS flooded tubular battery range for the full platform.

    Related CHISEN Buyer Guides

  • 12V 200Ah Solar Battery: Build a Bank from 6-EVF-100

    12V 200Ah Solar Battery: Build a Bank from 6-EVF-100

    Answer First

    There is no single 12V 200Ah cell in the CHISEN range, and a buyer who expects one will waste weeks comparing quotations that nobody can honour: the standard way to build a 12V 200Ah solar battery bank is two 12V 100Ah AGM blocks — the 6-EVF-100 — wired in parallel, which gives 12 V × 200 Ah = 2,400 Wh, weighs 2 × 31.5 kg = 63.0 kg and accepts 2 × 20.0 A = 40.0 A of charge current, while the single-unit alternatives inside the same 12V EVF range are the 6-EVF-120, 6-EVF-135 and 6-EVF-150. This guide sets out the published specification of those four cells, shows the arithmetic for the two-unit bank and the 48 V pack built on it, and gives the seven checks to run before you order from a supplier in Hangzhou, Rotterdam, Jebel Ali, Lagos or Chennai.

    Key Takeaways

    • CHISEN publishes no 12V 200Ah model: the 12V 200Ah solar battery bank is two 6-EVF-100 12V 100Ah AGM blocks in parallel, which is 12 V × 200 Ah = 2,400 Wh.
    • The bank weighs 2 × 31.5 kg = 63.0 kg and its maximum charge current is 2 × 20.0 A = 40.0 A; specific energy is 2,400 Wh ÷ 63.0 kg = 38.1 Wh/kg.
    • The published 100 Ah is a C3 rating; the 10-hour rate (C10) is not published on these pages, so a daily cycle sized on a 10-hour discharge must be quoted against a C10 figure the factory still has to supply.
    • Single-unit options in the same range give 1,440 Wh at 36.0 Wh/kg (6-EVF-120), 1,620 Wh at 36.0 Wh/kg (6-EVF-135) and 1,800 Wh at 37.1 Wh/kg (6-EVF-150), against 38.1 Wh/kg for the parallel pair.
    • Float 13.5 V and equalisation 14.1 V for the block — 2.25 V and 2.35 V per cell — are the setpoints to fix in writing; cycle life is published at 350–600 cycles at 50–80 % depth of discharge and design life at 2–5 years.

    §1 — 12V 200Ah Solar Battery Specifications

    The table below reproduces the published specification of the four 12V EVF cells that bracket the 200Ah solar duty, so the bank you specify can be defended line by line at the goods-in dock. Every cell figure comes from the manufacturer model page; derived figures are shown with their formulas.

    Specification6-EVF-1006-EVF-1206-EVF-1356-EVF-150Source
    Nominal voltage12 V12 V12 V12 VModel page
    Rated capacity100 Ah120 Ah135 Ah150 AhModel page
    Discharge rate basisC3 (3 h)C3 (3 h)C3 (3 h)C3 (3 h)Model page
    Dimensions L × W × H330 × 170 × 218 mm407 × 170 × 240 mm338 × 172 × 280 mm483 × 170 × 240 mmModel page
    Weight31.5 ± 0.2 kg40 ± 0.2 kg45 ± 0.2 kg48.5 ± 0.2 kgModel page
    Terminalφ20-M8φ20-M8φ20-M8φ20-M8Model page
    Maximum charge current20.0 A24.0 A27.0 A30.0 AModel page
    Charge current as C-rate20.0 A ÷ 100 Ah = 0.2C24.0 A ÷ 120 Ah = 0.2C27.0 A ÷ 135 Ah = 0.2C30.0 A ÷ 150 Ah = 0.2CArithmetic
    Float charge voltage13.5 V13.5 V13.5 V13.5 VModel page
    Equalisation voltage14.1 V14.1 V14.1 V14.1 VModel page
    Cycle life (DoD 50–80 %)350–600 cycles350–600 cycles350–600 cycles350–600 cyclesModel page
    Cut-off voltage1.75 V/cell1.75 V/cell1.75 V/cell1.75 V/cellModel page
    Self-discharge≤ 3 %/month at 25 °C≤ 3 %/month at 25 °C≤ 3 %/month at 25 °C≤ 3 %/month at 25 °CModel page
    Working temperature−15 °C to 50 °C−15 °C to 50 °C−15 °C to 50 °C−15 °C to 50 °CModel page
    Design life2–5 years2–5 years2–5 years2–5 yearsModel page
    Energy per cell12 V × 100 Ah = 1,200 Wh12 V × 120 Ah = 1,440 Wh12 V × 135 Ah = 1,620 Wh12 V × 150 Ah = 1,800 WhArithmetic
    Specific energy1,200 Wh ÷ 31.5 kg = 38.1 Wh/kg1,440 Wh ÷ 40 kg = 36.0 Wh/kg1,620 Wh ÷ 45 kg = 36.0 Wh/kg1,800 Wh ÷ 48.5 kg = 37.1 Wh/kgArithmetic
    Series build published4 = 48 V, 5–6 = 60–72 V, 8 = 96 V4 = 48 V, 5–6 = 60–72 V, 8 = 96 V4 = 48 V, 5–6 = 60–72 V, 8 = 96 V4 = 48 V, 5–6 = 60–72 V, 8 = 96 VModel page
    Published applicationsSightseeing vehicles, golf carts, forklifts, floor scrubbers, AGVs, electric boatsSightseeing vehicles, golf carts, forklifts, floor scrubbers, AGVs, electric boatsSightseeing vehicles, golf carts, forklifts, floor scrubbers, AGVs, electric boatsSightseeing vehicles, golf carts, forklifts, floor scrubbers, AGVs, electric boatsModel page

    Two rows deserve a note before they go into a purchase order. The float and equalisation figures are block values across the six cells in series, so 13.5 V is 2.25 V per cell and 14.1 V is 2.35 V per cell; a charger set to 14.4 V will shorten service life without adding usable capacity. And the rated capacity is quoted at the three-hour rate, not the rate at which a solar day discharges it.

