6-DMF-52 12V52Ah AGM VRLA Battery for Solar Street Lighting

BatteryMaintenanceOrReplacementOldBattery

Answer First

The 6-DMF-52 is CHISEN’s 12 V, 52 Ah AGM VRLA cell in a single 12 V case, published on the model page at 224×135×175 mm and 13.7 ± 0.2 kg. For a solar street lighting programme, that means one battery per luminaire head for a single-day autonomy design, or two in parallel for a two-night reserve, at a footprint that fits inside a standard 200–250 mm pole base cabinet. Every number quoted below comes from the published model page, and every derived figure is shown as an arithmetic step so a procurement engineer can re-check it.

For a 30 W LED head drawing from a dusk-to-dawn controller, the nominal stored energy of one 6-DMF-52 is 12 V × 52 Ah = 624 Wh. At a 50 % depth-of-discharge window the usable block is 624 Wh × 0.50 = 312 Wh, which supports a 30 W load for 312 Wh ÷ 30 W = 10.4 hours of night operation. If your controller holds the lamp above 30 W, or your site has three cloudy days in the design year, size up one step to the 6-EVF-60 listed on the full product range.

Key Takeaways

  • Published size and mass: 224×135×175 mm, 13.7 ± 0.2 kg, φ11.8-M6 terminals (Model page).
  • Charge discipline: float 13.5 V, equalise 14.1 V, maximum charge current 10.4 A, cutoff 1.75 V per cell (Model page).
  • Energy density: 12 V × 52 Ah = 624 Wh nominal; 624 Wh ÷ 13.7 kg ≈ 45.5 Wh/kg of product weight (Arithmetic).
  • Autonomy at 30 W: 624 Wh × 50 % DoD ÷ 30 W ≈ 10.4 hours per 6-DMF-52 (Arithmetic).
  • Climate envelope: −15…50 °C operating, ≤3 %/month self-discharge at 25 °C (Model page).

§1 — 6-DMF-52 Quick Specifications

ParameterValueSource
Nominal voltage12 VModel page
Nominal capacity52 AhModel page
Capacity rateC3Model page
Dimensions (L×W×H)224×135×175 mmModel page
Weight13.7 ± 0.2 kgModel page
Terminalφ11.8-M6Model page
Float voltage13.5 VModel page
Equalise voltage14.1 VModel page
Cycle life350–600 cyclesModel page
Maximum charge current10.4 AModel page
Discharge cutoff1.75 V per cellModel page
Self-discharge≤3 %/monthModel page
Working temperature−15…50 °CModel page
Design lifeNot publishedModel page
this model pagethe sibling model page

§2 — The Pain: Three Failure Modes in Solar Street Lighting Fleets

Failure mode one — undersized autonomy. A 52 Ah block is frequently quoted as “52 Ah at 10 A discharge”, but a real LED head with driver losses draws closer to 33–36 W than its nameplate wattage. At 35 W, the usable energy of one 6-DMF-52 is 624 Wh × 0.50 = 312 Wh, and 312 Wh ÷ 35 W = 8.9 hours. A controller that keeps the lamp on until 04:30 after a 19:00 dusk needs 9.5 hours. The arithmetic, not the label, decides whether the site runs on battery or on the grid. This is why the controller’s actual cut-off timing belongs in the tender documents.

Failure mode two — wrong charge window. A common field error is setting the controller to a 13.8 V absorption step instead of the published 14.1 V equalise value. At 13.8 V the pack is never fully equalised, so the lowest-stressed cells drift downward, internal resistance rises and the series string charges the weakest cell first. The published 14.1 V equalise setpoint exists for exactly this reason.

Failure mode three — heat at the base cabinet. A pole base cabinet in a tropical or equatorial project can reach 45 °C during the dry season. Self-discharge is published at no more than 3 % per month at 25 °C, and the operating envelope is −15…50 °C. Inside that envelope the chemistry still works, but every additional degree costs usable capacity, which shortens the autonomy computed above. Ventilation, shading and correct float behaviour are cheaper than adding a second battery.

§3 — The Choice: Matching Battery Chemistry to the Solar Duty Cycle

Solar street lighting is a float application with a daily shallow discharge, and the 6-DMF-52 is specified for it as an AGM VRLA product: the electrolyte is absorbed in the separator, so there is no liquid to spill, no water to top up and no vent to service. For a pole-mounted cabinet, a cabinet-door-down battery, a telecom cabinet or an outdoor enclosure with a narrow footprint, that sealed construction is the practical deciding argument.

