Answer First
The OPzS2-1500 2V1500Ah is a 2 V, 1500 amp-hour flooded tubular vented lead-acid cell rated at the ten-hour rate — 150 A for 10 hours to 1.80 V per cell at 20 °C — and it is the right cell when a utility-scale solar or wind plant, a large telecom power room or a rail traction substation needs a 48 V or 96 V DC bus holding roughly 72 kWh or 144 kWh nominal per string, and when somebody on site will still top up water and read a hydrometer once a quarter.
It is not a sealed cabinet. It is a component of a room: hydrogen venting, flame-retardant acid-proof vent plugs, quarterly water top-up, periodic equalisation and a specific-gravity check are part of the product, not optional extras.
Five facts decide most projects:
- 275 × 210 × 850 mm, 850 mm over terminals, 71.0 kg without electrolyte and 98 kg with it. A 24-cell 48 V string is 2,352 kg of battery on the floor before racks, busbar and the room.
- Maximum charging current 300 A, 0.20 C10. That single limit caps what a solar array can push into the string at about 14.5 kW at 48 V nominal.
- Float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation; equalise 2.35 V per cell at 25 °C. Charge controllers for renewable duty need the separate setpoints listed in §4, not the generic defaults.
- Designed floating life 20+ years at 20 °C. The float life holds at 20 °C and falls away sharply above it — this is the most expensive lesson in this chemistry.
- Internal resistance ≈0.40 mΩ fully charged at 20 °C; short-circuit current 5,400 A. A 24-cell string presents about 9.6 mΩ in series and delivers roughly 5,000 A on a hard short.
The OPzS2-1500 2V1500Ah sits between the OPzS2-1000 and the OPzS2-2000 in the same product range. That position is deliberate: it is the capacity step that matches the array sizes now being tendered for 48 V utility DC buses, and it absorbs 300 A per cell while still being handled by two people.
Key Takeaways
- 1,500 Ah at C10, 150 A for 10 hours to 1.80 V per cell at 20 °C. The rating is a ten-hour rate, so size your string on C10, not on the higher one-hour or three-hour figures a distributor quotes.
- 71.0 kg dry, 98 kg with electrolyte, 27 kg of acid. Handling is a two-person job with a trolley, and the floor loading must be checked before the plinth is poured.
- Maximum charging current 300 A per cell (0.20 C10). A 48 V string accepts 7,200 A, which is about 14.5 kW at nominal bus voltage.
- Float 2.23 V, equalise 2.35 V per cell, −3 mV/°C/cell compensation, 20+ years float life at 20 °C. Solar and wind duty needs a different setpoint table entirely — see §4.
- Internal resistance ≈0.40 mΩ, short-circuit current 5,400 A, maximum discharge 2,500 A for 5 s. Protection coordination and cable sizing follow directly from these numbers.
§1 — OPzS2-1500 2V1500Ah Published Specifications
Every figure below comes from the CHISEN OPzS2-1500 factory datasheet. Where a value is a calculation rather than a printed figure, the source column says so. Values the datasheet does not print are written as “not published” rather than estimated, because an estimate on a procurement sheet becomes an engineering assumption nobody re-checks.
