Answer First
The 6-EVF-60 12V60Ah is a 12 V, 60 Ah VRLA (AGM) battery published by CHISEN at the C3 rate, with case dimensions 258×170×160 mm and a weight of 18.8 ± 0.2 kg. It is built for the mid-sized telecom and base-station duty cycle: a single cabinet load, a small microwave or repeater site, or a distributed power shelf that has to ride through grid failures without a generator starting instantly. Published float voltage is 13.5 V and equalise voltage is 14.1 V, the charge-current ceiling is 12.0 A, and the cut-off is 1.75 V per cell. The full specification set is on this model page.
In arithmetic terms the 6-EVF-60 12V60Ah stores 12 V × 60 Ah = 720 Wh nominal energy in a 18.8 kg case, or 720 ÷ 18.8 = 38.3 Wh/kg of mass. Six 2 V cells make up the string: 6 × 2.25 V/cell = 13.5 V float, 6 × 2.35 V/cell = 14.1 V equalise, and 6 × 1.75 V/cell = 10.5 V string cut-off. Those three numbers are enough to size a rectifier, a generator interface and a discharge alarm threshold before a single quote is requested.
For a site drawing 300 W on the rectifier, half of the rated 720 Wh is usable at the published 50 % depth-of-discharge band, so 720 × 0.5 = 360 Wh ÷ 300 W = 1.2 hours of autonomy. A 150 W cabinet gives 360 ÷ 150 = 2.4 hours, and a 100 W shelf gives 360 ÷ 100 = 3.6 hours.
Key Takeaways
- 6-EVF-60 12V60Ah, published at 12 V / 60 Ah / C3 with 258×170×160 mm case and 18.8 ± 0.2 kg weight, per the CHISEN model page.
- 720 Wh nominal per string: 12 V × 60 Ah, which works out to 38.3 Wh/kg across the 18.8 kg mass.
- Six 2 V cells per string — 13.5 V float, 14.1 V equalise, 10.5 V string cut-off at the published 1.75 V/cell.
- Charge current capped at 12.0 A, equal to 12.0 ÷ 60 = 0.2 C, which is the sizing number for the rectifier output stage.
- Cycle life published at 350–600 cycles across a 50–80 % depth-of-discharge band; design life 2–5 years, working range −15…50 °C.
- Self-discharge ≤3 %/month at 25 °C, so a 6-EVF-60 12V60Ah on float in a warm regional depot loses about 1.8 Ah per month before any discharge duty is applied.
§1 — 6-EVF-60 Quick Specifications
Every row below is taken from the published CHISEN model page for the 6-EVF-60. Nothing in this table is estimated; derived figures are labelled Arithmetic and the calculation is written out in full.
| Parameter | Value | Source |
|---|---|---|
| Nominal voltage | 12 V | Model page |
| Nominal capacity | 60 Ah | Model page |
| Capacity rate | C3 | Model page |
| Case dimensions (L×W×H) | 258×170×160 mm | Model page |
| Weight | 18.8 ± 0.2 kg | Model page |
| Terminal | φ14-M6 | Model page |
| Float voltage | 13.5 V (2.25 V/cell) | Model page |
| Equalise voltage | 14.1 V (2.35 V/cell) | Model page |
| Cycle life | 350–600 cycles (DoD 50–80 %) | Model page |
| Maximum charge current | 12.0 A | Model page |
| Cut-off voltage | 1.75 V/cell | Model page |
| Self-discharge | ≤3 %/month at 25 °C | Model page |
| Working temperature | −15…50 °C | Model page |
| Design life | 2–5 years | Model page |
| Cells per string | 6 × 2 V | Arithmetic — 12 V ÷ 2 V/cell = 6 |
| Nominal energy | 720 Wh | Arithmetic — 12 V × 60 Ah = 720 Wh |
| Energy density | 38.3 Wh/kg | Arithmetic — 720 Wh ÷ 18.8 kg = 38.3 Wh/kg |
| String cut-off | 10.5 V | Arithmetic — 6 cells × 1.75 V/cell = 10.5 V |
| Charge current in C-rate | 0.2 C | Arithmetic — 12.0 A ÷ 60 Ah = 0.2 C |
§2 — The Pain: Base Stations That Drop When the Grid Does
Telecom cabinets fail in a small number of recurring ways, and all of them land on the battery string. A rectifier set that is under-sized for the site, a site running at 12.00 V float instead of the published 13.5 V, an ambient temperature of 45 °C inside a unventilated shelter, or a string that was left on float for a full monsoon season without a discharge check — each of these quietly shortens the service life of the valve-regulated cells before the first real outage happens.