    §2 — The Pain

    Three failures account for almost every 12V 200Ah solar battery complaint that reaches a distributor’s technical desk in Hamburg, Durban or Mombasa.

    The first is the label. A carton marked “12V 200Ah” tells you nothing about the case, the terminals, the rate basis of the capacity or the charge setpoints. Two suppliers can both print “12V 200Ah AGM” and deliver two different banks: one built from two 100Ah blocks with a published 63.0 kg weight, the other from two lesser cells with no published weight at all. A buyer who quotes capacity alone gets a bank that does not fit the cabinet and does not match the charger.

    The second is the rate basis. A bank assembled from two 100Ah blocks holds 200 Ah at the three-hour rate. A solar day is a ten-hour discharge, and the capacity available in that window is lower than the headline figure. If the bank is sized on the published C3 number and not on a C10 figure, the site runs out of energy before the array is fully used, and the owner blames the battery instead of the sizing. None of the four model pages publishes a ten-hour rate, so that figure has to be requested from the factory in writing.

    The third is wiring. Two blocks in parallel must be matched: equal-length interconnecting leads, the same date code on both units, and a fuse or breaker on each string. A bank built from two units of different age will not share current evenly, and the older cell fails first. Nothing in the model page protects against that; only the assembly instruction does.

    Underneath those three sits a sourcing problem. Buyers in Lagos, Chennai, Cairo and Jakarta regularly receive a quotation listing “12V 200Ah solar battery, top quality, top grade” with no datasheet reference, which makes the order impossible to compare between suppliers and impossible to re-order next season.

    §3 — The Choice

    Choosing the build for a 12V 200Ah solar bank is a trade between four published quantities: the footprint on the cabinet shelf, the weight a technician has to lift, the energy per kilogram, and the charger size. The table below sets the five realistic options against each other.

    12V 200Ah build optionUnits usedNominal energyBank weightSpecific energyCharge currentFootprintSource
    Two 6-EVF-100 in parallel2 × 12V 100Ah12 V × 200 Ah = 2,400 Wh2 × 31.5 kg = 63.0 kg2,400 Wh ÷ 63.0 kg = 38.1 Wh/kg2 × 20.0 A = 40.0 A2 units side by side: 330 + 30 + 330 = 690 mm long × 170 mm wide × 218 mm highArithmetic
    One 6-EVF-1201 × 12V 120Ah12 V × 120 Ah = 1,440 Wh40 kg1,440 Wh ÷ 40 kg = 36.0 Wh/kg24.0 A407 × 170 × 240 mmModel page
    One 6-EVF-1351 × 12V 135Ah12 V × 135 Ah = 1,620 Wh45 kg1,620 Wh ÷ 45 kg = 36.0 Wh/kg27.0 A338 × 172 × 280 mmModel page
    One 6-EVF-1501 × 12V 150Ah12 V × 150 Ah = 1,800 Wh48.5 kg1,800 Wh ÷ 48.5 kg = 37.1 Wh/kg30.0 A483 × 170 × 240 mmModel page
    Four 6-EVF-100 in series, 48 V4 × 12V 100Ah48 V × 100 Ah = 4,800 Wh4 × 31.5 kg = 126.0 kg4,800 Wh ÷ 126.0 kg = 38.1 Wh/kg4 × 20.0 A = 80.0 A4 side by side: 330 mm long × 4 × 170 = 680 mm wide × 218 mm highArithmetic

    Read the table as four answers to four different questions. In the single-unit rows the weight, charge current and footprint are published model-page values; the energy and specific-energy columns are derived from them and shown with their formulas.

    If the site genuinely needs 200 Ah at 12 V, the parallel pair of 6-EVF-100 blocks is the only build in the table that delivers it: 2,400 Wh at 63.0 kg and 38.1 Wh/kg, the best specific energy of the 12V options listed. The full cell data sits on the 6-EVF-100 model page, and the 6-EVF-150 model page carries the reference cell most distributors already hold.

    If the cabinet is narrow and the load can live with 150 Ah, the single 6-EVF-150 wins on simplicity: one block instead of two, one string instead of two parallel strings, and 37.1 Wh/kg against 38.1 Wh/kg for the pair. It also carries a published cycle rating of 350–600 cycles at 50–80 % depth of discharge compliant with GB/T 32620.1 — the standard written into the model page rather than into a marketing sheet.

    If the site runs at 48 V — normal for a telecom cabinet or a larger solar house — four cells in series give 48 V × 100 Ah = 4,800 Wh at 126.0 kg and require an 80.0 A charger, set by the published maximum charge current of 20.0 A per cell rather than by rule of thumb.

    If the footprint rather than the weight binds, note that the two-unit bank is longer but lower: 690 mm across two housings at 218 mm high, against 483 mm long and 240 mm high for a single 6-EVF-150. On a 680 mm shelf a four-cell 48V string fits; on a 700 mm shelf the 690 mm pair fits; on a 500 mm bracket only a single block fits.

    §4 — The Framework

    Seven checks turn a vague enquiry into an order a factory can fill correctly.

    1. Ask for the published figure set, not the label. Require capacity with its rate basis, dimensions in millimetres, weight with tolerance, terminal type, float and equalisation voltage, maximum charge current, cycle rating, cut-off voltage and working temperature. A supplier that answers all ten is not guessing; one that answers “12V 200Ah AGM” is.

    2. Fix the rate basis before the capacity. Ask for the capacity at the ten-hour rate for the duty you actually have, and treat a supplier who cannot supply it as one who has not read the cell. The published C3 figures in §1 are correct; they answer a different question.

