OPzS2-150 2V150Ah Flooded Tubular Cell: Published Specs and Sizing

pg 1 9

Answer First

The OPzS2-150 2V150Ah is a 2 V, 150 amp-hour flooded tubular vented lead-acid cell rated at the 10-hour rate — 15 A for 10 hours down to 1.80 V per cell at 20 °C — and it is the correct cell for a telecom DC plant, a substation or a solar-powered cabinet that needs a 48 V bus holding about 7.2 kWh nominal per string, on a site where somebody will still read the electrolyte level and top up distilled water every quarter.

It is not a sealed block. Hydrogen venting, acid-proof flame-retardant vent plugs, scheduled water top-up and periodic equalisation are part of the product, not optional extras, and a project that treats the OPzS2-150 2V150Ah as a drop-in sealed cabinet battery discovers the difference in the first hot season.

The complete published data set for this cell sits on the OPzS2-150 2V150Ah model page, and the rest of the flooded range is listed under tubular flooded lead-acid batteries.

Key Takeaways

  • Capacity is rate-dependent. The nameplate figure is 150 Ah at C10 (15 A to 1.80 V/cell at 20 °C). At longer rates the cell delivers more: 170 Ah at C24, 186 Ah at C48, 195 Ah at C72, 203 Ah at C100, 206 Ah at C120 and 210 Ah at C240 (Datasheet).
  • Charging setpoints are fixed by the datasheet. Float 2.23 V/cell at 25 °C, equalising 2.35 V/cell at 25 °C, temperature compensation −3 mV/°C/cell, designed float life 20+ years at 20 °C (Datasheet). Solar and wind controllers use the 2.25 ± 0.005 V/cell float and 2.40 ± 0.01 V/cell equalising setpoints, with a −4 mV/cell/°C compensation coefficient (Datasheet).
  • Mechanical data is what decides the rack. Body 103 × 206 × 354 mm, 409 mm total height over the terminals, 10.5 kg without electrolyte and 14.5 kg with electrolyte (Datasheet).
  • Two limits protect the cell. Maximum charging current is 30 A (0.20 × C10) and internal resistance is about 1.2 mΩ fully charged at 20 °C, with a 2400 A short-circuit current (Datasheet).
  • A 48 V string is simple arithmetic. 24 cells give 7,200 Wh nominal, 348.0 kg with electrolyte (24 × 14.5 kg) and 28.8 mΩ of internal resistance (24 × 1.2 mΩ) (Arithmetic).

§1 — OPzS2-150 2V150Ah Quick Specifications

ParameterOPzS2-150 published valueSource
ModelOPzS2-150, flooded tubular stationary cell, 2 V 150 AhModel page
Nominal voltage2 VDatasheet
Nominal capacity150 Ah at C10 (15 A, 1.80 V/cell, 20 °C)Datasheet
C10 discharge current15 A (150 Ah ÷ 10 h)Arithmetic
Capacity at C24 / C48 / C72170 Ah / 186 Ah / 195 AhDatasheet
Capacity at C100 / C120 / C240203 Ah / 206 Ah / 210 AhDatasheet
Float voltage2.23 V/cell at 25 °CDatasheet
Equalising voltage2.35 V/cell at 25 °CDatasheet
Float setpoint, solar and wind2.25 ± 0.005 V/cell at 25 °CDatasheet
Equalising setpoint, solar and wind2.40 ± 0.01 V/cell at 25 °CDatasheet
Temperature compensation, float−3 mV/°C/cellDatasheet
Temperature compensation, solar and wind−4 mV/cell/°CDatasheet
Designed float life20+ years at 20 °CDatasheet
Dimensions L × W × H103 × 206 × 354 mmDatasheet
Container height354 mmDatasheet
Total height over terminals409 mmDatasheet
Terminal centre spacing108 mmDatasheet
Terminal20 mm OD, M8 thread, 7 mm depth, female copper insert M8Datasheet
Terminal tightening torque10–12 N·mDatasheet
Weight without electrolyte10.5 kg (23.2 lbs)Datasheet
Weight with electrolyte14.5 kg (32.0 lbs)Datasheet
ElectrolyteDiluted sulphuric acid, 1.240 g/cm³ at 20 °CDatasheet
Acid weight per cell4.0 kgDatasheet
Internal resistanceApprox. 1.2 mΩ, fully charged at 20 °CDatasheet
Maximum charge current30 ADatasheet
Charge characteristicConstant charge at 0.15 CA to 2.40 V at 20 °CDatasheet
Maximum discharge current (5 s)1000 ADatasheet
Short circuit current2400 ADatasheet
Self dischargeApprox. 4 % per month at 20 °CDatasheet
Ambient, discharge−25 °C to +65 °CDatasheet
Ambient, charge−20 °C to +65 °CDatasheet
Ambient, storage−15 °C to +40 °CDatasheet
Complied standardsIEC 60896-11, DIN 40736, IEC 61427, Eurobat long life guide, BS 6290 part 4, UL 1989Datasheet
Management systems and marksISO 9001, ISO 14001, GB/T 28001, CE, RU recognised componentDatasheet