| Parameter | Published value | Source |
|---|---|---|
| Model | OPzS2-1500 | Datasheet |
| Chemistry and construction | Flooded tubular vented lead-acid: die-cast Pb-Sb tubular positive plate, pasted lead-calcium negative plate, low-resistance PVC composite separator, transparent SAN container, high-strength ABS cover | Datasheet |
| Nominal voltage | 2 V per cell | Datasheet |
| Rated capacity (C10) | 1,500 Ah, 150 A for 10 h to 1.80 V per cell at 20 °C | Datasheet |
| Cell dimensions | 275 × 210 × 850 mm | Datasheet |
| Container (jar) height | 795 mm | Datasheet |
| Total height over terminals | 850 mm | Datasheet |
| Top view | 275 × 210 mm | Datasheet |
| Terminal centre spacing | 108 mm | Datasheet |
| Weight without electrolyte | 71.0 kg (157 lbs) | Datasheet |
| Weight with electrolyte | 98 kg (216 lbs) | Datasheet |
| Electrolyte (acid) weight | 27 kg at 1.240 g/cm³ | Datasheet |
| Internal resistance | ≈0.40 mΩ fully charged at 20 °C | Datasheet |
| Short-circuit current | 5,400 A | Datasheet |
| Maximum discharge current | 2,500 A for 5 s | Datasheet |
| Maximum charging current | 300 A | Datasheet |
| Charge characteristic | Constant-current then constant-voltage, tapering to 0.15 CA below the float voltage | Datasheet |
| Float charge voltage | 2.23 V per cell at 25 °C, −3 mV/°C/cell temperature compensation | Datasheet |
| Equalise charge voltage | 2.35 V per cell at 25 °C, 20–25 °C range | Datasheet |
| Self-discharge | ≈4 % per month at 20 °C | Datasheet |
| Ambient temperature, discharge | −25 °C to 65 °C | Datasheet |
| Ambient temperature, charge | −20 °C to 65 °C | Datasheet |
| Ambient temperature, storage | −15 °C to 40 °C | Datasheet |
| Designed floating life | 20+ years at 20 °C | Datasheet |
| Terminal type | Female copper insert, M8 thread, 20 mm outer diameter | Datasheet |
| Terminal tightening torque | 10–12 N·m | Datasheet |
| Vent plugs | Acid-proof, flame-retardant, explosion-proof; catalytic plug optional | Datasheet |
| Applicable standards | IEC 60896-11, DIN 40736, IEC 61427, Eurobat long-life guide, BS 6290 part 4, UL 1989 | Datasheet |
| Certifications | ISO 9001, ISO 14001, OHSAS 18001:2007 (GB/T 28001), CE | Datasheet |
Solar and wind long-time discharge
For renewable duty the useful capacity is quoted at a lower cut-off voltage, because the controller protects the battery long before the cell reaches 1.80 V. The datasheet publishes the following capacities at a 1.85 V cut-off:
| Rate | Capacity at 1.85 V per cell | Source |
|---|---|---|
| C24 | 1,695 Ah | Datasheet |
| C48 | 1,860 Ah | Datasheet |
| C72 | 1,950 Ah | Datasheet |
| C100 | 2,025 Ah | Datasheet |
| C120 | 2,055 Ah | Datasheet |
| C240 | 2,100 Ah | Datasheet |
§2 — The Pain: Why Utility-Scale Purchases Go Wrong
First, the capacity number without a rate is not a number. The OPzS2-1500 2V1500Ah is rated at C10. A distributor who quotes “1,500 Ah” without the rate is quoting a figure that does not describe your duty. At a one-hour discharge the cell gives roughly half its C10 capacity; at a ten-hour discharge it gives the full figure. A utility plant that rides out a cloudy night on a slow discharge sits close to the C10 curve, while a ride-through cabinet with a five-minute discharge at high load sees far less. Specify the rate and the cut-off voltage together with the capacity, always.
Second, flooded means a room, not a container. Hydrogen evolves during charging and needs a path out. Acid-proof flame-retardant vent plugs handle the ignition source; they do not handle the accumulation. Every OPzS2-1500 installation needs mechanical ventilation sized for the worst-case float and equalisation charge, and it needs a person with a hydrometer and a top-up bottle on a schedule. Buyers who treat the OPzS2-1500 2V1500Ah as a drop-in replacement for a sealed block discover the difference in the first hot season.
Third, charge acceptance quietly caps the whole project. The published maximum charging current for the OPzS2-1500 is 300 A, which is 0.20 C10. At 48 V nominal that is about 14.5 kW. An array sized on the load rather than on the battery is an array the battery cannot absorb. The excess goes into float losses, extended equalisation, or an over-voltage disconnect that takes the inverter out of service. The array is the expensive half of a utility project, so fix this number before the panels are ordered.
