6-EVF-60 12V60Ah Solar and Off-Grid Energy Storage Battery

BatteryMaintenanceOrReplacementOldBattery

Answer First

The 6-EVF-60 12V60Ah is the 12 V VRLA model CHISEN publishes for solar and off-grid storage duty. Every figure in this article comes from the published model page rather than from an estimate: nominal 12 V / 60 Ah at the C3 rate, case 258×170×160 mm, weight 18.8 ± 0.2 kg, φ14-M6 terminals, float 13.5 V, equalise 14.1 V, maximum charge current 12.0 A, cutoff 1.75 V/cell, self-discharge ≤3 %/month @25 °C, working range −15…50 °C, published design life 2–5 years.

For arithmetic, one 12 V string is six series cells (12 V ÷ 2 V per cell = 6 cells), so a single string carries 12 V × 60 Ah = 720 Wh nominal, and 720 Wh ÷ 18.8 kg = 38.3 Wh/kg of stored energy before any inverter loss. The same string floats at 6 × 2.25 V = 13.5 V, equalises at 6 × 2.35 V = 14.1 V, and reaches its cutoff at 6 × 1.75 V = 10.5 V. That is the working envelope a project engineer sets the charge controller to.

CHISEN ships these cells from its eight production bases with an annual capacity of 70 million kVAh, and the units reach distributors in India, Nigeria, Kenya, Vietnam, Brazil, Egypt and Pakistan, with main port departures from Ningbo and Shanghai and forwarding through Shenzhen, Xiamen and Hong Kong. Full case data for the model sits on this model page.

Key Takeaways

  • 6-EVF-60 12V60Ah is a 12 V 60 Ah AGM cell at the C3 rate, with published dimensions of 258×170×160 mm and 18.8 ± 0.2 kg, so shelf and cabinet planning can be done before the order is placed.
  • Float 13.5 V and equalise 14.1 V (2.25 V and 2.35 V per cell across six cells) are published setpoints, not controller defaults to guess at.
  • Maximum charge current is 12.0 A per string, which is 60 Ah × 0.20 C10 — size the MPPT charge controller against that ceiling.
  • Cutoff 1.75 V/cell gives a 10.5 V string cutoff and defines the usable energy window for daily cycle planning.
  • Published design life is 2–5 years at a 50–80 % depth of discharge, and self-discharge is ≤3 %/month @25 °C, which sets the idle-storage loss during monsoon or winter periods.
  • Charge acceptance, not nominal capacity, limits off-grid runtime — plan the array around the 12.0 A ceiling and size the solar collector from the daily load.

§1 — 6-EVF-60 Quick Specifications

The table below reproduces the published data for the 6-EVF-60 without adjustment. The source column names the origin of every line so that a specification check during incoming inspection can be traced back to a printed source rather than to a catalogue summary.

ParameterPublished valueSource
Nominal voltage12 VModel page
Nominal capacity60 AhModel page
RateC3Model page
Dimensions L×W×H258×170×160 mmModel page
Weight18.8 ± 0.2 kgModel page
Terminalφ14-M6Model page
Float voltage13.5 VModel page
Equalise voltage14.1 VModel page
Cycle life350–600 cycles (DoD 50–80 %)Model page
Maximum charge current12.0 AModel page
Cutoff voltage1.75 V/cellModel page
Self-discharge≤3 %/month @25 °CModel page
Working temperature−15…50 °CModel page
Design life2–5 yearsModel page
Cell count per 12 V string6 cells (12 V ÷ 2 V per cell)Arithmetic
String nominal energy720 Wh (12 V × 60 Ah)Arithmetic
Energy-to-weight ratio38.3 Wh/kg (720 Wh ÷ 18.8 kg)Arithmetic
String cutoff voltage10.5 V (6 cells × 1.75 V)Arithmetic

§2 — The Pain: Nominal Capacity Is Not Usable Energy Off the Grid

Solar and off-grid buyers lose money in one specific way: they buy on the label Ah figure and then discover, in the second summer, that the bank cannot carry the load through three cloudy days. The 60 Ah printed on the 6-EVF-60 case is a C3 laboratory value measured at 25 °C on a controlled discharge. A field installation discharges the same energy over 8 to 20 hours, at temperatures that swing with the container, and with the losses of a charge controller and an inverter in the path.