Every row above is traceable. Values taken from the manufacturer’s OPzS2-150 datasheet are marked Datasheet, values taken from the published English product page are marked Model page, and derived figures are marked Arithmetic wherever they appear in the text. If a supplier cannot tell you which of the three a given figure is, treat the figure as unverified.

Solar and wind controller setpoints for the OPzS2-150

The same datasheet publishes a separate parameter set for renewable sites, and these are the values that actually go into a solar or wind charge controller.

Controller parameterPublished settingWhy the number matters
Over voltage disconnect2.47 ± 0.01 V/cell at 25 °CThe point at which the controller stops charging and the array is isolated
Regulation / equalising voltage2.40 ± 0.01 V/cell at 25 °CHigher than the mains float because the array has to push against the bus
Array reconnection voltage2.23 ± 0.005 V/cell at 25 °CThe bus voltage at which charging resumes
Float voltage setting2.25 ± 0.005 V/cell at 25 °CThe renewable float setpoint, above the 2.23 V mains float
Low voltage alarm1.95 ± 0.005 V/cell at 25 °CThe alarm threshold for the control room
Low voltage disconnect1.90 ± 0.005 V/cell at 25 °CThe load is shed at this point to protect the cells
Load reconnect voltage2.09 ± 0.01 V/cell at 25 °CThe load is restored once the bus recovers
Temperature compensation coefficient−4 mV/cell/°CThe coefficient used on renewable sites, distinct from the −3 mV/°C/cell float value

Long-time discharge capacity for solar and wind duty (final voltage 1.85 V)

Discharge rateC24C48C72C100C120C240
OPzS2-150 capacity170 Ah186 Ah195 Ah203 Ah206 Ah210 Ah
Stored energy at 2 V340 Wh372 Wh390 Wh406 Wh412 Wh420 Wh

Source: Datasheet for the capacity row, Arithmetic for the energy row (2 V × Ah).

§2 — The Pain: Where 2V 150Ah Projects Go Wrong

The first failure is a specification failure. Buyers routinely receive a quotation that says only “2V 150Ah tubular” and treat every 2 V 150 Ah cell in the world as interchangeable. The published OPzS2-150 data makes the differences explicit: capacity at C10 is 150 Ah, but capacity at C24 is 170 Ah and at C240 is 210 Ah. A bank sized on the C10 number for a slow-discharge backup duty is undersized; a bank sized on the C240 number for a five-hour discharge duty is over-purchased. Both mistakes trace back to a quotation that never stated the rate and the end voltage.

The second failure is thermal. A 48 V string of 24 OPzS2-150 cells accepts a maximum charging current of 30 A per cell, so a charger set to deliver more — which happens when the charger is sized for the string’s nominal power rather than for the cells’ acceptance — pushes the electrolyte into gassing and dries the separator faster than the topping-up interval can repair. The same string on a solar site needs the higher 2.25 ± 0.005 V/cell float and the 2.40 ± 0.01 V/cell equalising setpoint; on a mains-float site the correct values are 2.23 V/cell and 2.35 V/cell at 25 °C. These are not interchangeable, and a controller left on the wrong setpoint is the classic cause of premature capacity loss.

The third failure is weight and access planning. The OPzS2-150 is 10.5 kg without electrolyte and 14.5 kg with electrolyte, and the full height over the terminals is 409 mm, not the 354 mm body height. A 24-cell string with electrolyte weighs 348.0 kg (24 × 14.5 kg, Arithmetic). Cabinets, plinths and lifting plans are usually drawn against the body height and a lighter shipping weight, and the result is a string that does not fit the rack and a handling plan that understates the load.

The fourth failure is assuming sealed behaviour. This cell vents hydrogen during overcharge, needs acid-proof flame-retardant vent plugs, needs distilled water, and needs a scheduled equalising period. Those four obligations are why the OPzS2-150 2V150Ah wins in cabinets with a permanent operator — a central DC plant serving a national mobile network operator in Chennai, a fixed-line exchange in Rotterdam, a substation compound outside Nairobi — and loses in unmanned roadside or container sites.

