Answer First
The OPzV2-2000 2V2000Ah is a sealed tubular-plate gel stationary cell rated 2000 Ah at C10 to 1.80 V/cell at 20 °C, published with a designed floating life of 20+ years at 20 °C, an internal resistance of approx. 0.37 mΩ fully charged at 25 °C, a maximum charge current of 400 A and a short circuit current of 8300 A — the cell that a utility-scale or large-capacity stationary installation is usually built from when the specification calls for a very large block of energy in a 48 V string without pushing the cell count past what the cabinets, the floor and the string bus can carry.
OPzV2-2000 refers to a gel-electrolyte stationary cell in the OPzV series: the trailing 2 denotes the 2 V nominal cell voltage, 2000 is the nominal capacity in ampere-hours, and the OPzV prefix identifies the tubular-plate construction with a gel electrolyte rather than a flooded one. Every rating a technical evaluator needs is published against a stated condition — capacity at C10 to 1.80 V/cell at 20 °C, internal resistance fully charged at 25 °C, floating life referenced to 20 °C — and that is what allows a string of this size to be engineered and priced before any commercial discussion begins.
Demand-side commentary from the IEA, BloombergNEF and Benchmark Minerals is useful for framing the direction of grid-scale and large stationary storage spending, and it also deserves a caution: none of those institutions publishes a cell-level specification, so none of them can confirm a capacity, a float life or a terminal torque. Procurement is settled at the datasheet level. On the published data the OPzV2-2000 resolves the three questions that dominate a project of this size: whether the energy can be delivered inside the required window without a voltage derate, whether the charger programme can restore the string after a deep discharge, and whether a 3.5-tonne string can be installed, transported and maintained within the logistics of the destination port.
Key Takeaways
- The rating is condition-bound. 2000 Ah is quoted at C10 to 1.80 V/cell at 20 °C, which is a 200 A discharge for ten hours. A capacity figure quoted without its rate, its end voltage and its temperature cannot be compared against anything else, because every supplier selects different conditions and the number then means different things.
- Float life is a 20 °C number. The datasheet states 20+ years of floating life at 20 °C, and the same 20 °C reference carries the self-discharge rate of approx. 2 % per month. A supplier quoting a lifetime for a warmer ambient is making a different claim, and that difference belongs in the commercial comparison rather than in a footnote.
- A 24-cell string is fully calculable. 24 × 2 V × 2000 Ah = 96 kWh nominal, with 8.88 mΩ of string internal resistance, a 9,600 A string charge ceiling, and 3,480 kg of cells. Every one of those figures follows directly from the cell data and can be checked before an order is placed.
- The size gain comes from fewer connections, not better chemistry. At 4000 Wh and 145 kg the cell delivers 27.6 Wh/kg, against 27.3 Wh/kg for the 1000 Ah cell and 29.4 Wh/kg for the 1500 Ah cell. Energy density is effectively unchanged; what changes is that a string needs fewer cells, fewer interconnects and fewer cabinets.
- Verification is inexpensive when the data is published. Setpoints, the temperature compensation coefficient, drawing dimensions, terminal torque, internal resistance, the short circuit current, the certifications and the standards list are all stated, so a technical approval can be completed against the datasheet and the supply question settled afterwards.
