Answer First
Before an OPzV battery China supplier can be judged on price, you should be able to verify six things on the supplier’s own datasheet: a float charge voltage of 2.23 V per cell at 25 °C, an equalise charge voltage of 2.35 V per cell at 25 °C, a temperature compensation coefficient of −3 mV/°C/cell, a design float life of 20+ years @ 20 °C, capacity measured at more than one discharge rate, and a certification trail that includes IEC 60896-21/22 and IEC 61427. A quotation that cannot be matched to those six items is not a quotation for a defined product, it is a quotation for a cell of unknown provenance.
Five numbers decide most tubular gel evaluations: 2.23 V per cell at 25 °C for float, 2.35 V per cell at 25 °C for equalisation, −3 mV/°C/cell for temperature compensation, 20+ years @ 20 °C for design float life, and 0.56 mΩ for the internal resistance of a 2 V 500 Ah cell measured at 25 °C. Every one of them is published on the manufacturer datasheet. Every one of them should match, line for line, before a purchase order is raised.
Key Takeaways
- A tubular gel order is a specification order, not a catalogue order. The datasheet is the contract, and the quotation is only an offer against it.
- Float voltage of 2.23 V per cell at 25 °C and equalise voltage of 2.35 V per cell at 25 °C are non-negotiable. A supplier quoting a different float voltage is selling a different chemistry.
- Temperature compensation of −3 mV/°C/cell is what makes a 20+ years @ 20 °C float life claim credible in a hot climate. Check that the value is printed, not merely promised.
- A single headline amp-hour figure hides the real deliverable. Ask for the capacity at several discharge rates, because a C10 number and a C100 number differ by 10 to 15 percent on the same cell.
- Verification is cheap before the order and expensive after it. Ask for the capacity curve, the cycle certification and the charge-voltage recipe in writing, then hold the shipment to the same document.
§1 — Quick Specifications Table
The table below is the published rating for the 2 V 500 Ah tubular gel cell, taken from the manufacturer datasheet. Every other figure in this article is either copied from the same document or derived from it by arithmetic, and each derived value is labelled as such.
| Parameter | Value | Source |
|---|
| Model | OPzV2-500, 2 V tubular gel | Datasheet |
| Nominal voltage | 2 V | Datasheet |
| Nominal capacity | 500 Ah at C10 to 1.80 V per cell | Datasheet |
| Dimensions | 166 x 206 x 506 mm | Datasheet |
| Weight | 36.3 kg (80.0 lbs) | Datasheet |
| Float charge voltage | 2.23 V @ 25 °C | Datasheet |
| Equalise charge voltage | 2.35 V @ 25 °C | Datasheet |
| Design float life | 20+ years @ 20 °C | Datasheet |
| Temperature compensation | −3 mV/°C/cell | Datasheet |
| Internal resistance | approx. 0.56 mΩ at 25 °C | Datasheet |
| Max. charge current | 100 A | Datasheet |
| Max. discharge current, 5 s | 2,000 A | Datasheet |
| Short circuit current | 2,600 A | Datasheet |
| Self-discharge | approx. 2 % per month at 20 °C | Datasheet |
| Discharge temperature range | −40 to 65 °C | Datasheet |
| Charge temperature range | −30 to 65 °C | Datasheet |
| Storage temperature range | −25 to 45 °C | Datasheet |
| Terminal | Female copper insert M8, 10 to 12 N·m | Datasheet |
| Standards | IEC 60896-21/22, DIN 40472, IEC 61427, YD/T 1360, BS 6290 part 4, UL 1989, Eurobat | Datasheet |
| 24-cell string weight at 48 V | 24 x 36.3 kg = 871.2 kg | Arithmetic |
| 24-cell string internal resistance | 24 x 0.56 mΩ = 13.44 mΩ | Arithmetic |
| 24-cell string charge capacity | 24 x 100 A = 2,400 A | Arithmetic |
| 24-cell string nominal energy | 24 x 2 V x 500 Ah = 24,000 Wh | Arithmetic |
For solar and wind duty the same datasheet carries a separate parameter set, and this is where most quotations diverge. The float setting rises to 2.27 ± 0.005 V per cell at 25 °C and the regulation and equalise voltage rises to 2.40 ± 0.01 V per cell at 25 °C. The over-voltage disconnect sits at 2.47 ± 0.01 V per cell, the array reconnection voltage at 2.23 ± 0.005 V, the low voltage alarm at 1.95 ± 0.005 V, the low voltage disconnect at 1.90 ± 0.005 V and the load reconnect voltage at 2.09 ± 0.01 V. The temperature compensation coefficient widens to a range of −3 to −5 mV per cell per degree Celsius. A supplier who quotes the telecom float values for a solar installation is telling you they have never configured a controller against these settings.