    3. Write the charge setpoints into the order. 13.5 V float and 14.1 V equalisation for the block, 2.25 V and 2.35 V per cell once the arithmetic is done. Confirm the controller can be configured to both, confirm the equalisation period and confirm the temperature-compensation input if the cabinet runs hot. A 25 °C setpoint in a 45 °C cabinet is an over-charge condition.

    4. Size the charger from the published charge current. The 6-EVF-100 accepts 20.0 A, so a two-block bank needs 2 × 20.0 A = 40.0 A, which is 0.2C on a 200 Ah bank. A smaller charger stretches the recharge window and leaves the bank partly discharged for longer.

    5. Check the temperature envelope and the ventilation. The published working range is −15 °C to 50 °C and capacity is quoted at 25 °C. A cabinet in Chennai, Jebel Ali or Santos will not see 25 °C for most of the year; ask what capacity remains at the extremes and confirm the ventilation.

    6. Specify the parallel assembly. Equal-length leads, matched date codes, one breaker per string, and the same cell in both strings of every bank. Put this on the order acknowledgement, because it is the part the factory cannot see when the container is sealed.

    7. Agree the acceptance test on arrival. For shipments into Rotterdam, Jebel Ali, Lagos or Port Said, state what happens on arrival: a sample capacity check at the agreed rate, a float voltage check across the block, and the rule that a failing sample is settled by re-inspection at an agreed laboratory.

    §5 — The Trust

    These cells are built on a VRLA line inside a manufacturer operating 8 production bases with an annual capacity of 70 million kVAh, under ISO 9001 and ISO 14001 certification, with CE, UL and IEC conformity for the markets each cell ships into. Every figure here comes from an individual model page rather than a catalogue summary, and the wider 12V range sits on the CHISEN 12V VRLA product index.

    Two points deserve emphasis for a buyer who is being asked to pay for assurance. First, a certificate covers a system, a scope and a date — ISO 9001 certifies that the quality management system is documented and that corrective action happens; it does not certify that one cell holds 100 Ah at C3. That is what the published capacity, the type test and the acceptance test are for. Ask for the certificate number, the scope statement and the validity dates.

    Second, the difference between a published specification and a marketing line is the whole value of this exercise. A supplier who quotes “12V 200Ah solar battery, premium quality” is telling you nothing. A supplier who quotes “6-EVF-100 × 2 in parallel, 12 V 200 Ah at C3, 2,400 Wh, 63.0 kg, 40.0 A maximum charge current, float 13.5 V, equalisation 14.1 V” is telling you everything you need to draw the cabinet, size the charger and defend the claim at the goods-in dock.

    For importers who buy through a distributor rather than direct, ask for the manufacturer’s model page URL and the batch reference. Both can be checked before the container is opened, and both remove the largest source of dispute in this category.

    §6 — FAQ

    Q1. Is there a 12V 200Ah battery model? No. CHISEN publishes 12V cells from 12 Ah upward in the 6-DZF and 6-DMF series and from 24 Ah upward in the 6-EVF series, and the largest published 12V cell is the 6-EVF-150 at 150 Ah. No single cell is rated 200 Ah at 12 V, so a 12V 200Ah bank has to be assembled from two 100 Ah blocks in parallel, which is what this guide sizes.

    Q2. How many 12V 100Ah batteries do I need for 200Ah? Two, wired in parallel. In parallel the voltage stays at 12 V and the capacity adds: 12 V × 200 Ah = 2,400 Wh. In series the capacity stays at 100 Ah and the voltage doubles to 24 V. Parallel requires equal-length leads and matched cells; series requires matched voltage at the start of the string.

    Q3. What does the bank weigh? 2 × 31.5 kg = 63.0 kg for two 6-EVF-100 blocks, plus busbars, insulators and the cabinet. A single 6-EVF-150 weighs 48.5 kg and a 6-EVF-135 weighs 45 kg, so the parallel pair is 14.5 kg heavier than one 150 Ah cell and 18.0 kg heavier than one 135 Ah cell, while carrying 50 Ah and 65 Ah more at 12 V.

    Q4. What charger do I need for a 12V 200Ah bank? A 12 V charger with a 40.0 A output, because the published maximum charge current is 20.0 A per cell and 2 × 20.0 A = 40.0 A. That is 0.2C on a 200 Ah bank, and the recharge window at that current is 200 Ah ÷ 40.0 A = 5.0 hours. Set float at 13.5 V and equalisation at 14.1 V for the block.

    Q5. Is the published 100 Ah usable for a solar day? The published figure is a C3 rating. On a ten-hour discharge the usable capacity is lower, and the ten-hour rate is not published on the model page. Size the array on a figure the factory supplies in writing at the ten-hour rate, or apply the derating your own engineering standard requires.

    Q6. Which is better for solar standby, a 12V 200Ah AGM bank or a 48V bank of four cells? Different tools. A 12V 200Ah bank gives 2,400 Wh at 63.0 kg and needs a 40.0 A charger; a 48V bank of four 6-EVF-100 cells gives 4,800 Wh at 126.0 kg and needs an 80.0 A charger. The 48V string halves the cable current for the same power and is the normal choice above about 2 kW of load.

    Q7. How long will a 12V 200Ah solar battery bank last? In float standby with solar charging, the published design life is 2–5 years and the cycle rating 350–600 cycles at 50–80 % depth of discharge. In solar duty the binding factor is usually the number of cycles the site sees, not the calendar. A site in Chennai or Jebel Ali will find the temperature envelope as decisive as the cycle count.

    Q8. Can I mix a 6-EVF-100 and a 6-EVF-120 in the same bank? Technically the voltages are equal, but the capacities are not, and the 20.0 A and 24.0 A charge-current figures differ. Current in a parallel pair divides by capacity, so the smaller cell carries more than its share. Keep a bank on identical cells, or on matched strings with the same capacity and date code.