§1 — OPzV2-2000 2V2000Ah Quick Specifications Table
| Parameter | Published value | Source |
|---|---|---|
| Model | OPzV2-2000, tubular-plate gel stationary cell, 2 V 2000 Ah | Model page |
| Nominal voltage | 2 V | Datasheet |
| Nominal capacity | 2000 Ah at C10 to 1.80 V/cell at 20 °C | Datasheet |
| C10 discharge current | 200 A (2000 Ah ÷ 10 h) | Arithmetic |
| Designed floating life | 20+ years @ 20 °C | Datasheet |
| Printed dimensions (L × W × H) | 399 × 212 × 807 mm | Datasheet |
| Drawing container height | 772 mm | Datasheet |
| Drawing total height | 807 mm | Datasheet |
| Drawing width / length | 212 mm / 399 mm | Datasheet |
| Terminal spacing | 108 mm across width, 110 mm and 110 mm along length | Datasheet |
| Terminal | 20 mm OD, M8 thread, 7 mm depth, female copper insert M8 | Datasheet |
| Terminal tightening torque | 10–12 N·m | Datasheet |
| Approximate weight | 145 kg (320 lbs) | Datasheet |
| Internal resistance | Approx. 0.37 mΩ, fully charged at 25 °C | Datasheet |
| Maximum charge current | 400 A | Datasheet |
| Charge characteristic | Constant charge at 0.15 CA to 2.40 V at 20 °C | Datasheet |
| Maximum discharge current (5S) | 3000 A | Datasheet |
| Short circuit current | 8300 A | Datasheet |
| Self discharge | Approx. 2 % per month at 20 °C | Datasheet |
| Float charge voltage | 2.23 V @ 25 °C | Datasheet |
| Equalise charge voltage | 2.35 V @ 25 °C | Datasheet |
| Temperature compensation | −3 mV/°C/cell | Datasheet |
| Ambient, discharge | −40 °C to +65 °C | Datasheet |
| Ambient, charge | −30 °C to +65 °C | Datasheet |
| Ambient, storage | −25 °C to +45 °C | Datasheet |
| Container material | ABS, UL94-V0 optional | Datasheet |
| Applicable standards | IEC 60896-21/22, DIN 40472, IEC 61427, YD/T 1360, Eurobat long-life guide, BS 6290 part 4, UL 1989 | Datasheet |
| Certifications | ISO 9001 (EIC), ISO 14001 (UKAS/UCC), GB/T 28001 / OHSAS 18001:2007 (UCC), CE, RU (UL Recognized Component) | Datasheet |
The final voltage recommended for a given discharge rate is published as well: below 0.05 C the cell supports at least 1.90 V per cell, between 0.05 C and 0.08 C at least 1.85 V, between 0.08 C and 0.2 C at least 1.80 V, between 0.2 C and 0.6 C at least 1.75 V, between 0.6 C and 1.0 C at least 1.70 V, and from 1 C to 2 C at least 1.60 V. Those figures, not a nominal 2 V, are what a battery management system should be configured against.
§2 — The Pain
An installation at this scale fails on integration long before it fails on chemistry. The recurring problems are a specification that cannot be compared, a string whose consequences nobody has computed, and logistics that were never sized for the cell.
Specification ambiguity is the first. A 2000 Ah cell quoted without a rate, an end voltage and a temperature is not a 2000 Ah cell, it is a marketing label. At this capacity the ambiguity is expensive, because a 2000 Ah cell that delivers only its C3 rating is a fundamentally different procurement from one that delivers its C10 rating, and the difference shows up as a cabinet count, a rectifier size or an autonomy shortfall on day one of commissioning. The same applies to float life quoted at a warmer ambient than the site will see, and to internal resistance quoted without a temperature.
String-level arithmetic is the second. A 24-cell string at this size is 96 kWh and 3,480 kg of cells. The mass alone determines floor loading, aisle width, the lifting plan, the handling equipment specification and the freight booking, because a cell of this weight is not palletised the way a 25 kg cell is. The 8.88 mΩ string resistance and the 9,600 A string charge ceiling determine the busbar, the DC breaker and the rectifier specification. When these are computed after the order is placed, they are computed by a party who does not carry the consequence.
Logistics is the third, and it is the failure mode that surprises buyers most often. Cells of 145 kg have a very different shipping profile from cells of 84 kg: the pallet configuration, the container loading plan, the number of containers for a given megawatt-hour, the crane requirement at the discharge port and the labour to unload all change with the cell weight and the pallet height. A tender that prices the cells and forgets the handling profile produces an installation that cannot be received.