The OPzV2-500 tubular gel model page carries the same published figures, which is a useful cross-check: a manufacturer whose product page and datasheet disagree has a documentation problem, and a documentation problem becomes a warranty problem.
§2 — The Pain
The pattern is always the same. A buyer asks for a quotation on 2 V gel cells for a 48 V DC bus in Mombasa or Durban, receives three responses inside a day, and finds that only one of them answers the question. The other two quote a cell, a price per unit and a delivery window, and leave the technical content undefined.
That leaves the buyer with a de facto choice between two risks. Accept the undefined quotation and carry the risk of a cell whose float behaviour, temperature compensation and actual capacity are unknown, then discover the shortfall during the first hot season in service. Or spend the next three weeks demanding datasheets, capacity curves and certification documents, and lose the schedule while the shipment sits in a port in Ningbo or Jebel Ali.
The deeper problem is that tubular gel cells look interchangeable on paper. Every 2 V 500 Ah gel cell has the same nominal voltage, roughly the same headline capacity and a terminal that fits the same busbar. The differences that decide service life are printed on page two of the datasheet, in a table of long-term discharge capacity and cycle life, and they are almost never included in a quotation email. A cell with 5,500 cycles at 20 % depth of discharge and one with 3,000 cycles at the same depth are the same object to a purchasing system and completely different objects over a ten year life.
There is a second trap in the quoting process itself. A supplier will often quote the C10 capacity because that is the headline figure on the catalogue page. But a telecom DC plant in Chennai or a solar site in Ho Chi Minh does not run at a ten hour discharge rate. On the same cell, the capacity at C100 is lower and the capacity at C24 is higher, and the manufacturer publishes the whole curve so that the buyer can select on the duty cycle rather than on the label. When a quotation quotes one number with no rate attached, it is not quoting capacity, it is quoting a label.
Third, the certification trail is where most unverifiable suppliers give themselves away. IEC 60896-21/22 and IEC 61427 are not decorations on a datasheet. IEC 60896-21 and 22 cover stationary lead-acid valve regulated batteries and their methods of test, and IEC 61427 covers the cycling test that produces a cycle life figure. DIN 40472, BS 6290 part 4 and UL 1989 sit alongside them, and YD/T 1360 is the Chinese telecom standard for the same class of product. A supplier who lists none of these, or who lists a certificate number that cannot be produced on request, is not qualified to supply a DC plant.
The final voltage table above is the second half of that discipline, and the long-term discharge and cycle life curves on page two of the same datasheet are the third.
§3 — The Choice
Once the datasheet is in front of you, the choice narrows quickly, because the OPzV range is graded by capacity and the differences between grades are published rather than negotiable.