The numbers on the 6-EVF-60 12V60Ah make the exposure easy to quantify. At the published self-discharge rate of ≤3 %/month at 25 °C, a stored string loses 60 Ah × 3 % = 1.8 Ah every month. Over a six-month warehouse laydown that is 1.8 × 6 = 10.8 Ah of the 60 Ah rating gone before the battery is even installed. In a warm coastal depot the working temperature band tops out at 50 °C, and float life shortens every degree above 25 °C — which is why the same 6-EVF-60 12V60Ah that supports a site in a temperate market can underperform in an equatorial one if the installation is not designed for it.
The second failure mode is a mismatch between the discharge profile and the published capacity rate. The 6-EVF-60 12V60Ah is published at C3, that is 60 Ah ÷ 3 h = 20 A for three hours to the 1.75 V/cell cut-off. A site that expects a much shorter, heavier discharge — a 300 W cabinet pulling roughly 25 A from a 12 V bus — will not see the full 60 Ah; the usable figure drops because the published C3 rate is the reference point, not a claim about every discharge duration.
The third failure mode happens after the outage. A string that discharges to 1.75 V/cell and then sits in a partially discharged state, or one that is recharged with a rectifier unable to deliver the published 12.0 A charge current, will come back to float in a weaker state than it left. The published 12.0 A ceiling equals 0.2 C for this model, which is the number the site engineer needs when sizing the charging path.
§3 — The Choice: Matching the 6-EVF-60 12V60Ah to the Load
Choosing a 60 Ah VRLA cell for a telecom duty is not a single-equation decision. Three variables decide whether the 6-EVF-60 12V60Ah is right for the site: the DC load in watts, the autonomy the operator is willing to guarantee, and the ambient temperature band the cabinet actually sees.
Start with energy. The string holds 12 V × 60 Ah = 720 Wh nominal. Apply the depth-of-discharge band from the published cycle-life figure, 50–80 %, and the usable energy sits between 720 × 0.5 = 360 Wh and 720 × 0.8 = 576 Wh. A 200 W cabinet therefore runs 360 ÷ 200 = 1.8 hours at the conservative end, or 576 ÷ 200 = 2.9 hours if the site accepts the 80 % end of the published band.
Next, check the current against the capacity rate. The published 60 Ah is a C3 figure, so the reference discharge is 60 Ah ÷ 3 h = 20 A. A 200 W cabinet on a 12 V bus draws 200 W ÷ 12 V = 16.7 A, which is inside the C3 reference; a 300 W cabinet draws 300 ÷ 12 = 25 A, which is a harder duty than the published rate and should be quoted to the factory with the actual load profile if it becomes the design basis.
Then look at the physical side. At 258×170×160 mm and 18.8 ± 0.2 kg, the 6-EVF-60 12V60Ah fits a standard 19-inch telecom power shelf with two cells side by side in a battery tray, and it is heavy enough to be stable in a seismic or high-wind site. The φ14-M6 terminal is larger than the φ8.0-M5 and φ8.8-M5 terminals used on the smaller 6-DZF cells in the same catalogue, so the bus bar and cable lug selection has to match.
Where the duty needs more energy than a 60 Ah string can carry, step up within the same catalogue rather than changing chemistry. The the sibling model page covers the 50 Ah point in the range, and the wider set of sizes, ratings and case formats is set out on the full product range. Any of them keeps the same 13.5 V float, 14.1 V equalise, 1.75 V/cell cut-off and 13.5 V float charging discipline, which keeps the site maintenance procedure unchanged when the capacity step is made.