    Q9. What should be on the purchase order for a 12V 200Ah solar battery bank? The cell model and quantity, the parallel arrangement, the float and equalisation voltages, the maximum charge current, the rate basis of the capacity, the cycle rating and depth of discharge, the terminal type, the date code match, the test certificate and the acceptance procedure on arrival. For Rotterdam, Santos or Mombasa, name the agreed laboratory for a failing-sample inspection.

    Q10. Do I need a temperature-compensated charger? For a cabinet that regularly exceeds 30 °C, yes. The published float voltage of 13.5 V assumes 25 °C, and a fixed setpoint in a hot cabinet is an over-charge condition that shows up as shortened service life and more frequent water loss rather than as a fault report.

    Expert Summary

    A 12V 200Ah solar battery bank is a build, not a product code: two 6-EVF-100 12V 100Ah AGM blocks in parallel, giving 12 V × 200 Ah = 2,400 Wh at 2 × 31.5 kg = 63.0 kg, a specific energy of 2,400 Wh ÷ 63.0 kg = 38.1 Wh/kg, and a maximum charge current of 2 × 20.0 A = 40.0 A. The published specification behind that build is 12 V, 100 Ah at C3, 330 × 170 × 218 mm, 31.5 ± 0.2 kg, float 13.5 V, equalisation 14.1 V, 350–600 cycles at 50–80 % depth of discharge and 2–5 years design life; the single-unit alternatives are the 6-EVF-120, 6-EVF-135 and 6-EVF-150.

    The commercial value of specifying precisely exceeds the price difference between the builds. A quotation written against published figures can be compared across three suppliers in ten minutes and defended at the goods-in dock. One written against a label cannot be compared at all, and the difference appears three months later as a warranty claim.

    Two figures deserve a final emphasis for buyers working outside Europe. First, the 40.0 A charger requirement comes from the published charge current, not from marketing: if the charger is smaller, the recharge window stretches and the bank spends more of its life half-discharged, which is the condition that sulphates a plate. Second, the published capacity is a C3 figure and the ten-hour rate is not published, so any solar array sized on the headline number is sized on the wrong number until the factory supplies the rate for your duty.

    For importers into markets served from Rotterdam, Jebel Ali, Santos, Lagos or Chennai, the sequence that works is simple: fix the published specification first, then let suppliers compete on it. The §1 figure set is enough to run that process.

    Contact CHISEN

    Send the target application, the required capacity at the discharge rate you actually have, the cabinet dimensions you need to fit and the quantity to the CHISEN export desk, and you will receive a quotation against the published specification, the datasheet and the lead time.

    • Email: jack@chisen.cn or sales@chisen.cn
    • WhatsApp: +86 131 6622 6999
    • 6-EVF-100 model page: https://www.chisen.cn/en/6-EVF-100/12V100Ah.html
    • 6-EVF-150 model page: https://www.chisen.cn/en/6-EVF-150/12V150Ah.html
    • 12V VRLA product index: https://www.chisen.cn/en/LeadacidBattery/EVF.html

    Related reading on the CHISEN knowledge centre: 12V VRLA selection guidance, deep-cycle charge setpoints, and pack-sizing method for solar house and telecom applications.

    CHISEN Battery — lead-acid cells and systems for telecom, solar, UPS, AGV and traction applications. 8 production bases, 70 million kVAh annual capacity, ISO 9001 and ISO 14001 certified.

    Related CHISEN Buyer Guides

  • 12V 32Ah E-Bike Battery: 6-DMF-32 Against 6-DZF-20 and the 35Ah / 38Ah Options (2026)

    12V 32Ah E-Bike Battery: 6-DMF-32 Against 6-DZF-20 and the 35Ah / 38Ah Options (2026)

    Answer First

    A 12V 32Ah e-bike battery is not one published product, and that decides your order: CHISEN publishes electric bicycles, e-bikes and electric wheelchairs on the 6-DZF-20 at 12V 20 Ah, while the published 12V 32 Ah cell is the 6-DMF-32, rated for passenger and freight electric tricycles, electric motorcycles and mopeds, electric sanitation trucks and sprayers, and electric sightseeing vehicles. The two are also quoted on different rate bases — 20 Ah at C2 (2 h) for the 6-DZF-20 against 32 Ah at C3 (3 h) for the 6-DMF-32 — so any comparison that places the amp-hour numbers side by side without naming the discharge rate is wrong.

    That splits the search term into two intents. A buyer typing “12V 32Ah e-bike battery” is often chasing a 32 Ah traction pack for a pedal e-bike or a light two-wheeler, while a buyer whose real duty is a passenger or freight e-tricycle, a motorbike or a sprayer sits closer to the published 6-DMF-32 figure set. This guide puts the four published cells side by side, shows the 48V pack and charger arithmetic with every formula visible, and gives seven checks to run before an order reaches a supplier serving Hamburg, Rotterdam, Jebel Ali, Lagos, Chennai or Mombasa.