| Model | Voltage | Capacity | Dimensions (mm) | Weight | Internal resistance | Max. charge current | Source |
|---|
| OPzV2-500 | 2 V | 500 Ah | 166 x 206 x 506 | 36.3 kg | 0.56 mΩ at 25 °C | 100 A | Datasheet |
| OPzV2-700 | 2 V | 700 Ah | 254 x 210 x 506 | 51.0 kg | 0.55 mΩ at 25 °C | 140 A | Datasheet |
| OPzV2-1000 | 2 V | 1,000 Ah | 233 x 210 x 681 | 73.2 kg | 0.5 mΩ at 25 °C | 200 A | Datasheet |
| OPzV2-1500 | 2 V | 1,500 Ah | 275 x 210 x 831 | 102 kg | 0.45 mΩ at 25 °C | 300 A | Datasheet |
| OPzV2-2500 | 2 V | 2,500 Ah | 487 x 212 x 807 | 181 kg | 0.3 mΩ at 25 °C | 500 A | Datasheet |
Two features of that table decide a lot in practice. The first is internal resistance. It falls from 0.56 mΩ on the 500 Ah cell to 0.3 mΩ on the 2,500 Ah cell, which means the larger cell delivers a short circuit with less voltage collapse and needs a smaller busbar. The second is mass. A 48 V string of the 500 Ah cell weighs 871.2 kg, while the same busbar built from the 1,500 Ah cell weighs 2,448.0 kg. If the battery room floor was designed around a particular cell height, the cell count changes the answer, and the height does change across the range from 506 mm to 807 mm.
The string arithmetic is worth setting out on paper before the quotation arrives, because it is the part a buyer can check without opening a datasheet.
| Model | 24-cell string weight | String internal resistance | String charge capacity | Nominal energy | Source |
|---|
| OPzV2-500 | 24 x 36.3 kg = 871.2 kg | 24 x 0.56 mΩ = 13.44 mΩ | 24 x 100 A = 2,400 A | 24 x 2 V x 500 Ah = 24,000 Wh | Arithmetic |
| OPzV2-700 | 24 x 51.0 kg = 1,224.0 kg | 24 x 0.55 mΩ = 13.20 mΩ | 24 x 140 A = 3,360 A | 24 x 2 V x 700 Ah = 33,600 Wh | Arithmetic |
| OPzV2-1000 | 24 x 73.2 kg = 1,756.8 kg | 24 x 0.5 mΩ = 12.0 mΩ | 24 x 200 A = 4,800 A | 24 x 2 V x 1,000 Ah = 48,000 Wh | Arithmetic |
| OPzV2-1500 | 24 x 102 kg = 2,448.0 kg | 24 x 0.45 mΩ = 10.8 mΩ | 24 x 300 A = 7,200 A | 24 x 2 V x 1,500 Ah = 72,000 Wh | Arithmetic |
| OPzV2-2500 | 24 x 181 kg = 4,344.0 kg | 24 x 0.3 mΩ = 7.2 mΩ | 24 x 500 A = 12,000 A | 24 x 2 V x 2,500 Ah = 120,000 Wh | Arithmetic |
Capacity is also a function of the discharge rate, and the manufacturer publishes the whole curve so the buyer can select on the duty cycle. The final voltage setting that goes with each rate is fixed rather than negotiable.
| Discharge current | Final voltage per cell | Source |
|---|
| Below 0.05 C | 1.90 V | Datasheet |
| 0.05 C to 0.08 C | 1.85 V | Datasheet |
| 0.08 C to 0.2 C | 1.80 V | Datasheet |
| 0.2 C to 0.6 C | 1.75 V | Datasheet |
| 0.6 C to 1.0 C | 1.70 V | Datasheet |
| 1 C to 2 C | 1.60 V | Datasheet |
A DC plant at a site in Chennai typically runs a backup discharge between 0.2 C and 0.6 C, which means the 1.75 V cutoff applies and the usable capacity sits below the C10 headline. An installation in Karachi running a shallow daily cycle reads the C100 figure instead. Any OPzV battery China quotation that quotes one capacity number without a rate has not been built around either duty cycle.