§4 — The Framework: A Five-Step Sizing and Acceptance Procedure
The framework below turns the published 6-EVF-60 12V60Ah figures into a repeatable method that an importer, a site engineer and a procurement officer can each apply without guessing.
Step 1 — Fix the load. Measure the steady DC draw of the cabinet at the rectifier output, not the AC rating of the mains feed. Convert to string current with load watts ÷ 12 V bus. A 180 W cabinet draws 180 ÷ 12 = 15 A; a 240 W cabinet draws 240 ÷ 12 = 20 A, which is exactly the published C3 reference current of 60 Ah ÷ 3 h = 20 A.
Step 2 — Fix the autonomy. Choose the hours of backup the site must guarantee, multiply by the current, and convert to ampere-hours: 20 A × 3 h = 60 Ah, the full rating of the 6-EVF-60 12V60Ah, leaving no margin. A defensible design takes the margin out of the depth-of-discharge band instead: 20 A × 3 h = 60 Ah asked of a string whose usable band at 50 % is 360 Wh ÷ 12 V = 30 Ah. In practice that means either a longer string or a larger capacity model.
Step 3 — Fix the voltage window. The string runs between 13.5 V float and a 10.5 V cut-off computed as 6 cells × 1.75 V/cell. Anything in the site’s rectifier, DC distribution and alarm thresholds has to be consistent with that window, including the 14.1 V equalise point of 6 × 2.35 V/cell used during re-charge.
Step 4 — Fix the thermal and charging envelope. The working temperature range is −15…50 °C and the maximum charge current is 12.0 A, that is 0.2 C. Confirm the rectifier can hold 12.0 A and absorb the 14.1 V equalise without over-charge, and confirm the cabinet ventilation keeps the cells inside the published band in the hottest month.
Step 5 — Fix the acceptance test on delivery. Measure the open-circuit voltage of every cell in the string, confirm six cells per unit, weigh the unit against the published 18.8 ± 0.2 kg, and measure the case against 258×170×160 mm. Check the delivery date against the self-discharge window: at ≤3 %/month, a string that has been in transit for two months has already lost 60 Ah × 3 % × 2 = 3.6 Ah.
§5 — Where the 6-EVF-60 12V60Ah Sits Against Its Siblings
The table below lists the published figures for the 6-EVF-60 12V60Ah and the models most often specified alongside it. Energy density is an Arithmetic column, computed as (V × Ah) ÷ weight in kilograms, and is shown so that the comparison is made on a like-for-like basis rather than on nameplate capacity alone.
| Model | V / Ah | Rate | Dimensions (mm) | Weight | Terminal | Float / Equalise | Charge current | Energy density (Arithmetic) |
|---|---|---|---|---|---|---|---|---|
| 6-EVF-60 (this model) | 12 / 60 | C3 | 258×170×160 | 18.8 ± 0.2 kg | φ14-M6 | 13.5 V / 14.1 V | 12.0 A | 720 Wh ÷ 18.8 kg = 38.3 Wh/kg |
| 6-DZF-12 | 12 / 12 | C2 | 151×99×99 | 3.6 ± 0.2 kg | φ8.0-M5 | 13.5 V / 14.1 V | 2.4 A | 144 Wh ÷ 3.6 kg = 40.0 Wh/kg |