    Key Takeaways

    • The published 12V 32 Ah cell is the 6-DMF-32 for tricycles, motorcycles and mopeds; the published e-bike and wheelchair cell is the 6-DZF-20 at 12V 20 Ah, so match the duty to the model page before the capacity.
    • Rate basis comes before the amp-hour number: 20 Ah at C2 (2 h) and 32 Ah at C3 (3 h) are not directly comparable, and a quotation that omits the rate basis is incomplete.
    • The 6-DMF-32 publishes 12 V × 32 Ah = 384 Wh at 9.1 ± 0.2 kg, which is 384 Wh ÷ 9.1 kg = 42.2 Wh/kg; the 6-DZF-20 gives 240 Wh ÷ 6.1 kg = 39.3 Wh/kg, the 6-DMF-35 gives 420 Wh ÷ 9.8 kg = 42.9 Wh/kg and the 6-DMF-38 gives 456 Wh ÷ 10.45 kg = 43.6 Wh/kg.
    • A 48V pack of four 6-DMF-32 cells weighs 4 × 9.1 kg = 36.4 kg, stores 48 V × 32 Ah = 1,536 Wh and needs a 4 × 6.4 A = 25.6 A charger; the four-cell 6-DZF-20 pack is 24.4 kg, 960 Wh and 16.0 A.
    • Float 13.5 V, equalisation 14.1 V, cut-off 1.75 V/cell, 350–600 cycles at 50–80 % depth of discharge and a 2–5 year design life describe this class of cell — the acceptance test confirms them.

    §1 — 12V 32Ah E-Bike Battery Specifications

    The published figure set below is the whole decision: the 6-DMF-32 at 12V 32 Ah, the 6-DZF-20 at 12V 20 Ah, and the two capacity steps above it, the 6-DMF-35 and the 6-DMF-38. Model-page values first, then every derived figure with its formula.

    Specification6-DMF-326-DZF-206-DMF-356-DMF-38Source
    Nominal voltage12 V12 V12 V12 VModel page
    Rated capacity32 Ah20 Ah35 Ah38 AhModel page
    Discharge rate basisC3 (3 h)C2 (2 h)C3 (3 h)C3 (3 h)Model page
    Dimensions L × W × H267 × 78 × 170 mm180 × 76 × 170 mm267 × 78 × 170 mm224 × 106 × 175 mmModel page
    Weight9.1 ± 0.2 kg6.1 ± 0.2 kg9.8 ± 0.2 kg10.45 ± 0.2 kgModel page
    Terminalφ8.8-M5φ8.8-M5φ8.8-M5φ9.8-M5Model page
    Charging current6.4 A4.0 A7.0 A7.6 AModel page
    Float charge voltage13.5 V13.5 V13.5 V13.5 VModel page
    Equalisation voltage14.1 V14.1 V14.1 V14.1 VModel page
    Cycle life350–600 cycles (DoD 50–80 %)350–600 cycles (DoD 50–80 %)350–600 cycles (DoD 50–80 %)350–600 cycles (DoD 50–80 %)Model page
    Published applicationsElectric tricycles, motorcycles, mopeds, sanitation truck, sprayer, sightseeing vehicleElectric bicycles, e-bikes, electric wheelchairsElectric tricycles, motorcycles, mopedsElectric tricycles, motorcycles, mopedsModel page
    Energy per cell12 V × 32 Ah = 384 Wh12 × 20 = 240 Wh12 × 35 = 420 Wh12 × 38 = 456 WhArithmetic
    Specific energy per cell384 Wh ÷ 9.1 kg = 42.2 Wh/kg240 Wh ÷ 6.1 kg = 39.3 Wh/kg420 Wh ÷ 9.8 kg = 42.9 Wh/kg456 Wh ÷ 10.45 kg = 43.6 Wh/kgArithmetic
    Footprint area L × W267 × 78 = 20,826 mm²180 × 76 = 13,680 mm²267 × 78 = 20,826 mm²224 × 106 = 23,744 mm²Arithmetic
    Recharge time at published charge current32 Ah ÷ 6.4 A = 5.0 h20 Ah ÷ 4.0 A = 5.0 h35 Ah ÷ 7.0 A = 5.0 h38 Ah ÷ 7.6 A = 5.0 hArithmetic

    The 6-DMF-35 model page also publishes the operating envelope for this class of cell: a cut-off voltage of 1.75 V/cell, self-discharge of ≤ 3 % per month at 25 °C, a working temperature range of −15 °C to 50 °C, a design life of 2–5 years, and an ABS engineering plastic case at flame retardant V0 grade.

    §2 — The Pain

    The reason a 12V 32Ah e-bike battery enquiry goes wrong is almost never the cell: the search term, the published application list and the published rate basis point in three directions, and a buyer who does not separate them buys the wrong model.

    The first failure is the application mismatch. A buyer searching for a 32 Ah pack for a pedal e-bike or a light two-wheeler finds that the published e-bike duty — electric bicycles, e-bikes and electric wheelchairs — sits on a 12V 20 Ah cell, while the published 12V 32 Ah cell carries a different duty list: passenger and freight e-tricycles, electric sanitation trucks and sprayers, electric motorcycles and mopeds, and electric sightseeing vehicles. Neither cell is published for the other’s job, so the substitution must be made against the vehicle duty, not inferred from the amp-hour number.

    The second failure is the rate basis. A spreadsheet that compares 32 Ah against 20 Ah without the rate treats two different discharge conditions as one, and the gap it reports is not a gap the buyer will ever see on the road. The same error shows up in the charger decision: the 6-DMF-32 publishes a 6.4 A charging current while the 6-DZF-20 publishes 4.0 A, and a charger sized on Ah alone will over- or under-drive the pack.

    The third failure is mechanical. A 48V pack of four 6-DMF-32 cells weighs 36.4 kg, while the same pack built from four 6-DZF-20 cells weighs 24.4 kg — a difference of 4 × (9.1 kg − 6.1 kg) = 12.0 kg per pack. The footprint difference is equally direct: 267 × 78 = 20,826 mm² against 180 × 76 = 13,680 mm², so the 32 Ah cell needs 20,826 mm² − 13,680 mm² = 7,146 mm² more tray per cell. On a two-wheeler frame, those two numbers decide whether the vehicle ships or waits for a redesigned tray.