Cycle life is the third published curve, and it is where the gel construction earns its place next to a flooded cell, because the gel cell can be cycled far more often without losing plate capacity.
| Model | Depth of discharge | Published cycle life | Source |
|---|
| OPzV2-500 | 20 % | approx. 5,500 cycles | Datasheet |
| OPzV2-500 | 40 % | approx. 3,500 cycles | Datasheet |
| OPzV2-500 | 60 % | approx. 2,500 cycles | Datasheet |
| OPzV2-500 | 80 % | approx. 1,800 cycles | Datasheet |
| OPzV2-500 | 100 % | approx. 1,400 cycles | Datasheet |
| OPzV2-700 | 20 % | approx. 5,500 cycles | Datasheet |
| OPzV2-700 | 50 % | approx. 2,400 cycles | Datasheet |
| OPzV2-1000 | 20 % | approx. 5,500 cycles | Datasheet |
| OPzV2-1000 | 40 % | approx. 3,100 cycles | Datasheet |
| OPzV2-1500 | 20 % | approx. 5,700 cycles | Datasheet |
| OPzV2-1500 | 40 % | approx. 3,100 cycles | Datasheet |
| OPzV2-2500 | 20 % | approx. 5,500 cycles | Datasheet |
| OPzV2-2500 | 50 % | approx. 3,000 cycles | Datasheet |
One further point belongs in the comparison, because it is the first question a European or North American buyer asks and the one most often answered with a marketing sentence rather than a number. Tubular gel and tubular flooded are not the same product in a different case. The gel cell measures 166 x 206 x 506 mm and weighs 36.3 kg for 500 Ah, and it loses roughly 2 % of capacity per month at 20 °C in open circuit. A flooded 500 Ah cell of the same nominal capacity measures 104 x 206 x 399 mm, carries 4.5 kg of acid on top of a 13.0 kg dry mass, and loses roughly 4 % per month. The gel cell is taller, heavier and needs no watering, and it operates from −40 to 65 °C on discharge against −25 to 65 °C for the flooded cell. Those are published differences on two datasheets, and they are the reason a site in Port Said or Santos and a site in Warsaw do not buy the same cell.
§4 — The Framework
Seven criteria will settle a tubular gel sourcing decision faster than any price comparison, and all seven can be answered from documents rather than from a sales conversation.
1. The charge recipe, printed on the datasheet. Float at 2.23 V per cell at 25 °C, equalise at 2.35 V per cell at 25 °C, compensation at −3 mV/°C/cell, and a design float life of 20+ years @ 20 °C. If any one of these is absent, the cell is not qualified for a DC plant and the 20 year claim is not supported.
2. Capacity at the duty rate. Demand the long-term discharge table and select on the rate that matches your site, not the C10 label. Ask which final voltage is used at each rate and expect the table of final voltages to be consistent with it.
3. Internal resistance and short circuit current. These determine the busbar cross-section, the fuse rating and the protection coordination. A 2 V 500 Ah cell publishes 0.56 mΩ at 25 °C, 100 A of maximum charge current, 2,000 A at five seconds and 2,600 A of short circuit current. Nothing about those four numbers may be left to a catalogue.
4. The certification trail. IEC 60896-21/22 for the cell and the valve-regulated construction, IEC 61427 for the cycling test behind the cycle life figure, DIN 40472, BS 6290 part 4, UL 1989, YD/T 1360 for Chinese telecom installations and Eurobat for the long life classification. Ask for the certificate numbers, not for the words.
5. Ambient and self-discharge against the site. Confirm the discharge, charge and storage ranges cover your worst month, not your average month. For a DC plant in Apapa or Tema the storage range of −25 to 45 °C is the relevant constraint during a shipping delay, and self-discharge decides how much standby loss the site accepts in the weeks before load is connected.
6. Physical fit. Check the cell dimensions against the rack, the battery room door and the handling equipment at the port of discharge. The shells in this range are not interchangeable, and they are not a single platform, so a drawing taken from a different model is not a substitute for the dimension line on the datasheet.
7. The documentation that must travel with the shipment. Test certificates, the capacity curve at the specified rates, the charge-voltage recipe, the warranty terms and the failure-analysis route. This is the set that converts a quotation into a specification, and it is also the set that settles a claim three years later. A supplier that cannot produce it on request has already told you how the claim will be handled.
§5 — The Trust
The market for 2 V tubular gel from China is not a scam market, and the reputable factories in Ningbo, Shenzhen and Shanghai are not hiding anything. But the quoting process rewards vagueness, and vagueness is the actual risk.