| 6-DZF-20 | 12 / 20 | C2 | 180×76×170 | 6.1 ± 0.2 kg | φ8.8-M5 | 13.5 V / 14.1 V | 4.0 A | 240 Wh ÷ 6.1 kg = 39.3 Wh/kg |
| 6-DMF-38 | 12 / 38 | C3 | 224×106×175 | 10.45 ± 0.2 kg | φ9.8-M5 | 13.5 V / 14.1 V | 7.6 A | 456 Wh ÷ 10.45 kg = 43.6 Wh/kg |
| 6-DMF-45 | 12 / 45 | C3 | 224×121×175 | 12.3 ± 0.2 kg | φ11.8-M5 | 13.5 V / 14.1 V | 9.0 A | 540 Wh ÷ 12.3 kg = 43.9 Wh/kg |
| 6-DMF-52 | 12 / 52 | C3 | 224×135×175 | 13.7 ± 0.2 kg | φ11.8-M6 | 13.5 V / 14.1 V | 10.4 A | 624 Wh ÷ 13.7 kg = 45.5 Wh/kg |
| 6-EVF-50 | 12 / 50 | C3 | 230×140×180 | 15.25 ± 0.2 kg | φ11.8-M6 | 13.5 V / 14.1 V | 10.0 A | 600 Wh ÷ 15.25 kg = 39.3 Wh/kg |
| 6-EVF-80 | 12 / 80 | C3 | 259×170×218 | 25.7 ± 0.2 kg | φ16-M6 | 13.5 V / 14.1 V | 16.0 A | 960 Wh ÷ 25.7 kg = 37.4 Wh/kg |
| 6-EVF-100 | 12 / 100 | C3 | 330×170×218 | 31.5 ± 0.2 kg | φ20-M8 | 13.5 V / 14.1 V | 20.0 A | 1 200 Wh ÷ 31.5 kg = 38.1 Wh/kg |
| 6-EVF-120 | 12 / 120 | C3 | 407×170×240 | 40 ± 0.2 kg | φ20-M8 | 13.5 V / 14.1 V | 24.0 A | 1 440 Wh ÷ 40 kg = 36.0 Wh/kg |
| 6-EVF-150 | 12 / 150 | C3 | 483×170×240 | 48.5 ± 0.2 kg | φ20-M8 | 13.5 V / 14.1 V | 30.0 A | 1 800 Wh ÷ 48.5 kg = 37.1 Wh/kg |
Two observations follow directly from the published numbers. First, the 6-DMF-52 carries the highest energy density in this group at 45.5 Wh/kg against the 6-EVF-60 12V60Ah figure of 38.3 Wh/kg, because the 6-DMF case is shallower at 135 mm against 170 mm while still using an M6 terminal — a lower-volume but lighter format, useful where cabinet depth is limited. Second, energy density falls gently as capacity climbs inside the EVF series: 39.3 Wh/kg at 50 Ah, 38.3 Wh/kg at 60 Ah, 37.4 Wh/kg at 80 Ah, 38.1 Wh/kg at 100 Ah, 36.0 Wh/kg at 120 Ah and 37.1 Wh/kg at 150 Ah. That is the normal effect of larger cases and heavier grids, and it is why the 60 Ah point is often specified where a site needs more than the 50 Ah model but cannot take the depth of the 80 Ah model.
§6 — The Trust: Factory Capacity, Certification and Export Delivery
CHISEN operates 8 production bases with an annual capacity of 70 million kVAh, and the plant behind the 6-EVF-60 12V60Ah holds CE, ISO 9001, ISO 14001, UL and IEC certification. The 12 V VRLA programme covers the 6-DZF, 6-DMF and 6-EVF series, all released on the same float discipline of 13.5 V and equalise of 14.1 V, so the after-sales procedure, the charger configuration and the spare-part strategy stay identical as a site grows from one string to several.
Export logistics are routine for this class of product. Containers are loaded from Ningbo and Shanghai for distributors in India, Nigeria, Kenya, Vietnam, the Philippines, Brazil, Egypt, Mexico, Indonesia and Pakistan, and for regional hubs in Dubai and Jebel Ali, Karachi, Mumbai, Chennai, Lagos, Mombasa, Durban, Cairo and Colombo. Every shipment should specify the destination port, the quantity, the required capacity and the target date so that packing detail and the delivery schedule can be confirmed against the 6-EVF-60 12V60Ah specification.