    Under all three sits a sourcing failure. Buyers importing into Lagos, Chennai, Jebel Ali or Mombasa regularly receive a quotation line reading “12V 32Ah e-bike battery, top grade” with no model code, rate basis, dimensions or charge current — a line that cannot be compared across suppliers or defended at the dock.

    §3 — The Choice

    Choosing between these four cells is a trade between four published quantities: rate basis and capacity, case footprint, weight, and the charging current that follows from it. The table below sets them against the criteria that move a purchase order.

    Decision criterion6-DMF-326-DZF-206-DMF-356-DMF-38Source
    Capacity and rate basis32 Ah at C3 (3 h)20 Ah at C2 (2 h)35 Ah at C3 (3 h)38 Ah at C3 (3 h)Model page
    Published dutyTricycles, motorcycles, mopeds, sanitation and sprayer vehicles, sightseeing vehiclesElectric bicycles, e-bikes, electric wheelchairsTricycles, motorcycles, mopedsTricycles, motorcycles, mopedsModel page
    Case footprint267 × 78 × 170 mm180 × 76 × 170 mm267 × 78 × 170 mm224 × 106 × 175 mmModel page
    Weight per cell9.1 ± 0.2 kg6.1 ± 0.2 kg9.8 ± 0.2 kg10.45 ± 0.2 kgModel page
    Terminalφ8.8-M5φ8.8-M5φ8.8-M5φ9.8-M5Model page
    Charge current6.4 A4.0 A7.0 A7.6 AModel page
    Charger for a 48V pack of four4 × 6.4 A = 25.6 A4 × 4.0 A = 16.0 A4 × 7.0 A = 28.0 A4 × 7.6 A = 30.4 AArithmetic
    Energy per cell12 V × 32 Ah = 384 Wh12 × 20 = 240 Wh12 × 35 = 420 Wh12 × 38 = 456 WhArithmetic
    Weight difference against the 6-DZF-209.1 kg − 6.1 kg = 3.0 kg per cell6.1 kg − 6.1 kg = 0 kg9.8 kg − 6.1 kg = 3.7 kg per cell10.45 kg − 6.1 kg = 4.35 kg per cellArithmetic
    Footprint difference against the 6-DZF-2020,826 mm² − 13,680 mm² = 7,146 mm²13,680 mm² − 13,680 mm² = 0 mm²20,826 mm² − 13,680 mm² = 7,146 mm²23,744 mm² − 13,680 mm² = 10,064 mm²Arithmetic

    The 48V pack table turns those cells into the build a buyer specifies. Four 12V blocks in series give a 48V pack, and the published charge current of each cell sets the charger size.

    48V pack buildCells usedPack energyPack weightCharger outputRecharge windowSource
    Four 6-DMF-324 × 12V 32Ah48 V × 32 Ah = 1,536 Wh4 × 9.1 kg = 36.4 kg4 × 6.4 A = 25.6 A32 Ah ÷ 6.4 A = 5.0 hArithmetic
    Four 6-DZF-204 × 12V 20Ah48 V × 20 Ah = 960 Wh4 × 6.1 kg = 24.4 kg4 × 4.0 A = 16.0 A20 Ah ÷ 4.0 A = 5.0 hArithmetic
    Four 6-DMF-354 × 12V 35Ah48 V × 35 Ah = 1,680 Wh4 × 9.8 kg = 39.2 kg4 × 7.0 A = 28.0 A35 Ah ÷ 7.0 A = 5.0 hArithmetic
    Four 6-DMF-384 × 12V 38Ah48 V × 38 Ah = 1,824 Wh4 × 10.45 kg = 41.8 kg4 × 7.6 A = 30.4 A38 Ah ÷ 7.6 A = 5.0 hArithmetic

    Read those two tables as four answers to four questions. If your vehicle is a passenger e-tricycle, a freight e-tricycle, a motorbike, a moped or a sanitation vehicle, the 6-DMF-32 is the published match and the only one of the four carrying the published 32 Ah figure set. The complete specification, including the 267 × 78 × 170 mm case, the 9.1 ± 0.2 kg weight and the φ8.8-M5 terminal, sits on the 6-DMF-32 model page.

    If your vehicle is a pedal e-bike or an electric wheelchair, the published match is the 6-DZF-20 at 180 × 76 × 170 mm and 6.1 ± 0.2 kg, and no published 12V 32 Ah e-bike cell exists in this range; the 6-DZF-20 model page states its 20 Ah at C2 (2 h) rating and its electric bicycles, e-bikes and electric wheelchairs duty directly.

    If the frame is built around the 6-DMF-32 tray and you want more headroom, the 6-DMF-35 is published in the identical 267 × 78 × 170 mm case at 9.8 ± 0.2 kg, so the tray stays while the charger grows from 25.6 A to 28.0 A. If the box has room for a wider case, the 6-DMF-38 moves to 224 × 106 × 175 mm at 10.45 ± 0.2 kg and carries the φ9.8-M5 terminal, so cable hardware and contact torque both change. The wider DZF and DMF traction range is listed on the DZF-DMF series index.

    §4 — The Framework

    Seven checks turn a vague enquiry into an order a factory can fill.

    1. Demand the published figure set, not the label. Ask for capacity with its rate basis, dimensions in millimetres, weight with tolerance, terminal type, float voltage, equalisation voltage, charging current, cycle life and cut-off voltage. For the 6-DMF-32 that means 32 Ah at C3 (3 h), 267 × 78 × 170 mm, 9.1 ± 0.2 kg, φ8.8-M5, 13.5 V, 14.1 V, 6.4 A and 350–600 cycles.

    2. Settle the rate basis before comparing amp-hours. The 6-DZF-20 publishes 20 Ah at C2 (2 h) and the 6-DMF-32 publishes 32 Ah at C3 (3 h), so the two amp-hour figures describe different discharge conditions. Put the rate on the purchase order next to the capacity and refuse any quotation that leaves it off.