The float voltage that drifts. Ask three suppliers for the float voltage and you will commonly receive 2.23 V, a value a hundredth of a volt higher, and a figure expressed as a range. Only the first is correct for this product range. A float voltage a hundredth of a volt above the rating is about 2.4 volts across a 24-cell string, which is enough to hold the cell in equalisation for a large part of every day and therefore enough to shorten plate life materially over a decade. This is not a rounding difference that can be corrected in the controller, because the controller will be set once and left alone.
The capacity that is quoted at the wrong rate. C10 is the catalogue number and it is the easiest number to copy. Ask for the capacity at the rate your site will actually discharge at, and for the final voltage that goes with it.
The certification that cannot be produced. Certificate references are cheap to include in an email. Ask for the issuing document and for the test report behind the cycle life figure. The IEC 61427 cycling test is what turns a cycle life claim into a measured number.
The warranty that excludes the case it was sold for. Read the exclusion list. Exclusions for physical damage, for operation outside the published charge voltage window and for cells operated without temperature compensation are standard in the industry, and all three will apply if the site settings are wrong.
The cell that arrives out of tolerance. A delivered batch should arrive with a voltage spread within the manufacturer’s tolerance and intact terminals. At a receiving point in Santos, Manzanillo or Gdansk, measure before the pallet is broken down and record it, because the receiving record is the evidence that supports a later claim.
The most useful single test is a capacity challenge. Ask the supplier to state, in writing, the capacity they will guarantee at a stated discharge rate, a stated final voltage and a stated temperature, and to accept that figure into the warranty. A supplier who answers will also give you the datasheet you needed in the first place. A supplier who declines has told you the head number on the catalogue page is the only figure they will stand behind.
For scale, the 1,000 Ah tubular gel cell in the same OPzV range publishes 0.5 mΩ at 25 °C, 200 A of maximum charge current and a 48,000 Wh 24-cell string, documented to the same standard as the 500 Ah cell. Consistency of documentation across a range is itself evidence of a controlled factory.
§6 — FAQ
Q1. What is the minimum a supplier must publish before I place a tubular gel order? Six items: float charge voltage of 2.23 V per cell at 25 °C, equalise charge voltage of 2.35 V per cell at 25 °C, temperature compensation of −3 mV/°C/cell, a design float life of 20+ years @ 20 °C, capacity stated at more than one discharge rate with the final voltage for each rate, and a certification trail that includes IEC 60896-21/22 and IEC 61427. If a quotation is missing any of them, it is not yet a quotation for a defined product.
Q2. Why does a gel cell cost more than a flooded cell of the same capacity? Because the construction is different and the manufacturing steps are different. The gel cell at 500 Ah measures 166 x 206 x 506 mm and weighs 36.3 kg, while a flooded 500 Ah cell measures 104 x 206 x 399 mm with a 13.0 kg dry mass plus 4.5 kg of acid. The gel cell contains no free liquid electrolyte, needs no watering on site, loses about 2 % of capacity per month at 20 °C against 4 % for flooded, and operates on discharge from −40 to 65 °C against −25 to 65 °C. Those differences are the reason for the price and the reason the cell suits sites with no maintenance access.
Q3. Does the float life of 20+ years @ 20 °C apply to my site? It applies at 20 °C, which is the reference temperature on the datasheet. The float life curve on the same page shows approximately 10 years at 30 °C. If the annual average at your site is 30 °C or above, the design figure should be read from the 30 °C curve instead. In a container port such as Rotterdam or Gdansk the average may be close to the reference; in a hot installation at Port Said or Chennai it will not be.
Q4. How many cells do I need for a 48 V bus, and what does that weigh? Twenty-four cells. At 500 Ah each, 24 x 36.3 kg = 871.2 kg, 24 x 0.56 mΩ = 13.44 mΩ of string resistance and 24 x 100 A = 2,400 A of maximum charge current, with 24 x 2 V x 500 Ah = 24,000 Wh of nominal energy. At 1,000 Ah each the same bus weighs 1,756.8 kg and delivers 48,000 Wh.
