6-EVF-50 12V50Ah Telecom and Base Station Backup Power

ups data center battery room lead acid banks 17

Answer First

The 6-EVF-50 is a 12 V, 50 Ah C3-rated sealed VRLA monobloc for telecom and base-station backup power. Published values: 12 V nominal, 50 Ah at C3, 230 × 140 × 180 mm, 15.25 ± 0.2 kg, float 13.5 V, equalise 14.1 V, maximum charge current 10.0 A, cutoff 1.75 V per cell. The full set is on this model page.

Worked from those figures, one 12V 50Ah battery carries 12 V × 50 Ah = 600 Wh of nameplate energy, and 600 Wh ÷ 15.25 kg = 39.3 Wh/kg. At C3 the discharge current is 50 Ah ÷ 3 h ≈ 16.7 A, and the string reaches the published cutoff at 6 cells × 1.75 V = 10.5 V. Backup runtime is not decided by the label alone: it depends on site load, parallel strings, discharge temperature, battery age and float discipline — all computable from published data.

Key Takeaways

  • Published envelope: 12 V, 50 Ah, C3, 230 × 140 × 180 mm, 15.25 ± 0.2 kg, terminal φ11.8-M6 — every value is sourced from the model page.
  • Energy: 12 V × 50 Ah = 600 Wh, and 600 Wh ÷ 15.25 kg = 39.3 Wh/kg.
  • Voltage discipline is fixed: float 13.5 V and equalise 14.1 V across six cells, with the string floor at 1.75 V per cell, or 10.5 V.
  • Charge current is published: 10.0 A maximum sets recharge time and the rectifier output the site needs.
  • Runtime must be computed: at C3 a 12V 50Ah battery gives 50 Ah ÷ 3 h ≈ 16.7 A, so a 30 A site load needs two parallel strings.
  • Temperature is the hidden derating factor: base-station cabinets in India, Nigeria, Kenya, Vietnam, the Philippines and Brazil routinely run far above the 25 °C reference behind the published self-discharge figure.

§1 — 6-EVF-50 Quick Specifications

The 6-EVF-50 is a 12 V, 50 Ah C3-rated sealed VRLA monobloc. Every row below is transcribed from the published model data — nothing is estimated.

ParameterPublished valueSource
Nominal voltage12 VModel page
Capacity50 AhModel page
Dimensions L × W × H230 × 140 × 180 mmModel page
Weight15.25 ± 0.2 kgModel page
Terminalφ11.8-M6Model page
Float voltage13.5 VModel page
Equalise voltage14.1 VModel page
Maximum charge current10.0 AModel page

§2 — The Pain: Base Stations That Fail Before the Battery Does

The runtime gap. A 12V 50Ah battery delivers 50 Ah over three hours to 1.75 V per cell — roughly 16.7 A, or about 200 W at 12 V at the start of discharge. A base station drawing 30 A is therefore short on one string and depends on the generator; two parallel strings belongs in the purchase specification.

The temperature gap. Published self-discharge of ≤ 3 % per month is a 25 °C figure and the working range runs to 50 °C. Outdoor cabinets in Nigeria, Kenya, Vietnam, the Philippines, Egypt, Mexico and Brazil sit well above 25 °C for much of the year, which shortens achievable runtime, accelerates self-discharge and pushes the string into the equalise window more often. Site temperature compensation belongs in the tender document.

§3 — The Choice: Single 12 V String, 48 V Tower, or Both

Option A — 12 V strings on a 12 V bus. Each 12V 50Ah battery is self-contained, with several strings in parallel behind one controller. This suits small outdoor enclosures, microwave links and roadside cabinets: simple cable routing, one string swapped at a time, low parts count. Its weakness is current — 16.7 A per string at C3 — so a real load needs several parallel strings, each with its own fusing and monitoring tap.

Option B — 48 V tower from 12 V units. Four monobloc units are series-stacked to 48 V, the classical telecom arrangement. Arithmetic: 50 Ah ÷ 6 h ≈ 8.3 A per string at a six-hour rate, and 48 V × 8.3 A ≈ 400 W from the same 600 Wh of nameplate energy. At 12 V the same energy is drawn at 16.7 A, so the tower carries a quarter of the current and the cable losses.