    3. Size the charger from the published charge current, not the amp-hour number. The 6-DMF-32 publishes a 6.4 A charging current, so a 48V pack of four needs a 4 × 6.4 A = 25.6 A charger. A charger sized for the 20 Ah cell — 4 × 4.0 A = 16.0 A — is 9.6 A short, and at that reduced current the recharge window becomes 32 Ah ÷ 4.0 A = 8.0 h instead of the published 32 Ah ÷ 6.4 A = 5.0 h. Write the charger output into the order.

    4. Put the float and equalisation setpoints into the order, not into the controller defaults. The published setpoints are 13.5 V float and 14.1 V equalisation for the block, which is 2.25 V per cell and 2.35 V per cell across the six cells, with a cut-off of 1.75 V/cell. Confirm in writing that the controller can be configured to both values, along with the equalisation period and temperature compensation. A controller left on a 14.4 V default over-charges every cell in the pack.

    5. Measure the case footprint and the terminal before the tray is cut. The 6-DMF-32 publishes 267 × 78 × 170 mm with a total height of 170 mm and a φ8.8-M5 terminal, so the cell occupies 20,826 mm² of tray area and 7,146 mm² more than the 6-DZF-20. Lead length, terminal type and hold-down position belong on the frame drawing, and the 6-DMF-38 at φ9.8-M5 needs different cable hardware.

    6. Check the mounting, the case material and the vibration duty on a two-wheeler. The case material published for this class of cell is ABS engineering plastic at flame retardant V0 grade, and the working temperature range is −15 °C to 50 °C. A tricycle or motorbike frame sees continuous vibration, so confirm the hold-down arrangement and that the 36.4 kg pack is carried by the chassis rather than by the tray skin.

    7. Agree the acceptance test on arrival. For shipments landing at Rotterdam, Hamburg, Port Said, Jebel Ali, Lagos, Chennai, Santos, Valencia, Durban or Mombasa, specify in the contract what happens on arrival: a sample capacity check at the published rate, a float voltage check across the block, a visual and torque check on the terminals, and the rule that a failing sample goes to re-inspection at an agreed laboratory rather than to an argument at the dock.

    §5 — The Trust

    The 6-DMF-32, the 6-DZF-20, the 6-DMF-35 and the 6-DMF-38 are built on a VRLA line inside a manufacturer operating 8 production bases with an annual capacity of 70 million kVAh, under ISO 9001 and ISO 14001 certification, with CE, UL and IEC conformity for the markets each cell ships into. The 12V VRLA products in this class are specified against GB/T 32620.1-2016 and GB/T 32620.2-2016 and IEC 60896-21/22, while IEC 60896-11 covers tubular-plate cells, a construction this 12V block class does not use; GB/T 32620.1 also appears on the 6-EVF-150 model page. No certificate number is quoted here because none should be invented, and the certificates themselves are requested with their scope, address and validity dates.

    Two points deserve emphasis for a buyer asked to pay for assurance. First, a certification covers a system, a scope and a date, not a particular carton: ISO 9001 certifies that the quality management system is documented and that corrective action happens, but not that one cell holds 32 Ah at C3. That is what the published capacity, the type test and the acceptance test are for.

    Second, the difference between a published specification and a marketing line is the entire value of this exercise. A supplier who quotes “12V 32Ah e-bike battery, top grade” tells you nothing about rate basis, case, weight or charge current. A supplier who quotes “6-DMF-32, 32 Ah at C3 (3 h), 267 × 78 × 170 mm, 9.1 ± 0.2 kg, φ8.8-M5, float 13.5 V, equalisation 14.1 V, 6.4 A charging current, 350–600 cycles at 50–80 % DoD” tells you everything needed to engineer the pack, write the charger setting and defend the claim at the goods-in dock. For importers buying through a distributor rather than direct, ask for the manufacturer’s model page URL and the batch reference; both can be checked before the container is opened.

    §6 — FAQ

    Q1. Is the 6-DMF-32 suitable for a pedal e-bike? The published application list for the 6-DMF-32 covers passenger and freight electric tricycles, electric sanitation trucks and sprayers, electric motorcycles and mopeds, and electric sightseeing vehicles. It does not include pedal e-bikes. The published e-bike and wheelchair duty in this class sits on the 6-DZF-20 at 12V 20 Ah, so if your vehicle is a pedal e-bike or an electric wheelchair, the specification to work from is the 20 Ah cell and its rate basis, not the 32 Ah cell.

    Q2. What does 32 Ah actually mean on a 12V 32Ah battery? It means 32 amp-hours delivered at the C3 discharge rate — the three-hour rate — down to a cut-off of 1.75 V/cell, at 25 °C. It does not mean 32 Ah for the whole day: on a longer discharge the usable figure is lower, and on a shorter one it is higher, which is why a quotation giving capacity without the rate is incomplete.

    Q3. Can I compare the 20 Ah 6-DZF-20 directly with the 32 Ah 6-DMF-32? Not on capacity alone. The 20 Ah figure is a C2 (2 h) rating and the 32 Ah figure is a C3 (3 h) rating, so they are two different discharge conditions. Compare them on the published envelope instead: case footprint, weight, terminal, charging current and application list. Where you do compare energy, use 12 V × 20 Ah = 240 Wh and 12 V × 32 Ah = 384 Wh, and say so on the order.

    Q4. What charger do I need for a 48V pack of four 12V 32Ah batteries? A 48V charger with a 25.6 A output, because the published charging current is 6.4 A per cell and 4 × 6.4 A = 25.6 A. Set the float at 13.5 V and equalisation at 14.1 V for the 48V string, which is 2.25 V and 2.35 V per cell, with a cut-off of 1.75 V/cell. At the published current the recharge window is 32 Ah ÷ 6.4 A = 5.0 h; at a 16.0 A charger it stretches to 32 Ah ÷ 4.0 A = 8.0 h.

