6-EVF-120 12V120Ah Solar and Off-Grid Energy Storage Battery

BatteryMaintenanceOrReplacementOldBattery

Answer First

The 6-EVF-120 is a 12 V, 120 Ah sealed VRLA battery rated at the C3 rate, and the numbers a solar or off-grid installer needs are published on the factory model page: 407×170×240 mm case, 40 ± 0.2 kg, terminals type φ20-M8, float 13.5 V, equalise 14.1 V, maximum charge current 24.0 A, cutoff 1.75 V/cell, self-discharge ≤3 %/month at 25 °C, working range −15…50 °C, cycle life 350–600 cycles and design life 2–5 years. Nothing here is inferred — every derived figure below is arithmetic on those printed values.

One block stores 12 V × 120 Ah = 1,440 Wh nominal, and 720 Wh usable at the 50 % depth of discharge the cycle-life figure is quoted at; two blocks in series give a 24 V bank of 2,880 Wh nominal. Full drawings and terminal layouts are on this model page. CHISEN ships this 12 V VRLA line to distributors in India, Nigeria, Kenya, Vietnam, the Philippines and Brazil, exported from China through Ningbo, Shanghai and Jebel Ali, with Mumbai, Lagos, Mombasa, Dubai, Durban and Port Said routing.

Key Takeaways

  • Published, not estimated: the 6-EVF-120 is 12 V, 120 Ah at C3, 407×170×240 mm, 40 ± 0.2 kg, with float 13.5 V and equalise 14.1 V taken straight from the model page.
  • Energy per block is 1,440 Wh: 12 V × 120 Ah = 1,440 Wh nominal, or 720 Wh usable at 50 % depth of discharge.
  • Charge current is capped at 24.0 A, exactly 20 % of nameplate: 24.0 A ÷ 120 Ah = 0.2 C.
  • Equalise 14.1 V equals 2.35 V/cell across the six cells of the string; float 13.5 V equals 2.25 V/cell; cutoff 1.75 V/cell × 6 cells = 10.5 V end of discharge.
  • Weight is the logistics number: a two-block 24 V bank is 80 ± 0.4 kg of battery and a four-block bank is 160 ± 0.8 kg, so shelf loading and handling must be checked before the pallet is opened.

§1 — 6-EVF-120 Quick Specifications

Every line below is reproduced from the published specification sheet for the 6-EVF-120. The source column states where each value comes from: printed on the factory model page, or arithmetic performed on printed values and shown in the text that follows.

ParameterValueSource
Nominal voltage12 VModel page
Rated capacity120 Ah at C3Model page
Dimensions (L×W×H)407×170×240 mmModel page
Weight40 ± 0.2 kgModel page
Terminalφ20-M8Model page
Float voltage13.5 VModel page
Equalise voltage14.1 VModel page
Cycle life350–600 cyclesModel page
Maximum charge current24.0 AModel page
Cut-off voltage1.75 V/cellModel page
Self-discharge≤3 %/month at 25 °CModel page
Working temperature−15…50 °CModel page
Design life2–5 yearsModel page
Cells per 12 V string6Arithmetic
Nominal energy per block1,440 WhArithmetic

§2 — The Pain: Off-Grid Banks That Fail on Paper and in Service

Most off-grid projects do not fail because the battery is bad. They fail because the bank was specified from a nameplate number and then operated outside the window the manufacturer publishes. The 6-EVF-120 sheet makes that easy to diagnose, because capacity is 120 Ah at C3, and cycle life is 350–600 cycles at 50–80 % depth of discharge. Treat 120 Ah as a wall of charge and draw 60 A for two hours, and the block is being asked for 60 A ÷ 120 Ah = 0.5 C — twice its rated rate — while the pack is simultaneously being used as if it were a 60 Ah block. Both mistakes shorten service life.

The second pain is charge acceptance. The published maximum charge current for the 6-EVF-120 is 24.0 A, which is 20 % of the 120 Ah rating. A controller that delivers 30 A into a 24 V bank of two blocks is overdriving cells whose limit is 24.0 A per 12 V block; the ceiling for that bank is 24.0 A × 2 blocks = 48.0 A total string current.

§3 — The Choice: Sizing the 6-EVF-120 Against a Real Load Profile

The disciplined way to choose this model is to start from daily energy demand and work backwards to a bank, then verify the result against the published limits.