§3 — The Choice
The OPzV2-2000 sits at the top of the published OPzV2 range, and the comparison is a question of connections, cabinets and floor area rather than of any single headline figure.
| OPzV2-1000 | OPzV2-1200 | OPzV2-1500 | OPzV2-2000 | |
|---|---|---|---|---|
| Capacity @ C10 to 1.80 V @ 20 °C | 1000 Ah | 1200 Ah | 1500 Ah | 2000 Ah |
| Printed dimensions | L233 × W210 × H681 mm | L275 × W210 × H681 mm | L275 × W210 × H831 mm | L399 × W212 × H807 mm |
| Approximate weight | 73.2 kg (161.4 lbs) | 84 kg (185 lbs) | 102 kg (225 lbs) | 145 kg (320 lbs) |
| Max charge current | 200 A | 240 A | 300 A | 400 A |
| Internal resistance | approx. 0.5 mΩ @ 25 °C | approx. 0.46 mΩ @ 25 °C | approx. 0.45 mΩ @ 25 °C | approx. 0.37 mΩ @ 25 °C |
| Short circuit current | 5400 A | 6400 A | 6200 A | 8300 A |
| Float / equalise | 2.23 V / 2.35 V @ 25 °C | 2.23 V / 2.35 V @ 25 °C | 2.23 V / 2.35 V @ 25 °C | 2.23 V / 2.35 V @ 25 °C |
| Designed floating life | 20+ yr @ 20 °C | 20+ yr @ 20 °C | 20+ yr @ 20 °C | 20+ yr @ 20 °C |
| String arithmetic, 24 cells in series | OPzV2-1000 | OPzV2-1200 | OPzV2-1500 | OPzV2-2000 |
| — | — | — | — | — |
| Nominal energy (24 × 2 V × Ah) | 48.0 kWh | 57.6 kWh | 72.0 kWh | 96.0 kWh |
| String mass (24 × cell weight) | 1,756.8 kg | 2,016 kg | 2,448 kg | 3,480 kg |
| String internal resistance (24 × IR) | 12.0 mΩ | 11.04 mΩ | 10.8 mΩ | 8.88 mΩ |
| String max charge current (24 × I) | 4,800 A | 5,760 A | 7,200 A | 9,600 A |
| Mass energy density (Wh ÷ kg) | 2,000 ÷ 73.2 = 27.3 Wh/kg | 2,400 ÷ 84 = 28.6 Wh/kg | 3,000 ÷ 102 = 29.4 Wh/kg | 4,000 ÷ 145 = 27.6 Wh/kg |
The OPzV2-2000 string figures are derived from the cell data, and the working is shown so that each figure can be checked:
| Derivation for the OPzV2-2000, 24 cells in series | Working | Source |
|---|---|---|
| Nominal energy | 24 × 2 V × 2000 Ah = 96 kWh | Arithmetic |
| String mass with cells | 24 × 145 kg = 3,480 kg | Arithmetic |
| String internal resistance | 24 × 0.37 mΩ = 8.88 mΩ | Arithmetic |
| String max charge current | 24 × 400 A = 9,600 A | Arithmetic |
| Mass energy density | 4,000 Wh ÷ 145 kg = 27.6 Wh/kg | Arithmetic |
| C10 discharge current | 2,000 Ah ÷ 10 h = 200 A | Arithmetic |
The OPzV2-2000 is more reliable than the OPzV2-1500 in a string sized around a fixed cell count, because it returns 2000 Ah against 1500 Ah at the same C10 test while lowering the internal resistance from approx. 0.45 mΩ to approx. 0.37 mΩ, which reduces the voltage drop and the heat generated during recharge at the same load. It is a better fit than two OPzV2-1000 cells in parallel, because one 2000 Ah cell at approx. 0.37 mΩ halves the connection count per unit of energy against two 1000 Ah cells at approx. 0.5 mΩ, and every parallel connection is a termination that has to be made, torqued, inspected and eventually maintained. The OPzV2-2000 is better suited to large stationary float duty than a comparable LFP product, because its 2.23 V float and 2.35 V equalise programme matches the installed charger hardware and the existing 48 V bus without altering the charge regime or the string architecture. The OPzV2-2000 is more reliable in service than an unspecified 2 V 2000 Ah cell, because every rating it publishes is tied to a stated condition — C10 to 1.80 V/cell at 20 °C, internal resistance measured fully charged at 25 °C, float life referenced to 20 °C — which removes the guesswork that causes premature string replacement on projects this large.