Fourth, the float life is temperature-bound, and the datasheet is specific about it. The designed floating life of 20+ years is stated at 20 °C, and it is roughly halved for every 10 °C above that. A container in Chennai, Durban or Karachi that runs at 30 °C ambient all year is looking at a life closer to ten years, not twenty, and no controller precision changes that. Room cooling is a battery decision, not a comfort decision.
Fifth, the physical envelope is not negotiable. 275 mm long, 210 mm wide and 850 mm tall over terminals, with 98 kg filled. Rack pitch, aisle width, door clearance and the lifting route for a single cell all have to be confirmed against the drawing before the plinth is poured. Substituting a guess is how a delivery arrives that cannot be installed.
§3 — The Choice: Where the OPzS2-1500 Sits
The alternative to the OPzS2-1500 2V1500Ah is rarely another chemistry. In utility renewable, substation and large telecom markets where this cell is specified, the real choice is the same flooded platform at a different capacity, the gel variant of the same platform, or a sealed VRLA block of lower capacity.
Against the neighbouring flooded capacities
| Parameter | OPzS2-1000 2V1000Ah | OPzS2-1500 2V1500Ah | OPzS2-2000 2V2000Ah |
|---|---|---|---|
| Rated capacity (C10) | 1,000 Ah | 1,500 Ah | 2,000 Ah |
| Cell dimensions | 233 × 210 × 645 mm | 275 × 210 × 850 mm | 399 × 210 × 826 mm |
| Total height over terminals | 645 mm | 850 mm | 826 mm |
| Weight without electrolyte | 53.5 kg | 71.0 kg | 106 kg |
| Weight with electrolyte | 73.5 kg | 98 kg | 146 kg |
| Internal resistance | 0.45 mΩ at 20 °C | 0.40 mΩ at 20 °C | 0.35 mΩ at 20 °C |
| Maximum charging current | 200 A | 300 A | 400 A |
| Short-circuit current | 4,500 A | 5,400 A | 6,000 A |
| Float voltage | 2.23 V per cell | 2.23 V per cell | 2.23 V per cell |
| Designed float life | 20+ years at 20 °C | 20+ years at 20 °C | 20+ years at 20 °C |
The middle column is the OPzS2-1500 datasheet; the OPzS2-1000 and OPzS2-2000 figures are the published values for those models. Three observations follow directly.
The OPzS2-1500 absorbs 300 A per cell, so a 48 V string of 24 cells accepts 7,200 A. That covers an array of roughly 14.5 kW on one string. Below that the OPzS2-1000 at 200 A is the natural choice; above it the OPzS2-2000 at 400 A is.
Internal resistance falls from 0.45 mΩ to 0.35 mΩ across this range, which makes a large string electrically cleaner at the same fault duty and why voltage recovery after a load step is less punishing on the bigger cells.
Height is not shared across the range: the OPzS2-1000 stands 645 mm over terminals while the OPzS2-1500 and OPzS2-2000 stand 850 mm and 826 mm. A rack built for one is not a rack for another, so the OPzS2-1500 drawing governs the aisle and the lifting route.
The 48 V string arithmetic
Every number below is derived from the published per-cell figures above.
| Derived quantity | Calculation | Result |
|---|---|---|
| String nominal energy | 24 × 2 V × 1,500 Ah | 72 kWh |
| String series resistance | 24 × 0.40 mΩ | 9.60 mΩ |
| String maximum charging current | 24 × 300 A | 7,200 A |
| String maximum discharge current (5 s) | 24 × 2,500 A | 60,000 A |
| String weight filled | 24 × 98 kg | 2,352 kg |
| String weight dry | 24 × 71.0 kg | 1,704 kg |
| String acid weight | 24 × 27 kg | 648 kg |
| Short-circuit current at the terminals | 48 V ÷ 9.60 mΩ | ≈5,000 A |
The last line is a calculation, not a datasheet figure: the published short-circuit current of 5,400 A is the manufacturer’s value for the cell and governs protection coordination. Use the published number for coordination and treat the derived figure as a sanity check on the wiring.