Step 1 — Daily energy. A rural telecom or small solar household running a 300 W evening load for five hours draws 300 W × 5 h = 1,500 Wh/day. Add 20 % for inverter losses and seasonal variation: 1,500 Wh × 1.2 = 1,800 Wh/day.

Step 2 — Usable energy per block. The published capacity is 120 Ah at C3 with cycle life quoted at 50–80 % depth of discharge, so design at the conservative 50 % end: 120 Ah × 0.50 = 60 Ah usable, and 12 V × 60 Ah = 720 Wh usable per block.

Step 3 — Blocks for autonomy. For a two-day autonomy target: 1,800 Wh/day × 2 days = 3,600 Wh required, and 3,600 Wh ÷ 720 Wh per block = 5 blocks. Adding a 10 % spare for stragglers and end-of-life tolerance gives 5 × 1.1 = 5.5, rounded up to 6 blocks. In a 24 V topology that is 6 ÷ 2 = 3 strings of 2 blocks in series, giving 6 × 720 Wh = 4,320 Wh usable and 6 × 1,440 Wh = 8,640 Wh nominal.

Step 4 — Check charge and discharge. Three parallel strings must be able to absorb the array current: 24.0 A maximum per 12 V block × 6 blocks = 144 A maximum total bank charge current at 24 V, with each parallel path held under 24.0 A.

§4 — The Framework: Commissioning, Monitoring and Maintenance the Published Numbers Allow

Commissioning a 6-EVF-120 bank means measuring what the sheet says the battery should be doing. Float voltage: a fully charged 12 V block should read 13.5 V at rest, which is 2.25 V/cell across the six cells. Equalise voltage: during absorption the charger should reach 14.1 V, which is 2.35 V/cell; sustained equalising at that level is what drives the block to full charge, and the failure mode to watch is a controller that never reaches it, because a bank that only ever floats at 13.5 V drifts toward the shallow end of the published cycle life.

A monitoring routine that respects the published data is simple. Monthly float check: read and log the block voltage at float; with self-discharge at ≤3 %/month at 25 °C, a monthly correction is sufficient. Annual terminal check: the φ20-M8 specification fixes the hardware, and loose terminals are the most common cause of the voltage imbalance that shortens service life. Temperature log: within the published −15…50 °C range the block behaves to specification; above 50 °C the 2–5 year design life no longer applies.

§5 — Where the 6-EVF-120 Sits Against the Published 12 V VRLA Line

The table below lists published values for the 6-EVF-120 and for six neighbouring 12 V models on the same factory model pages. Every cell is a printed value, not an estimate.

ModelVCapacityRateL×W×H mmWeightTerminalFloatEqualiseCharge currentCutoffDesign lifeSource
6-EVF-12012120 AhC3407×170×24040 ± 0.2 kgφ20-M813.5 V14.1 V24.0 A1.75 V/cell2–5 yearsModel page
6-EVF-501250 AhC3230×140×18015.25 ± 0.2 kgφ11.8-M613.5 V14.1 V10.0 A1.75 V/cell2–5 yearsModel page
6-EVF-801280 AhC3259×170×21825.7 ± 0.2 kgφ16-M613.5 V14.1 V16.0 A1.75 V/cell2–5 yearsModel page
6-EVF-10012100 AhC3330×170×21831.5 ± 0.2 kgφ20-M813.5 V14.1 V20.0 A1.75 V/cell2–5 yearsModel page
6-EVF-15012150 AhC3483×170×24048.5 ± 0.2 kgφ20-M813.5 V14.1 V30.0 A1.75 V/cell2–5 yearsModel page
6-DMF-451245 AhC3224×121×17512.3 ± 0.2 kgφ11.8-M513.5 V14.1 V9.0 A1.75 V/cell2–5 yearsModel page

The smaller 6-DMF and 6-DZF sizes share the same electrical regime — float 13.5 V, equalise 14.1 V, cutoff 1.75 V/cell, self-discharge ≤3 %/month at 25 °C, working range −15…50 °C — and differ only in terminal hardware and case size, from φ8.0-M5 on the 12 Ah 6-DZF-12 up to φ20-M8 on the 6-EVF-120 and 6-EVF-150. The full product range lists every size with its drawing and terminal layout.

§6 — The Trust: Factory Evidence Behind Every Figure Quoted Above

Every specification in this article comes from the published model page for the 6-EVF-120, and the factory behind that sheet runs on eight production bases with an annual capacity of 70 million kVAh. Certifications for export documentation and tender submissions are CE, ISO 9001, ISO 14001, UL and IEC.