Q5. Which charge settings do I programme into the controller for a solar site? The solar and wind parameter set on the datasheet, not the telecom float set. Float at 2.27 ± 0.005 V per cell at 25 °C, regulation and equalise at 2.40 ± 0.01 V, over-voltage disconnect at 2.47 ± 0.01 V, array reconnection at 2.23 ± 0.005 V, low voltage alarm at 1.95 ± 0.005 V, low voltage disconnect at 1.90 ± 0.005 V and load reconnect at 2.09 ± 0.01 V, with compensation widened to a range of −3 to −5 mV per cell per degree Celsius. The charge condition is constant charge at 0.15 CA up to 2.40 V at 20 °C.
Q6. What does cycle life mean when the same cell also has a 20+ year float life? They describe two different duties. Float life is calendar life on a continuous float charge with shallow cycling, and it is roughly 20 years at 20 °C. Cycle life counts full charge and discharge cycles at a stated depth of discharge, and on the 500 Ah cell it runs from approximately 5,500 cycles at 20 % depth of discharge down to approximately 1,400 cycles at 100 %. A site that cycles daily should size against the cycle curve; a site on float standby should size against the float curve.
Q7. Should I accept a lower price from a supplier that will not provide the test documents? No. The reduction you gain applies to a cell whose actual capacity, actual charge behaviour and actual cycle life are unknown, and the cost of that uncertainty falls on you at the first hot season and at the first warranty claim. The documents take hours to provide and cost the supplier almost nothing, so a refusal to provide them is information about how the claim will be handled later.
Q8. How do I check a delivered batch? Measure the open circuit voltage of every cell and compare the spread across the batch against the manufacturer’s tolerance, inspect the terminals for damage, confirm the cell count and the model designation against the order, and for flooded cells confirm the electrolyte level. Record the results at the point of unloading, whether that is Santos, Durban, Nhava Sheva or Chattogram, because the receiving record is the evidence that supports a later claim.
Expert Summary
A tubular gel sourcing decision from an OPzV battery China supplier should be made against published data, not against a price per unit, and the published data is short enough to hold in your head. Float charge voltage 2.23 V per cell at 25 °C. Equalise charge voltage 2.35 V per cell at 25 °C. Temperature compensation −3 mV/°C/cell. Design float life 20+ years @ 20 °C, which becomes roughly 10 years at 30 °C on the published curve. Capacity published at several discharge rates, each with its own final voltage, from 1.90 V per cell below 0.05 C down to 1.60 V per cell between 1 C and 2 C. Cycle life published against depth of discharge, from approximately 5,500 cycles at 20 % down to approximately 1,400 cycles at 100 % on the 500 Ah cell. Internal resistance published per model and per reference temperature, from 0.56 mΩ at 25 °C on the 500 Ah cell down to 0.3 mΩ on the 2,500 Ah cell. A certification trail naming IEC 60896-21/22, DIN 40472, IEC 61427, YD/T 1360, BS 6290 part 4, UL 1989 and Eurobat, with the test reports available on request. String arithmetic that you can check without a datasheet, such as 24 x 36.3 kg = 871.2 kg and 24 x 100 A = 2,400 A for a 48 V bus built from 500 Ah cells. And a solar-specific charge recipe that differs from the telecom float settings, with float at 2.27 ± 0.005 V, regulation at 2.40 ± 0.01 V and compensation between −3 and −5 mV per cell per degree Celsius. A supplier who publishes all of that, on one document, from one factory, is a supplier whose warranty will mean something. A supplier who publishes one capacity number and a delivery window is selling you an object, not a specification.
Contact CHISEN — 24-Hour Response
Send us the duty cycle, the bus voltage, the string configuration, the ambient temperature at the site and the discharge profile, and you will receive a sizing sheet with the cell grade, the string arithmetic and the charge settings calculated for your installation, within 24 hours.
- Sales: sales@chisen.cn
- General enquiries: jack@chisen.cn
- WhatsApp: +86 131 6622 6999
- Product reference: OPzV2-500 tubular gel, 2 V 500 Ah
Related reading: the OPzV tubular gel battery range.
Related CHISEN Buyer Guides