Three consequences follow from that gap, and each one has to be engineered rather than assumed.

First, the nominal number overstates usable energy. A conservative planning rule for this model takes the 720 Wh nominal per string at 50 % depth of discharge, which is 720 Wh × 0.50 = 360 Wh of deliverable energy per string per cycle. A second rule of thumb is to apply the published 90 % inverter efficiency on top, so the usable figure at the load becomes 360 Wh × 0.90 = 324 Wh.

Second, the charge path is the real bottleneck on an off-grid site. The published maximum charge current for this model is 12.0 A. If a site draws 300 W continuously, the array must be recharged every day, and the recharge energy at the battery terminals has to arrive at no more than 12.0 A × 13.5 V = 162 W per string. One string therefore cannot restore a 300 W load while also supplying it — two strings in parallel can, at 24.0 A and 324 W, and that is the ceiling of the published charge window.

Third, idle loss compounds the problem in hot climates. At the published self-discharge of ≤3 %/month @25 °C, a string left in storage loses roughly 720 Wh × 0.03 = 21.6 Wh in 30 days at 25 °C, and the rate rises as the temperature climbs past that reference point.

None of this makes the 6-EVF-60 12V60Ah unsuitable for solar duty. It makes the duty cycle the thing that has to be specified. The published cutoff of 1.75 V/cell and the published 350–600 cycle range at 50–80 % depth of discharge define the window the cell was designed for; matching the load curve to that window is the whole job.

§3 — The Choice: Sizing a String Against a Real Load Curve

Start from the load, not from the cell. Write down the daily energy in watt-hours from the site survey — a typical rural telecom or small commercial installation in Nigeria, Kenya or Pakistan runs between 300 Wh and 1,200 Wh per day — then convert that into strings with the 720 Wh nominal figure: strings = daily Wh ÷ 720 Wh, then add the autonomy reserve that the local weather pattern requires.

For a 300 W night-time load with three usable hours, the arithmetic reads: 300 W × 3 h = 900 Wh at the load, ÷ 0.90 inverter efficiency = 1,000 Wh at the battery, ÷ 360 Wh usable per string = 2.8 strings, so three strings in parallel. Each string then has to accept its share of the recharge, and three strings give a combined maximum charge current of 3 × 12.0 A = 36.0 A, which is the number the charge controller has to be rated against.

The solar collector follows from the same sheet. For 720 Wh per string per day with five peak sun hours and a 50 % system loss factor, the collector works out at 720 Wh ÷ (5 h × 0.50) = 288 Wp per string, so a 300 Wp module set is the practical match for one 6-EVF-60 12V60Ah string.

Load scenarioEnergy at loadStrings neededCharge window requiredCollector per string
50 W continuous50 W × 8 h = 400 Wh400 ÷ 360 = 1.2 → 2 strings2 × 12.0 A = 24.0 A720 Wh ÷ (5 h × 0.50) = 288 Wp
100 W evening only100 W × 4 h = 400 Wh400 ÷ 360 = 1.2 → 2 strings2 × 12.0 A = 24.0 A288 Wp
300 W night load300 W × 3 h = 900 Wh900 ÷ 324 = 2.8 → 3 strings3 × 12.0 A = 36.0 A288 Wp
300 W plus 3 cloudy days900 Wh × 4 = 3,600 Wh3,600 ÷ 360 = 10 → 10 strings10 × 12.0 A = 120.0 A288 Wp
the sibling model pagethe full product range

§4 — The Framework: Setpoints, Charge Control and Commissioning

A 12 V AGM string on a solar site has four moving parts, and each of them has a published number behind it.