§4 — The Framework
Seven numbers decide whether the OPzV2-2000 belongs in a given installation. Everything else is negotiation.
- Capacity at a stated rate and temperature. 2000 Ah at C10 to 1.80 V/cell at 20 °C, which is a 200 A discharge for ten hours, with the published final-voltage curve from 1.90 V down to 1.60 V for duty cycles away from the ten-hour rate.
- Internal resistance. Approx. 0.37 mΩ per cell fully charged at 25 °C, which becomes 8.88 mΩ across a 24-cell string, and that figure is the input to cable, busbar and interconnection sizing rather than a laboratory detail.
- Float and equalise setpoints with compensation. 2.23 V float and 2.35 V equalise at 25 °C, with −3 mV/°C/cell temperature compensation so the charger programme is written once and then left alone through seasonal swings in the enclosure.
- Charge acceptance. A maximum charge current of 400 A per cell, a constant-charge characteristic of 0.15 CA to 2.40 V at 20 °C, and a 9,600 A ceiling across a 24-cell string — the values to compare against the rectifier output of the installation.
- Discharge and fault duty. A maximum discharge current of 3000 A at the 5S rate and an 8300 A short circuit current, which set the DC bus breaker rating, the fuse coordination and the protection study for the battery enclosure.
- Mechanical, logistics and structural envelope. 399 × 212 × 807 mm printed dimensions with a 772 mm container height and 108 mm / 110 mm / 110 mm terminal spacing, 145 kg per cell, and a 24-cell string total of 3,480 kg — which determines floor loading, aisle width, the lifting plan, the pallet configuration and the container loading plan.
- Environmental window and self-discharge. Discharge from −40 °C to +65 °C, charge from −30 °C to +65 °C, storage from −25 °C to +45 °C, and self discharge of approx. 2 % per month at 20 °C, which together determine standby behaviour, seasonal outage handling and the storage regime for a site that is not permanently attended.
§5 — The Trust
A market with dense, well-written datasheets rewards buyers who verify rather than accept. The verification traps are well known to anyone who has bought stationary cells at this scale across several suppliers.
- Capacity without a condition. Ask for the rate, the end voltage and the temperature. If the reply is only “2000 Ah”, the cell has not been specified.
- Lifetime without an ambient. Require the stated temperature. 20+ years at 20 °C is the published claim; a figure quoted for another ambient is a different claim and a different risk.
- Dimensions without the drawing. Printed dimensions, a 772 mm container height and an 807 mm total height are three different measurements, and the 212 × 399 mm top view with the 108 mm and 110 mm terminal spacing is what actually fixes the rack.
- Internal resistance quoted without conditions. Ask whether it is measured fully charged and at what temperature, because approx. 0.37 mΩ at 25 °C is a specific number and not a generic one.
- Setpoints quoted as a range. A float programme should arrive as a value, a compensation coefficient and a measurement point — 2.23 V at 25 °C with −3 mV/°C/cell — not as a band.
- Standards listed without documents. Names printed on a brochure are not certificates. Request the accredited certificate numbers, the issuing bodies and the expiry dates, plus the UL file reference for the Recognized Component listing.
- Certification scope overstated. A RU (UL Recognized Component) mark applies to the component, not to a finished storage system or installation; final listing and field evaluation remain the integrator’s responsibility under the local code.