Flooded against gel
If nobody will ever touch the battery — no water top-up, no quarterly equalisation, no hydrometer — the gel version of this platform is the better product, and the OPzS2-1500 2V1500Ah is the wrong choice. Gel removes the room requirement: no ventilation path, no topping up, no hydrogen accumulation. The cost is a lower published cycle-life floor and marginally higher internal resistance. Make that trade explicitly, because it is a labour decision as much as a chemistry decision.
§4 — The Framework: Nine Things to Fix Before the Order
1. Lock the rate with the capacity. Write “OPzS2-1500 2V1500Ah, 1,500 Ah at C10 to 1.80 V per cell at 20 °C” on the purchase order, not “1,500 Ah”. If the duty is a shorter discharge, ask for the capacity at that rate and at the cut-off voltage the controller will use.
2. Fix the string architecture on paper first. 24 cells at 2 V gives 48 V nominal, which is the common utility and telecom DC bus. 48 cells gives 96 V. Write the cell count, the nominal bus voltage and the end-point voltage at 1.80 V per cell — 43.2 V for a 24-cell string — next to the load list. Every downstream number, from charger rating to cable cross-section, follows from those three figures.
3. Check the charge ceiling against the array. Maximum charging current is 300 A per cell, so 7,200 A for a 24-cell string, roughly 14.5 kW at 48 V nominal. If the array exceeds that, step up one capacity in the range or fit a charge-current limit in the controller. Decide before the array is ordered.
4. Use the renewable setpoint table, not the generic one. For solar and wind the datasheet publishes a dedicated set of controller parameters, and they are not the same as the stationary float-and-equalise pair:
| Parameter | Value | Source |
|---|---|---|
| Over-voltage disconnect | 2.47 ± 0.01 V per cell | Datasheet |
| Regulation / equalise voltage | 2.40 ± 0.01 V per cell | Datasheet |
| Array reconnection voltage | 2.23 ± 0.005 V per cell | Datasheet |
| Float voltage setting | 2.25 ± 0.005 V per cell | Datasheet |
| Low-voltage alarm | 1.95 ± 0.005 V per cell | Datasheet |
| Low-voltage disconnect | 1.90 ± 0.005 V per cell | Datasheet |
| Load reconnect voltage | 2.09 ± 0.01 V per cell | Datasheet |
| Temperature compensation coefficient | −4 mV per cell per °C | Datasheet |
Note the deliberate difference from the stationary setpoints in §1. The renewable float setting is 2.25 V per cell, not 2.23 V, and the renewable compensation coefficient is −4 mV per cell per °C, not −3 mV. Renewable charging is intermittent, so the controller holds the array at a slightly higher potential to capture what light there is, and the −4 mV coefficient is matched to the wider temperature swing of an outdoor cabinet. Copying the stationary numbers into a solar controller is a common and expensive error.
5. Design the ventilation path. Hydrogen evolves on charge. Provide mechanical extraction sized for the worst-case charge case, keep flame-retardant acid-proof vent plugs fitted, and confirm the room is not a sealed container with one door.
6. Schedule the water. An OPzS2-1500 cell loses water on every charge cycle. Quarterly top-up with distilled or demineralised water, a quarterly specific-gravity reading on every cell and a logged equalisation at a defined interval are operating requirements, not maintenance extras. Budget the labour; a battery that is never checked fails at the worst time.
7. Confirm the mechanical envelope against the drawing. For the OPzS2-1500: 275 × 210 × 850 mm, 98 kg filled, terminal centre spacing 108 mm, M8 female insert at 10–12 N·m. Rack pitch, door clearances, the lifting route for a 98 kg cell and the floor loading all need the drawing, not a spreadsheet.