Float. The published float voltage is 13.5 V for the string, which is 2.25 V per cell across six cells. Float is the resting voltage the string returns to once the harvest is finished, and it is the value that determines daily self-discharge losses and calendar life.

Equalise. The published equalise voltage is 14.1 V, or 2.35 V per cell. Equalise is a periodic top-up step, and it must be scheduled in coordination with the PV harvest — equalising in the evening when there is no charging current available will only raise the water loss without adding charge.

Charge current ceiling. Maximum charge current is 12.0 A, and that is the single most useful number for the installer: it sizes the controller, it sets the parallel string count, and it is the limit the manufacturer publishes for long-term battery life.

Cutoff. At 1.75 V per cell the string reaches 10.5 V, and that is where the load must be shed. Cutting deeper protects the cells and shortens cycle life; cutting shallow wastes stored energy and forces the controller to curtail harvest.

Commissioning follows the same order every time: confirm the controller is programmed to 13.5 V float and 14.1 V equalise for a six-cell string; confirm the current limit is set at or below 12.0 A per string; confirm the low-voltage disconnect at 10.5 V; measure the open-circuit voltage of each new string before the first discharge — a healthy new 6-EVF-60 12V60Ah string measures close to 12.6–12.8 V open circuit at 25 °C, and a spread beyond 0.2 V across the string indicates a connection or cell problem to resolve before the site goes live; then log the first full charge current and confirm the controller settles into absorption without tripping the ceiling.

Temperature compensation is the fourth setting worth confirming, because the published working range of −15…50 °C is a range of tolerance and not a licence to charge without compensation. Below freezing, the published charge current should be reduced; above 40 °C, the float setpoint should be trimmed. The published cycle life of 350–600 cycles at 50–80 % depth of discharge assumes that discipline.

§5 — Sibling Models in the 12 V VRLA Line

The comparison below uses published values only. Charge current, cutoff, float and equalise are identical across this 12 V line, so the decision between models is a decision about capacity, footprint, weight and current headroom.

ModelVCapacityRateL×W×H mmWeightTerminalFloatEqualiseCharge currentCutoffDesign life
6-DZF-121212 AhC2151×99×993.6 ± 0.2 kgφ8.0-M513.5 V14.1 V2.4 A1.75 V/cell2–5 years
6-DZF-201220 AhC2180×76×1706.1 ± 0.2 kgφ8.8-M513.5 V14.1 V4.0 A1.75 V/cell2–5 years
6-DMF-381238 AhC3224×106×17510.45 ± 0.2 kgφ9.8-M513.5 V14.1 V7.6 A1.75 V/cell—
6-DMF-451245 AhC3224×121×17512.3 ± 0.2 kgφ11.8-M513.5 V14.1 V9.0 A1.75 V/cell2–5 years
6-DMF-521252 AhC3224×135×17513.7 ± 0.2 kgφ11.8-M613.5 V14.1 V10.4 A1.75 V/cell—
6-EVF-501250 AhC3230×140×18015.25 ± 0.2 kgφ11.8-M613.5 V14.1 V10.0 A1.75 V/cell2–5 years
6-EVF-601260 AhC3258×170×16018.8 ± 0.2 kgφ14-M613.5 V14.1 V12.0 A1.75 V/cell2–5 years
6-EVF-801280 AhC3259×170×21825.7 ± 0.2 kgφ16-M613.5 V14.1 V16.0 A1.75 V/cell2–5 years
6-EVF-10012100 AhC3330×170×21831.5 ± 0.2 kgφ20-M813.5 V14.1 V20.0 A1.75 V/cell2–5 years
6-EVF-12012120 AhC3407×170×24040 ± 0.2 kgφ20-M813.5 V14.1 V24.0 A1.75 V/cell2–5 years
6-EVF-15012150 AhC3483×170×24048.5 ± 0.2 kgφ20-M813.5 V14.1 V30.0 A1.75 V/cell2–5 years

For the exact dimensions of the model this article covers, the published 258×170×160 mm case and 18.8 ± 0.2 kg weight are confirmed in the specification table in §1 above, and the same data can be checked against the published model page linked earlier in this article.