Option C — the hybrid used on most modern sites. The rectifier and DC distribution stay at 48 V while the rack holds parallel 12 V units, keeping Option A’s maintenance case and Option B’s distribution design. Capacity steps come from the published ladder — 12 Ah, 20 Ah, 38 Ah, 45 Ah, 52 Ah, then 50, 60, 80, 100, 120 and 150 Ah, listed on the full product range. Size on the load analysis, then prefer the nearest rung.

§4 — The Framework: Four Numbers That Decide the Purchase

Fix four numbers before comparing quotations.

Number 1 — the DC load in amps. Take the rectifier output rating and station consumption at its stated DC voltage: load in watts ÷ 48 V = amps for a 48 V tower, ÷ 12 V = amps for a 12 V cabinet. Use the worst-case site load.

Number 2 — the required autonomy in hours. Put 3, 6 or 8 hours on the first line of the specification, because every calculation below depends on it.

Number 3 — the strings required. Use the published C3 current: 50 Ah ÷ 3 h ≈ 16.7 A per string, so a 30 A load gives 30 A ÷ 16.7 A ≈ 1.8, or two strings with margin. For a 48 V tower, 50 Ah ÷ 6 h ≈ 8.3 A per 12 V unit and 8.3 A × 4 = 33.3 A per tower string, so a 30 A site fits on one tower of 6-EVF-50 units.

Number 4 — the recharge window. Maximum charge current is published at 10.0 A, so recovering 50 Ah takes about 5 hours at ideal efficiency and longer in practice, because the final stage is held at the 14.1 V equalise setpoint. Size the site on the grid window and let the generator window cover load only.

§5 — Sibling Models in the 12 V VRLA Block

The 6-EVF-50 sits in the middle of the CHISEN 12 V VRLA ladder. Below are published values for the surrounding models. Float is 13.5 V, equalise 14.1 V and cutoff 1.75 V per cell for every row.

ModelCapacityL × W × H (mm)WeightTerminalMax charge current
6-DMF-5252 Ah224 × 135 × 17513.7 ± 0.2 kgφ11.8-M610.4 A
6-EVF-5050 Ah230 × 140 × 18015.25 ± 0.2 kgφ11.8-M610.0 A
6-EVF-6060 Ah258 × 170 × 16018.8 ± 0.2 kgφ14-M612.0 A

The 50 Ah versus 52 Ah decision. The 6-DMF-52 and the 6-EVF-50 sit almost on top of each other — 52 Ah against 50 Ah, both C3, both φ11.8-M6, both at 13.5 V float and 14.1 V equalise, charge current 10.4 A against 10.0 A — but the case geometry differs: 224 × 135 × 175 mm at 13.7 ± 0.2 kg against 230 × 140 × 180 mm at 15.25 ± 0.2 kg. The next rung of the EVF block is the 6-EVF-60 at 18.8 ± 0.2 kg and 258 × 170 × 160 mm, published on the sibling model page.

Weight and gravimetric energy. The weight ladder tracks capacity — 13.7 kg, 15.25 kg and 18.8 kg across the rows shown — so shelf loading and lifting access can be planned from the catalogue. Using published nameplate energy ÷ published weight: the 6-EVF-50 gives 600 Wh ÷ 15.25 kg = 39.3 Wh/kg and the 6-EVF-60 gives 720 Wh ÷ 18.8 kg = 38.3 Wh/kg. Arithmetic on Model page values. The 6-EVF-50 carries the better gravimetric figure of the two, which matters where every kilogram has to be carried up.