The choice is between two configurations of the same chemistry.

One 6-DMF-52 in series. This is the single-string configuration: six 2 V cells in one case forming a 12 V nominal block, charged at 13.5 V float and 14.1 V equalise. It serves head loads up to roughly 30 W with one night of autonomy, which is the majority of municipal and perimeter lighting tenders.

Two 6-DMF-52 units in parallel. Two identical cases on the same 12 V bus give 2 × 52 Ah = 104 Ah, and 2 × 624 Wh = 1,248 Wh nominal. At the same 50 % working depth of discharge that is 1,248 Wh × 0.50 = 624 Wh usable, which carries a 30 W load for 624 Wh ÷ 30 W = 20.8 hours, or a 40 W load for 624 Wh ÷ 40 W = 15.6 hours. Parallel strings also give the site a second night of reserve, which matters where a second cloudy day must be absorbed without a generator start.

§4 — The Framework: A Commissioning Protocol That Survives Two Wet Seasons

The difference between a 6-DMF-52 that lasts and one that fails in its second year is rarely the cell. It is the set of numbers written into the controller configuration sheet. This protocol is the one CHISEN recommends in writing for street lighting projects, and every value traces back to the published model page.

Step 1 — fix the charge stages. Float at 13.5 V (6 cells × 2.25 V). Equalise at 14.1 V (6 cells × 2.35 V), at a controlled current, with a defined frequency and a temperature cutoff. Absorption is not a published figure for this model, so it is left to the controller manufacturer and should be recorded as to be requested from the factory if the project specification demands it.

Step 3 — set the low-voltage cutoff at 10.5 V. Cutoff at 1.75 V per cell × 6 cells = 10.5 V. Setting the cutoff above this point shortens the usable window without protecting the cells; setting it below this point pushes the tail of the discharge into a region the product is not rated for.

Step 4 — apply temperature compensation. The working range is −15…50 °C, and self-discharge is published at ≤3 %/month at 25 °C. In a closed cabinet the cell temperature can sit well above the ambient reading, so a battery-temperature sensor on the negative terminal of the first cell should feed the float voltage correction, typically −3 mV per °C per cell above 25 °C.

Step 5 — run a documented acceptance test on delivery. Measure open-circuit voltage per cell after at least 12 hours of rest, confirm the string reads 12.6 V to 13.0 V when fully charged, record the cell-lot date printed on the case, and photograph the terminal torque marks.

§5 — Where the 6-DMF-52 Sits in the 12 V AGM Range

The table below lists published figures for the 6-DMF-52 and its neighbours in the 12 V VRLA programme. Every value is taken from the model pages; the energy columns are arithmetic on those published values.

ModelCapacity / RateL×W×H mmWeightCharge currentNominal Wh (Arithmetic)Wh/kg (Arithmetic)Design life
6-DMF-3838 Ah / C3224×106×17510.45 ± 0.2 kg7.6 A38 × 12 = 456 Wh456 ÷ 10.45 ≈ 43.6Not published
6-DMF-4545 Ah / C3224×121×17512.3 ± 0.2 kg9.0 A45 × 12 = 540 Wh540 ÷ 12.3 ≈ 43.92–5 years
6-DMF-5252 Ah / C3224×135×17513.7 ± 0.2 kg10.4 A52 × 12 = 624 Wh624 ÷ 13.7 ≈ 45.5Not published
6-EVF-5050 Ah / C3230×140×18015.25 ± 0.2 kg10.0 A50 × 12 = 600 Wh600 ÷ 15.25 ≈ 39.32–5 years
6-EVF-6060 Ah / C3258×170×16018.8 ± 0.2 kg12.0 A60 × 12 = 720 Wh720 ÷ 18.8 ≈ 38.32–5 years

§6 — The Trust: Factory Capacity, Quality Control and Delivery

CHISEN Battery operates from Hangzhou, China, with 8 production bases and an annual capacity of 70 million kVAh across three product lines: flooded tubular OPzS2, gel tubular OPzV2, and 12 V VRLA in the 6-DZF, 6-DMF and 6-EVF programmes. The 6-DMF-52 comes from that 12 V VRLA line, the same line that produces the 6-DMF-38, the 6-DMF-45 and the 6-EVF series, which is why their dimensions, terminal position and setpoints are directly comparable.