- Freight and port assumptions left open. Confirm the port of loading (Shanghai, Ningbo or Shenzhen) and the nominated port of discharge (Rotterdam, Antwerp, Jebel Ali, Singapore, Durban, Santos or Long Beach), who carries the freight cost, the container loading plan for 145 kg cells, and whether the shipment is a full container of cells or a break-bulk consignment.
On documentation, the OPzV2-2000 is built to IEC 60896-21/22, DIN 40472, IEC 61427, YD/T 1360, the Eurobat long-life guide, BS 6290 part 4 and UL 1989, and the manufacturing operation holds ISO 9001, ISO 14001 and GB/T 28001 / OHSAS 18001:2007. The practical step is to ask for the documents behind those marks — accredited certificate numbers and validity dates, the UL file reference and the IEC 60896-21 test report — because that is the only part of a quality claim a buyer can audit. For a European project the DIN 40472 and IEC 60896-21 conformity is what satisfies the local installer; for a North American project the UL file reference is what the authority having jurisdiction will ask for; for a Chinese or South-East Asian utility the YD/T 1360 route is the one that matches local procurement practice. Production base in Hangzhou with loading typically through the ports of Shanghai and Ningbo means a buyer can also request the factory address, the loading port and the container marking in writing before the vessel is booked, and can compare those documents across more than one source rather than relying on a single reply.
§6 — FAQ
Q1. What does the model code OPzV2-2000 mean, and what type of cell is it? It identifies a sealed tubular-plate gel stationary lead-acid cell. The OPzV series follows the tubular-plate construction defined in DIN 40472, the trailing 2 is the 2 V nominal cell voltage, and 2000 is the nominal capacity in ampere-hours. The electrolyte is gelled in a thixotropic silica suspension rather than held as free liquid, which is what makes the cell maintenance-free, spill-proof and suitable for an enclosure without ventilation plenum design.
Q2. How is the 2000 Ah rated, and what discharge rate should a string be sized against? The 2000 Ah figure is published at C10 to 1.80 V/cell at 20 °C, which is a 200 A discharge for ten hours. Sizing must be done against the real discharge profile using the closest published rate and against the end voltage the installed rectifier can support at the end of a deep discharge, and the datasheet gives the final voltage recommended for each discharge band from below 0.05 C through to 2 C.
Q3. Does the 20+ year design life apply at my site’s ambient temperature? The published figure is 20+ years of floating life at 20 °C, and the same temperature is stated for the self-discharge rate of approx. 2 % per month. Float life falls as ambient temperature rises, so an enclosure that regularly exceeds 20 °C needs a derating calculation. Ask the supplier to state the assumed ambient, the float voltage programme and the expected number of discharges, and to confirm the basis on which the 20+ year claim is made.
Q4. What float and equalise voltages should the charger be programmed to? The datasheet specifies 2.23 V float and 2.35 V equalise at 25 °C, with temperature compensation of −3 mV/°C/cell. That compensation figure is what keeps the cell on its float curve through seasonal swings, and it is the parameter most often left out of a quotation. A gel cell with no compensation fitted will overcharge in summer and undercharge in winter, which shows up as water loss in the cell and a shortened service life.
Q5. Why choose one 2000 Ah cell instead of two 1000 Ah cells in parallel? One 2000 Ah cell at approx. 0.37 mΩ replaces two 1000 Ah cells at approx. 0.5 mΩ for the same energy, which halves the number of parallel terminations and therefore the number of joints to make, torque, inspect and maintain. Mass energy density is effectively the same — 27.6 Wh/kg against 27.3 Wh/kg — so the gain is in connection count, handling and footprint rather than in chemistry.
Q6. What are the physical dimensions, weight and terminal torque? Printed dimensions are 399 × 212 × 807 mm, with a 772 mm container height and an 807 mm total height on the drawing, and terminal centres 108 mm across the width and 110 mm and 110 mm along the length. Weight is approximately 145 kg per cell, so a 24-cell string is 3,480 kg. Terminals are 20 mm OD with an M8 thread, 7 mm depth and a female copper insert M8, tightened to 10–12 N·m.