For a site that needs one small controller bank beside the main storage strings, the sibling model page covers the 50 Ah member of this series on the identical electrical regime. CHISEN ships the 6-EVF-120 to importers, distributors, OEM programme buyers and EPC integrators in India, Nigeria, Kenya, Vietnam, the Philippines, Brazil, Egypt, the UAE, Turkey and South Africa, consolidated from Ningbo, Shanghai, Shenzhen, Guangzhou and Xiamen and routed through Mumbai, Lagos, Mombasa, Durban, Cairo, Port Said, Jakarta, Manila, Bangkok, Singapore, Dubai, Hamburg, Antwerp, Valencia, Santos, Callao and Colombo.

§7 — FAQ

Q1: What are the published nominal voltage and capacity of the 6-EVF-120? 12 V and 120 Ah at the C3 rate (Model page). Nominal energy is 12 V × 120 Ah = 1,440 Wh per block (Arithmetic).

Q2: What float and equalise setpoints does the manufacturer publish for the 6-EVF-120? Float 13.5 V and equalise 14.1 V per 12 V block (Model page), which is 2.25 V/cell and 2.35 V/cell across the six cells (Arithmetic).

Q3: What is the maximum charging current for the 6-EVF-120? 24.0 A per 12 V block (Model page) — exactly 20 % of the 120 Ah rating. A two-block 24 V bank therefore accepts 24.0 A × 2 = 48.0 A total.

Q4: What are the case dimensions and weight of the 6-EVF-120? 407×170×240 mm and 40 ± 0.2 kg (Model page). A two-block 24 V bank is 80 ± 0.4 kg of battery.

Q5: How many cells does a 12V120Ah string contain and what bus voltage does it give? Six cells — 12 V ÷ 2 V nominal per cell = 6 (Arithmetic). The string floats at 13.5 V, equalises at 14.1 V and reaches end of discharge at 6 × 1.75 V = 10.5 V.

Q6: What is the published design float life of the 6-EVF-120 and at what temperature? Design life is 2–5 years and the working range is −15…50 °C (Model page). Self-discharge is ≤3 %/month measured at 25 °C.

Q7: How should an importer verify the 6-EVF-120 on delivery? Measure each block at float (13.5 V expected, Model page), inspect the case and the φ20-M8 terminal, then run a C3 capacity test to the 1.75 V/cell cutoff. The export desk supplies the test protocol and shipping documents with the consignment.

Q8: How do I request a quotation or samples for the 6-EVF-120? Send the block quantity, terminal and packaging specification and the destination port to sales@chisen.cn, or to jack@chisen.cn. WhatsApp +86 131 6622 6999 reaches the export desk directly.

Expert Summary

The 6-EVF-120 is a 12 V, 120 Ah at C3 sealed VRLA battery whose published sheet is complete enough to design an entire solar or off-grid bank from: 407×170×240 mm, 40 ± 0.2 kg, φ20-M8 terminals, float 13.5 V, equalise 14.1 V, maximum charge current 24.0 A, cutoff 1.75 V/cell, self-discharge ≤3 %/month at 25 °C, −15…50 °C, cycle life 350–600 at 50–80 % depth of discharge and design life 2–5 years. Every derived figure is arithmetic on those printed values: 1,440 Wh nominal per block, 720 Wh usable at 50 % depth of discharge, 10.5 V end of discharge across six cells, 40 A continuous at the C3 rate, and a 24 V two-block bank accepting 48.0 A of charge current. Behind those figures sits a factory group of eight production bases and 70 million kVAh a year, certified to CE, ISO 9001, ISO 14001, UL and IEC, supplying importers, distributors, OEM programme buyers and EPC integrators from China to India, Nigeria, Kenya, Vietnam, the Philippines, Brazil, Egypt, the UAE, Turkey and South Africa. The model page is the starting document for the drawing, the terminal layout and the test protocol, and the export desk replies within 24 hours.

Contact CHISEN — 24-Hour Response

  • Email: sales@chisen.cn (general enquiries) | jack@chisen.cn (export desk)
  • WhatsApp: +86 131 6622 6999
  • Website: www.chisen.cn
  • Headquarters: CHISEN Battery, Hangzhou, China — 8 production bases, 70 million kVAh annual capacity, certified to CE, ISO 9001, ISO 14001, UL and IEC.

Quotations for the 6-EVF-120, technical sheets, samples and shipment documentation are answered within 24 hours by the export desk.