§6 — The Trust: Factory Capability, Certification and Delivery Verification

CHISEN operates 8 production bases with an annual capacity of 70 million kVAh and manufactures three families under one roof: flooded tubular OPzS2, gel tubular OPzV2, and the 12 V VRLA line that carries the 6-DZF, 6-DMF and 6-EVF models. The 6-EVF-60 12V60Ah is built in that 12 V VRLA line. The factory holds CE, ISO 9001, ISO 14001, UL and IEC certification, and the export desk sits in Hangzhou, China.

For an importer, the practical trust test happens on arrival, not in the brochure. A short incoming-inspection protocol covers the points that actually fail in transit or in long storage: check the case for cracks, bulges or leakage at the terminal boss; confirm the terminal type matches the published φ14-M6 and the polarity marking is legible; measure the open-circuit voltage of each string, which for a new string should read close to 12.6–12.8 V at 25 °C and should not spread beyond 0.2 V across the string; confirm the label shows 12 V / 60 Ah, the float and equalise values of 13.5 V and 14.1 V, and the shipping date; and check the print code and packing list against the purchase order before the container is broken.

Logistics are part of the same trust picture. Units leave the factory through Ningbo and Shanghai, with Shenzhen, Xiamen, Guangzhou, Wuhan and Chongqing available for onward consolidation, and they reach distributors in India, Nigeria, Kenya, Vietnam, the Philippines, Brazil, Egypt, Mexico, Indonesia, Pakistan, Bangladesh, the UAE, Saudi Arabia, Turkey, South Africa, Ghana, Senegal, Angola, Zambia, Tanzania, Morocco, Poland, Germany, Spain, Italy, Australia, Thailand, Malaysia and Singapore. Typical forwarder pairings include Jebel Ali and Dubai for Gulf destinations, Karachi and Mumbai for Pakistan and India, Chennai for South India, Mombasa and Durban for East and Southern Africa, Lagos for West Africa, Cairo and Port Said for Egypt, Santos and Callao for Latin America, and Hamburg, Rotterdam, Antwerp and Valencia for Europe.

The practical point is that a written setpoint sheet, a declared test method and a matching label on the pallet are what turn a battery order into a repeatable product. That is why every figure in this article is sourced from the published model page rather than from a general description of the 12 V VRLA range.

§7 — FAQ

Q1: What are the published nominal voltage and capacity of the 6-EVF-60? The published figures are 12 V and 60 Ah, rated at the C3 rate (Model page). Six series cells give the 12 V string, so each cell carries 60 Ah at a 12 V terminal — 720 Wh per string, calculated as 12 V × 60 Ah.

Q2: What float and equalise setpoints does the manufacturer publish for the 6-EVF-60? Float 13.5 V and equalise 14.1 V for the complete string (Model page). Across the six cells that is 2.25 V per cell at float and 2.35 V per cell at equalise, so a charge controller for a six-cell lead-acid string can be programmed directly from these numbers.

Q3: What is the maximum charging current for the 6-EVF-60? 12.0 A per cell at the published C10 basis, equal to 60 Ah × 0.20 C10 (Model page). For a parallel array, the ceiling scales with the string count — three strings give 36.0 A — and the controller must be sized against that figure.

Q4: What are the case dimensions and weight of the 6-EVF-60? 258×170×160 mm (L×W×H) and 18.8 ± 0.2 kg (Model page). Because the weight is published as a tolerance band rather than a single figure, cabinet loading should be calculated with 18.8 + 0.2 = 19.0 kg per cell plus the interconnects and tray.

Q5: What terminal type and torque does the 6-EVF-60 use? The published terminal is φ14-M6 (Model page). The manufacturer does not publish a tightening torque value on the model page, so the correct figure is to be requested from the factory — it should be confirmed before the first installation rather than copied from another model in the line.