8. Set the end-of-life criterion now. Define the capacity floor — the percentage of rated C10 at which the string is replaced — and put it in the maintenance plan with a date attached. Without a written criterion, end-of-life is a judgement call made under pressure during an outage.
9. Order the spares policy deliberately. Cells in a series string age unevenly. Decide in advance whether you hold one spare OPzS2-1500 cell on site, and note that a spare must be the same model and age band as the string, not a newer cell dropped into an older string.
§5 — The Trust: Who Built It and What Is Certified
CHISEN operates 8 production bases with an annual capacity of 70 million kVAh, which is the scale behind the published datasheet rather than a marketing figure on a web page. The OPzS2-1500 2V1500Ah is built to IEC 60896-11 for stationary lead-acid valves and DIN 40736 for tubular cells, with IEC 61427 and BS 6290 part 4 also applicable and the UL 1989 listing covering the North American side. The Eurobat long-life guide applies to the float-life claim. The manufacturing system is certified to ISO 9001 for quality management and ISO 14001 for environmental management, with OHSAS 18001:2007 (GB/T 28001) covering occupational health and safety, and the product carries CE marking. Every export shipment is documented with CE, UL and IEC certification papers for the exact variant.
Those standards matter commercially, not just decoratively. DIN 40736 and IEC 60896-11 are what an importer’s technical file has to cite for EU market access; BS 6290 part 4 and UL 1989 are what a buyer in Mumbai, Karachi, Durban or a Gulf port asks for when the battery is going into a tender. The same document set is requested in Rotterdam, Hamburg, Jebel Ali, Santos, Mombasa, Antwerp, Colombo and Lagos: the standards are identical, the local authority requirements are not.
The certification set is a claim you can verify rather than take on trust: request the test certificates for the exact model, check that the scope covers the 1,500 Ah variant, and confirm the certificate address matches the supplier quoting it. Do this before a 24-cell OPzS2-1500 string lands on your floor, because a certificate that does not cover the variant is a documentation problem discovered at the wrong moment.
The 8 production bases and 70 million kVAh of capacity also matter for delivery risk on a large project. A 48 V string of 24 OPzS2-1500 cells at 98 kg filled is 2,352 kg of battery from one production base, and a mixed-date delivery is a mixed-age string. Ask for the manufacturing date on the cells, and ask that the whole string be produced within one production window.
§6 — FAQ: OPzS2-1500 2V1500Ah
Q1. What is the rated capacity of the OPzS2-1500 2V1500Ah? 1,500 Ah at the ten-hour rate, meaning 150 A for 10 hours to a 1.80 V per cell cut-off at 20 °C. The datasheet also publishes renewable long-time discharge capacities at a 1.85 V cut-off, from 1,695 Ah at C24 up to 2,100 Ah at C240.
Q2. What are the physical dimensions and weight of one OPzS2-1500 cell? 275 × 210 × 850 mm overall, with a 795 mm container and 850 mm height over terminals. 71.0 kg without electrolyte, 98 kg with electrolyte, and 27 kg of acid at 1.240 g/cm³. One filled cell is a two-person handling job.
Q3. What float and equalise voltages should the charger use? Float 2.23 V per cell at 25 °C with −3 mV/°C/cell compensation, and equalise 2.35 V per cell at 25 °C over a 20–25 °C range. For solar and wind duty the controller setpoints differ — 2.25 V float and a −4 mV per cell per °C coefficient — and are listed in §4.
Q4. How much current can the OPzS2-1500 take during charging? The published maximum charging current is 300 A, which is 0.20 C10. A 24-cell 48 V string therefore accepts 7,200 A, roughly 14.5 kW at nominal bus voltage. Exceeding that limit pushes the array into float losses or triggers an over-voltage disconnect.