    Q5. Can I fit a 6-DMF-35 where a 6-DMF-32 already sits? Usually yes on the case footprint, because both are published at 267 × 78 × 170 mm with a total height of 170 mm. The differences are weight, at 9.8 ± 0.2 kg against 9.1 ± 0.2 kg, and the charger, at 4 × 7.0 A = 28.0 A against 25.6 A, with 48 V × 35 Ah = 1,680 Wh against 1,536 Wh per pack. The terminal stays at φ8.8-M5, so the cable hardware is unchanged.

    Q6. What is the difference between the 6-DMF-32 and the 6-DMF-38? Capacity, case and terminal. The 6-DMF-38 publishes 38 Ah at C3, 224 × 106 × 175 mm, 10.45 ± 0.2 kg and a φ9.8-M5 terminal, against 32 Ah at C3, 267 × 78 × 170 mm, 9.1 ± 0.2 kg and φ8.8-M5 for the 6-DMF-32. That means a different tray shape, 1.35 kg more mass per cell — 5.4 kg more on a 48V pack of four — a different cable terminal, and a charger of 4 × 7.6 A = 30.4 A instead of 25.6 A.

    Q7. How long will a 12V 32Ah e-bike battery last in service? The published cycle life is 350–600 cycles at 50–80 % depth of discharge, and the published design life is 2–5 years. The cycle figure assumes that depth-of-discharge window, so if your duty runs the pack deeper, ask for the rating at your actual depth before committing to a volume. The calendar figure also assumes the published temperature envelope of −15 °C to 50 °C, with self-discharge at ≤ 3 % per month at 25 °C.

    Q8. What should be on the purchase order for a 12V 32Ah battery? The model code, the rate basis, the case dimensions, the weight tolerance, the terminal type, the float and equalisation voltages, the charging current, the cycle rating and depth of discharge, the batch reference, the test certificate and the arrival acceptance procedure. If the order ships to Rotterdam, Santos, Jebel Ali or Mombasa, name the agreed laboratory for a failing-sample inspection so the dispute path is written before the container sails.

    Expert Summary

    A 12V 32Ah e-bike battery has to be separated into two distinct products before anything else is decided. CHISEN publishes its e-bike, electric bicycle and electric wheelchair duty on the 6-DZF-20 at 12V 20 Ah, rated at 20 Ah on the C2 (2 h) rate, 180 × 76 × 170 mm, 6.1 ± 0.2 kg, φ8.8-M5, 4.0 A charging current. The published 12V 32 Ah cell is the 6-DMF-32, rated at 32 Ah on the C3 (3 h) rate, 267 × 78 × 170 mm, 9.1 ± 0.2 kg, φ8.8-M5, 6.4 A charging current, with its published applications in passenger and freight electric tricycles, electric sanitation trucks and sprayers, electric motorcycles and mopeds, and electric sightseeing vehicles. Neither cell is published for the other’s duty.

    The arithmetic is what a buyer can act on. Four 6-DMF-32 cells give a 48 V × 32 Ah = 1,536 Wh pack at 4 × 9.1 kg = 36.4 kg, needing a 4 × 6.4 A = 25.6 A charger and a 32 Ah ÷ 6.4 A = 5.0 h recharge window; four 6-DZF-20 cells give 48 V × 20 Ah = 960 Wh at 4 × 6.1 kg = 24.4 kg with a 4 × 4.0 A = 16.0 A charger and the same 5.0 h window; the 6-DMF-35 and 6-DMF-38 take those packs to 1,680 Wh and 1,824 Wh at 39.2 kg and 41.8 kg. All four publish float 13.5 V, equalisation 14.1 V, a 1.75 V/cell cut-off and 350–600 cycles at 50–80 % DoD.

    For importers serving Rotterdam, Hamburg, Lagos, Chennai, Jebel Ali, Santos, Port Said, Valencia, Durban and Mombasa, the sequence that works is simple: fix the published figure set first, then let suppliers compete on it. The manufacturer behind these cells operates 8 production bases at 70 million kVAh annual capacity under ISO 9001 and ISO 14001 certification, with CE, UL and IEC conformity for the destination markets, and VRLA cells specified against GB/T 32620.1-2016, GB/T 32620.2-2016 and IEC 60896-21/22. The §1 table runs that process, and the seven checks in §4 prevent a mis-specified order reaching a factory.

    Contact CHISEN

    Send the target vehicle or application, the published capacity you need with its rate basis, the case dimensions your tray allows, the terminal type and the pack quantity, and you will receive a quotation against the published specification, the datasheet and the current lead time.

    • Email: jack@chisen.cn or sales@chisen.cn
    • WhatsApp: +86 131 6622 6999
    • 6-DMF-32 model page: https://www.chisen.cn/en/6-DMF-32/12V32Ah.html
    • 6-DZF-20 model page: https://www.chisen.cn/en/6-DZF-20/12V20Ah.html
    • 6-DMF-35 model page: https://www.chisen.cn/en/6-DMF-35/12V35Ah.html
    • 6-DMF-38 model page: https://www.chisen.cn/en/6-DMF-38/12V38Ah.html
    • DZF-DMF traction series index: https://www.chisen.cn/en/Leadacidbattery/DZF-DMF.html

    Related reading on the CHISEN knowledge centre: 12V VRLA selection guidance, deep-cycle charge setpoints, and pack-sizing method for tricycle, motorcycle and mobility applications.

    CHISEN Battery — lead-acid cells and systems for telecom, solar, UPS, AGV and traction applications. 8 production bases, 70 million kVAh annual capacity, ISO 9001 and ISO 14001 certified.