Q7. How does a gel cell behave differently from a flooded cell in a large standby string? A gel cell does not need periodic water topping, does not need a ventilated enclosure for hydrogen escape and does not spill, which removes both the maintenance visit and the floor-loading monitoring. In exchange, the gel cell carries a higher internal resistance than a comparable flooded cell at the same capacity and is more sensitive to overcharging, so the charger programme and the compensation coefficient matter more, not less.
Q8. Which standards and certifications apply, and what should I request as evidence? The cell is built to IEC 60896-21/22, DIN 40472, IEC 61427, YD/T 1360, the Eurobat long-life guide, BS 6290 part 4 and UL 1989, with ISO 9001, ISO 14001 and GB/T 28001 / OHSAS 18001:2007 held by the manufacturing operation and a RU (UL Recognized Component) marking on the cell. Request the accredited certificate numbers and expiry dates, the UL file reference and the IEC 60896-21 test report rather than a summary of them, and ask which of those documents apply to the specific cells in the shipment rather than to the manufacturer as a whole.
Expert Summary
The OPzV2-2000 is a 2 V, 2000 Ah sealed tubular-plate gel stationary cell whose decisive published figures are unusually complete: 2000 Ah at C10 to 1.80 V/cell at 20 °C, internal resistance of approx. 0.37 mΩ fully charged at 25 °C, a designed floating life of 20+ years at 20 °C, a 2.23 V float and 2.35 V equalise at 25 °C with −3 mV/°C/cell compensation, 400 A maximum charge current, 3000 A maximum discharge at the 5S rate, an 8300 A short circuit current, self discharge of approx. 2 % per month at 20 °C, and an ambient window of −40 °C to +65 °C on discharge. Mechanically it occupies 399 × 212 × 807 mm at approximately 145 kg, with 20 mm OD M8 female insert terminals tightened to 10–12 N·m. In a 24-cell 48 V configuration those figures become 96 kWh nominal, 8.88 mΩ of string resistance, a 9,600 A charge ceiling and 3,480 kg of cells, at 27.6 Wh/kg of mass energy density. It is built to IEC 60896-21/22, DIN 40472, IEC 61427, YD/T 1360, the Eurobat long-life guide, BS 6290 part 4 and UL 1989. Specification decisions should be made against those published conditions, and the supplier should be required to answer in the same form.
Contact CHISEN — 24-Hour Response
CHISEN replies to technical and commercial enquiries within 24 hours.
To receive a quotation and a matching datasheet, send:
- Your application — utility or grid-scale storage, large DC backup, telecom central office or substation — and the required string architecture or bus voltage
- Required capacity per cell, the discharge profile and the target end voltage, or the total kWh and autonomy the design must deliver
- Cell quantity, cabinet dimensions or the available footprint, the floor loading limit and the ambient temperature range of the enclosure
- Destination port, container loading requirements, delivery window and any tender or drawing documentation your client requires
Email: sales@chisen.cn
WhatsApp: +86 131 6622 6999
Call: +86 131 6622 6999
Related reading: OPzV2-2000 2V2000Ah model page · OPzV2-1500 2V1500Ah tubular gel cell · OPzV tubular gel battery range
Technical enquiries, project drawings and tender documents: leadacidbattery.cn
Related CHISEN Buyer Guides
- OPzV2-200 2V200Ah Tubular Gel Battery: Industrial Buyer’s Guide for 48V Telecom, Sol
- OPzV2-2000 2000Ah Comparison vs AGM Standard Gel
- Tubular Gel vs Tubular Flooded (OPzV vs OPzS): Which Is Right for Your Stationary Energy S
- OPzV2-1000 2V1000Ah Tubular Gel Battery for Telecom UPS Solar Storage — CHISEN Industrial
- OPzV2-150 2V150Ah Tubular Gel Battery — Telecom / UPS / Solar Backup Buyer’s Guide 2