Certification is held at factory level: CE, ISO 9001, ISO 14001, UL and IEC. Every shipment is released against the published model-page figures, so the dimension, weight and setpoint values in this article are the values on the factory record, not marketing approximations.

On delivery, importers across India, Nigeria, Kenya, Vietnam, the Philippines, Brazil, Egypt and Mexico receive the same documentation pack: the cell-lot date, the factory test record at the C3 rate, the certificate set and the packing list showing case dimensions and gross mass. Consolidated shipments leave through Shanghai, Ningbo and Shenzhen for Indian, African, Southeast Asian and Latin American ports including Mumbai, Karachi, Lagos, Mombasa, Port Said, Colombo and Santos.

§7 — FAQ

Q1: What are the published nominal voltage and capacity of the 6-DMF-52? The model page publishes 12 V and 52 Ah at the C3 rate. The case holds six 2 V cells, since 12 V ÷ 2 V = 6 cells (Model page, Arithmetic).

Q2: What float and equalise setpoints does the manufacturer publish for the 6-DMF-52? Float 13.5 V and equalise 14.1 V, which correspond to 2.25 V and 2.35 V per cell across six cells: 6 × 2.25 V = 13.5 V and 6 × 2.35 V = 14.1 V (Model page, Arithmetic).

Q3: What is the maximum charging current for the 6-DMF-52? 10.4 A (Model page), equal to 0.2 × 52 Ah. Set the controller’s current limit at or below this value and log the setting (Arithmetic).

Q4: What are the case dimensions and weight of the 6-DMF-52? 224×135×175 mm and 13.7 ± 0.2 kg (Model page). The length and height match the 38 Ah and 45 Ah cases; it is 14 mm wider than the 6-DMF-45.

Q5: What terminal type and torque does the 6-DMF-52 use? φ11.8-M6 insert terminals (Model page). The torque figure is not published for this model, so take the M6 insert value from the terminal maker and request the factory torque specification in writing before assembly.

Q6: How many cells does a 12V52Ah string contain and what bus voltage does it give? Six cells, because 12 V ÷ 2 V = 6 (Arithmetic). The string floats at 13.5 V, equalises at 14.1 V and reaches its published cutoff at 10.5 V, since 1.75 V × 6 = 10.5 V (Model page, Arithmetic).

Q7: What is the published design float life of the 6-DMF-52 and at what temperature? Design life is not published for this model; neighbouring 6-DMF and 6-EVF cases publish 2–5 years (Model page). Self-discharge is ≤3 %/month at 25 °C and the working range is −15…50 °C (Model page).

Q8: How should an importer verify the 6-DMF-52 on delivery? Rest the pack for at least 12 hours, measure open-circuit voltage per cell, confirm 12.6–13.0 V when fully charged, record the cell-lot date, and check the case against 224×135×175 mm and 13.7 ± 0.2 kg (Model page, procedure in §4).

Q9: Which certifications does the CHISEN factory behind the 6-DMF-52 hold? CE, ISO 9001, ISO 14001, UL and IEC are held by the factory in Hangzhou, China, and the certificate set is issued with the order documentation for each shipment.

Q10: How do I request a quotation or samples for the 6-DMF-52? Write to sales@chisen.cn or jack@chisen.cn, or send a WhatsApp message to +86 131 6622 6999. State the lamp load in watts, the required autonomy in hours, the controller setpoints and the delivery market, and the quotation can be returned against that configuration.

Expert Summary

The 6-DMF-52 is a published, sealed 12 V 52 Ah AGM VRLA block at 224×135×175 mm and 13.7 ± 0.2 kg, with float 13.5 V, equalise 14.1 V, a 10.4 A charge limit, a 1.75 V per cell cutoff, ≤3 %/month self-discharge at 25 °C and a −15…50 °C working range. For solar street lighting it carries 624 Wh nominal, about 312 Wh usable at 50 % depth of discharge, which is 10.4 hours of a 30 W head and 8.9 hours of a 35 W head; two units in parallel give 1,248 Wh nominal and 20.8 hours at 30 W. The dimension, mass, charge current, energy density and setpoints are all published, so sizing can be closed arithmetically instead of assumed; the two open items, design life and terminal torque, should be obtained from the factory in writing before award.