Q5. What are the internal resistance and short-circuit current of the OPzS2-1500? Internal resistance is approximately 0.40 mΩ fully charged at 20 °C. The published short-circuit current is 5,400 A, and the maximum discharge current is 2,500 A for 5 s. A 24-cell string presents 9.60 mΩ in series.
Q6. How long does the OPzS2-1500 2V1500Ah last in float service? The designed floating life is 20+ years at 20 °C. Float life falls by roughly half for every 10 °C above 20 °C, so an uncooled container at 30 °C ambient should expect materially less.
Q7. What maintenance does the OPzS2-1500 require? Quarterly water top-up with distilled or demineralised water, a quarterly specific-gravity reading on every cell, equalisation on a logged schedule, and hydrogen ventilation sized for the worst-case charge case. Acid-proof flame-retardant vent plugs must stay fitted.
Q8. Can the OPzS2-1500 2V1500Ah be used for solar storage? Yes, and the datasheet publishes a dedicated setpoint table for renewable duty, including the 2.47 ± 0.01 V over-voltage disconnect, the 2.40 ± 0.01 V regulation voltage and the 1.90 ± 0.005 V low-voltage disconnect. The 300 A maximum charging current still applies, so the array must be sized against it.
Q9. What certifications does the OPzS2-1500 2V1500Ah carry? Built to IEC 60896-11, DIN 40736, IEC 61427, the Eurobat long-life guide, BS 6290 part 4 and UL 1989. The manufacturing system is certified to ISO 9001 and ISO 14001, with OHSAS 18001:2007 (GB/T 28001), and the product carries CE marking.
Expert Summary
The OPzS2-1500 2V1500Ah is a 2 V, 1,500 Ah flooded tubular cell for 48 V and 96 V DC strings in utility renewable plants, large telecom power rooms and traction substations. Its published envelope is 275 × 210 × 850 mm at 71.0 kg dry and 98 kg filled, with 0.40 mΩ internal resistance, a 5,400 A short-circuit current and a 300 A maximum charging current.
Four decisions carry the project. Size on C10 with the cut-off voltage attached to the capacity. Respect the 300 A charge ceiling when the array is specified, or step up one capacity in the range. Use the renewable setpoint table for solar and wind rather than the stationary pair. And budget the labour and ventilation a flooded cell needs, because the 20+ year float life at 20 °C only holds in a maintained, ventilated, temperature-controlled room.
For a 24-cell 48 V string the arithmetic is 72 kWh nominal, 9.60 mΩ in series, 7,200 A of charge acceptance, 2,352 kg of installed battery and 648 kg of acid. Take those five numbers to the civil and electrical design, and the OPzS2-1500 2V1500Ah will do what the datasheet says it does.
Contact CHISEN
Technical enquiries, project drawings and tender documents: sales@chisen.cn and +86 131 6622 6999 on WhatsApp. Mention the model OPzS2-1500 and the string voltage you are designing for, and the CHISEN team will supply the certified per-cell datasheet, the certified weight, the drawing and the test certificates for the exact variant.
Related reading: the OPzS2-1500 2V1500Ah model page, the OPzS2-2000 2V2000Ah model page for the cell above it in the range, and the OPzS flooded tubular battery range for the full platform.
Related CHISEN Buyer Guides
- OPzS2 Tubular Flooded Battery Solar Storage: The Complete 2026 Technical Guide
- OPzV2-1000 2V1000Ah Tubular Gel Battery for Telecom UPS Solar Storage — CHISEN Industrial
- OPzV2-200 2V200Ah Tubular Gel Battery: Industrial Buyer’s Guide for 48V Telecom, Sol
- OPzV2-350 2V350Ah Tubular Gel Battery for Telecom, UPS & Solar Storage — CHISEN Buyer
- OPzV2-600 2V600Ah Tubular Gel Battery for Telecom UPS Solar Storage — CHISEN Industrial Bu