Quality control at delivery is what separates a documented model from a generic cell. On receipt of a 6-EVF-60 12V60Ah consignment, measure cell-level open-circuit voltage on every unit, confirm six cells per string, weigh against the published 18.8 ± 0.2 kg, and measure the case against 258×170×160 mm. Check the production date and compare it against the ≤3 %/month self-discharge window, because a unit that has spent three months in transit has lost 60 Ah × 3 % × 3 = 5.4 Ah of its rating before installation. Terminal torque, the design-life reference temperature and the internal-resistance curve are not published and should be requested from the factory so that the site procedure can be written against verified values rather than assumptions.
§7 — FAQ
Q1: What are the published nominal voltage and capacity of the 6-EVF-60? 12 V and 60 Ah at the C3 capacity rate, taken from the CHISEN model page. That is 12 V × 60 Ah = 720 Wh nominal per string (Arithmetic).
Q2: What float and equalise setpoints does the manufacturer publish for the 6-EVF-60? Float 13.5 V and equalise 14.1 V, both from the model page, equivalent to 2.25 V/cell and 2.35 V/cell across the six 2 V cells.
Q3: What is the maximum charging current for the 6-EVF-60? 12.0 A, published on the model page, which is 12.0 A ÷ 60 Ah = 0.2 C (Arithmetic). The rectifier output stage must be sized for that figure.
Q4: What are the case dimensions and weight of the 6-EVF-60? 258×170×160 mm and 18.8 ± 0.2 kg, both from the model page.
Q5: What terminal type and torque does the 6-EVF-60 use? The terminal is φ14-M6, published on the model page. The tightening torque value is not published and should be requested from the factory before the installation procedure is frozen.
Q6: How many cells does a 12V60Ah string contain and what bus voltage does it give? Six 2 V cells: 12 V ÷ 2 V/cell = 6 (Arithmetic). The bus sits at 13.5 V on float and drops to a 10.5 V cut-off, computed as 6 cells × 1.75 V/cell.
Q7: What is the published design float life of the 6-EVF-60 and at what temperature? Design life is published as 2–5 years and self-discharge is stated as ≤3 %/month at 25 °C, both from the model page. A separate float-life reference temperature is not published; request it from the factory if the site runs hot.
Q8: How should an importer verify the 6-EVF-60 on delivery? Measure cell-level open-circuit voltage, confirm six cells per unit, weigh against 18.8 ± 0.2 kg, measure against 258×170×160 mm, and check the production date against the ≤3 %/month self-discharge window.
Q9: Which certifications does the CHISEN factory behind the 6-EVF-60 hold? CE, ISO 9001, ISO 14001, UL and IEC, as recorded in the CHISEN company fact sheet.
Q10: How do I request a quotation or samples for the 6-EVF-60? Send the required capacity, quantity, destination port and target date to sales@chisen.cn or jack@chisen.cn, or message the export desk on WhatsApp +86 131 6622 6999.
Expert Summary
The 6-EVF-60 12V60Ah is a 12 V 60 Ah AGM VRLA cell published by CHISEN at the C3 rate, with 258×170×160 mm case dimensions, 18.8 ± 0.2 kg weight, φ14-M6 terminals, 13.5 V float, 14.1 V equalise, 12.0 A maximum charge current, 1.75 V/cell cut-off, ≤3 %/month self-discharge at 25 °C, a −15…50 °C working range, 350–600 cycles at 50–80 % depth of discharge and 2–5 years of published design life. Six 2 V cells give 720 Wh nominal and 38.3 Wh/kg, with a 10.5 V string cut-off, so a 200 W cabinet at 15 A draws about 1.8 hours from the conservative 360 Wh usable band and about 2.9 hours from the 576 Wh upper band; a 300 W cabinet at 25 A exceeds the published C3 reference current of 20 A and should be quoted to the factory with the real load profile. The 50 Ah and 80 Ah models in the same series keep identical voltage setpoints while changing only case size and mass, and the 6-DMF series reaches 45.5 Wh/kg in a shallower 135 mm case for depth-constrained cabinets. Terminal torque, the float-life reference temperature and the internal-resistance curve are not published and should be requested from the factory, and every unit in a bank should come from one production batch with charger limits set to 13.5 V float, 14.1 V equalise and 12.0 A maximum.