§6 — The Trust: Factory Data Behind Every Figure Above

Every number here comes from CHISEN, the factory behind it: CHISEN Battery in Hangzhou, China, with 8 production bases, 70 million kVAh of annual capacity, CE, ISO 9001, ISO 14001, UL and IEC certification, and flooded tubular OPzS2, gel tubular OPzV2 and 12 V VRLA lines in-house. Factory-controlled production means the 13.5 V float and 14.1 V equalise on the label are setpoints the cell went through, the φ11.8-M6 terminal, the ± 0.2 kg tolerance and the 230 × 140 × 180 mm case are controlled characteristics, and the 2–5 year design life with 350–600 cycles is stated rather than aspirational.

CHISEN exports the 12 V VRLA block to distributors and project buyers across India, Nigeria, Kenya, Vietnam, the Philippines, Brazil, Egypt, Mexico, Indonesia, Pakistan, Bangladesh, the UAE, South Africa, Ghana, Turkey, Poland, Germany, Spain, Australia and Thailand, with shipments moving out of Shanghai, Ningbo and Shenzhen through the ports of Shanghai, Jebel Ali, Mumbai, Karachi, Lagos, Mombasa, Durban, Cairo and Hamburg.

For site acceptance: verify the case marking against the order, measure open-circuit voltage on every monobloc after transport and rest, confirm the terminal hardware matches φ11.8-M6, weigh a sample against 15.25 ± 0.2 kg, and reconcile the packing list before the consignment is floated at 13.5 V. Quotations, samples and shipping documents to a named port are handled by the export desk, which replies within 24 hours.

§7 — FAQ

Q1: What are the published nominal voltage and capacity of the 6-EVF-50? The 12V 50Ah battery is published at 12 V nominal and 50 Ah at the C3 rate (Model page). Derived: 12 V × 50 Ah = 600 Wh of nameplate energy per monobloc.

Q2: What float and equalise setpoints does the manufacturer publish for the 6-EVF-50? Float 13.5 V and equalise 14.1 V (Model page) — 2.25 V and 2.35 V per cell across 6 cells, so a controller is set to the 12 V string values.

Q3: What is the maximum charging current for the 6-EVF-50? 10.0 A (Model page). Recovering a full 50 Ah discharge takes about 5 hours at ideal efficiency, longer in practice because the final stage is held at the 14.1 V equalise setpoint.

Q4: What are the case dimensions and weight of the 6-EVF-50? 230 × 140 × 180 mm and 15.25 ± 0.2 kg (Model page). Plan shelf loading and lifting access on those figures.

Q5: What terminal type and torque does the 6-EVF-50 use? φ11.8-M6 (Model page). Torque is not published and is to be requested from the factory.

Q6: How many cells does a 12V 50Ah battery string contain and what bus voltage does it give? Six cells: 12 V ÷ 2 V per cell = 6. The string sits at 13.5 V on float, 14.1 V on equalise, and reaches its floor at the published cutoff of 1.75 V per cell, or 6 × 1.75 V = 10.5 V.

Q7: How should an importer verify the 6-EVF-50 on delivery? Check the case marking against the order, measure open-circuit voltage on every monobloc, confirm the terminal hardware matches φ11.8-M6, weigh a sample against 15.25 ± 0.2 kg, and float the consignment at 13.5 V.

Q8: How do I request a quotation or samples for the 6-EVF-50? Email sales@chisen.cn or jack@chisen.cn, or use WhatsApp on +86 131 6622 6999, stating model, quantity, delivery port and target date. The ladder is on the full product range and the model data on this model page.

Expert Summary

The 6-EVF-50 is a 12 V, 50 Ah, C3-rated sealed VRLA monobloc: 230 × 140 × 180 mm, 15.25 ± 0.2 kg, φ11.8-M6 terminals, float 13.5 V, equalise 14.1 V, maximum charge current 10.0 A, cutoff 1.75 V per cell, design life 2–5 years. From those published values one 12V 50Ah battery holds 600 Wh at 39.3 Wh/kg and delivers about 16.7 A for three hours down to the 10.5 V string floor. Base-station runtime depends on load, autonomy, string count, site temperature and float discipline — all computable from published data before an order is issued. Behind the data stands CHISEN Battery of Hangzhou: 8 production bases, 70 million kVAh a year, CE, ISO 9001, ISO 14001, UL and IEC certification, and a 24-hour export desk.