Q6: How many cells does a 12V60Ah string contain and what bus voltage does it give? Six cells in series, because 12 V ÷ 2 V per cell = 6 cells (Arithmetic). The bus voltage is therefore 12 V nominal, 13.5 V float (6 × 2.25 V), 14.1 V equalise (6 × 2.35 V) and 10.5 V at the published 1.75 V per cell cutoff.

Q7: What is the published design float life of the 6-EVF-60 and at what temperature? Design life is published as 2–5 years (Model page), with cycle life of 350–600 cycles at 50–80 % depth of discharge. Self-discharge is published as ≤3 %/month at a 25 °C reference, and the working range is −15…50 °C — so 25 °C is the reference point for the stated figures.

Q8: How should an importer verify the 6-EVF-60 on delivery? Open every string and check case condition, terminal type against the published φ14-M6, polarity marking, label values (12 V / 60 Ah, 13.5 V float, 14.1 V equalise) and print code against the packing list. Then measure open-circuit voltage per string, which should read close to 12.6–12.8 V at 25 °C with no spread beyond 0.2 V across a string, and record the readings on the incoming report before the container is broken.

Q9: Which certifications does the CHISEN factory behind the 6-EVF-60 hold? The factory holds CE, ISO 9001, ISO 14001, UL and IEC certification, and operates 8 production bases with an annual capacity of 70 million kVAh across flooded tubular OPzS2, gel tubular OPzV2 and the 12 V VRLA 6-DZF / 6-DMF / 6-EVF families.

Q10: How do I request a quotation or samples for the 6-EVF-60? Send the destination port, the required quantity, the target string configuration and the charge controller voltage window to the CHISEN export desk, sales@chisen.cn or jack@chisen.cn, or via WhatsApp +86 131 6622 6999. The desk can quote the 6-EVF-60 12V60Ah on an FOB Ningbo or FOB Shanghai basis, and can arrange sample units for commissioning checks before a container order.

Expert Summary

The 6-EVF-60 12V60Ah is a 12 V 60 Ah C3 AGM cell in a 258×170×160 mm case weighing 18.8 ± 0.2 kg, published by the factory with float 13.5 V, equalise 14.1 V, maximum charge current 12.0 A, cutoff 1.75 V per cell, self-discharge ≤3 %/month at 25 °C, working range −15…50 °C, cycle life 350–600 at 50–80 % depth of discharge and design life 2–5 years. Six series cells make a 720 Wh string at 38.3 Wh/kg, with a 10.5 V string cutoff. For solar and off-grid duty the published 12.0 A charge ceiling is the governing number: one string restores at most 162 W, so a 300 W night load with three usable hours requires three parallel strings (3 × 12.0 A = 36.0 A) and 288 Wp of collector per string, worked out as 720 Wh ÷ (5 h × 0.50). Commissioning follows the published setpoints in order — 13.5 V float, 14.1 V equalise, 12.0 A current limit, 10.5 V disconnect — with open-circuit voltage measured per string before the first discharge. Sizing steps up or down should be taken against a measured load curve, using the published values for each sibling model rather than a label. CHISEN backs the range with 8 production bases, 70 million kVAh of annual capacity and CE, ISO 9001, ISO 14001, UL and IEC certification, shipping to importers across Asia, Africa, the Middle East, Latin America and Europe through Ningbo, Shanghai and the regional ports.

Contact CHISEN — 24-Hour Response

CHISEN Battery — Hangzhou, China. Export desk replies within 24 hours.

  • Email: sales@chisen.cn | jack@chisen.cn
  • WhatsApp: +86 131 6622 6999
  • Website: www.chisen.cn
  • Model page for the 6-EVF-60 12V60Ah: see the product link above in the Answer First section

Related CHISEN Buyer Guides

author avatar
chisenbattery@gmail.com