The fifth failure, and the one that costs the most money, is ignoring what happens when two strings in parallel drift apart. A 24-cell string of OPzS2-150 cells presents 28.8 mΩ of internal resistance (24 × 1.2 mΩ, Arithmetic). Two strings in parallel do not share load evenly once their float voltages separate by a few millivolts, and the weaker string silently carries less current while ageing faster. The cure is an equalising stage plus a rotation discipline, and both belong in the maintenance contract rather than in a commissioning checklist.

Markets also shape the delivery plan. A lead-acid article of this class leaves through Hamburg, Santos and Singapore for importers in Europe, Brazil and South-East Asia, and the import file has to name the destination market before the container is booked, because a vented cell and a sealed cell do not clear every port under the same rules.

§3 — The Choice: The OPzS2-150 Against Its Published Siblings

Buyers comparing cells inside the 100 Ah to 200 Ah window are usually choosing between a flooded cell and a gel cell, or between three flooded capacities. The table below uses published values only.

ModelCapacity at C10Weight dry / with electrolyteDimensions L × W × HTotal heightMax charging currentInternal resistanceShort-circuit current
OPzS2-100100 Ah8.0 kg / 12.6 kg103 × 206 × 354 mm409 mm20 A1.0 mΩ at 20 °C1500 A
OPzS2-150150 Ah10.5 kg / 14.5 kg103 × 206 × 354 mm409 mm30 A1.2 mΩ at 20 °C2400 A
OPzS2-200200 Ah13.0 kg / 17.5 kg103 × 206 × 354 mm409 mm40 A0.95 mΩ at 20 °C2600 A
OPzV2-100 (gel)100 Ah13.2 kg (sealed)103 × 206 × 354 mm390 mm30 A1.1 mΩnot published

Sources: OPzS2-100 and OPzS2-200 from their datasheets, with the OPzS2-100 short-circuit current from its model page; OPzV2-100 from the model page and its datasheet; the comparison itself is Arithmetic.

Four numbers drive the decision. First, dry weight: 8.0 kg, 10.5 kg and 13.0 kg for the three flooded cells — a cell that must be carried up a ladder or into a pit should be chosen with the wet weight in mind, not the dry one. Second, the charging current limit of 20 A, 30 A and 40 A, which must be matched to the charger output. Third, internal resistance, which does not fall in a straight line with capacity — 1.0 mΩ at 100 Ah, 1.2 mΩ at 150 Ah and 0.95 mΩ at 200 Ah — so a 24-cell string of the 200 Ah cell presents 22.8 mΩ (24 × 0.95 mΩ, Arithmetic) against 28.8 mΩ for the 150 Ah cell (24 × 1.2 mΩ, Arithmetic) and 24.0 mΩ for the 100 Ah cell (24 × 1.0 mΩ, Arithmetic). The 150 Ah cell therefore has the highest voltage drop of the three under the same load, which matters when the string is long and the load is heavy.

The fourth number is the maintenance profile, and here the published data is unambiguous. The flooded OPzS2-150 carries 14.5 kg of electrolyte in an open container that must be topped up and periodically equalised. The gel OPzV2-100 carries the same 103 × 206 mm footprint with a 390 mm total height, weighs 13.2 kg with the electrolyte immobilised in the gel, and needs no watering — the price of that is a 1.1 mΩ internal resistance, a 30 A charging limit and a shorter life under deep cycling. For a manned substation with a technician on call, the flooded cell usually delivers the lower cost per usable year; for a sealed container with no access, the gel cell removes a whole maintenance category. Both routes are legitimate, and the published figures above are what the comparison should be built on.

48 V string arithmetic across the three flooded capacities

CellCells in stringNominal energyWeight with electrolyteWeight without electrolyteString internal resistanceMaximum charging current
OPzS2-100244,800 Wh302.4 kg192.0 kg24.0 mΩ480 A
OPzS2-150247,200 Wh348.0 kg252.0 kg28.8 mΩ720 A
OPzS2-200249,600 Wh420.0 kg312.0 kg22.8 mΩ960 A

Source: Datasheet for the cell-level values, Arithmetic for the string rows.

For a 54-cell 108 V substation string the same OPzS2-150 arithmetic gives a float bus of 120.42 V (54 × 2.23 V), 16,200 Wh nominal, 783.0 kg with electrolyte (54 × 14.5 kg), 64.8 mΩ of internal resistance (54 × 1.2 mΩ) and a 1,620 A maximum charging current (54 × 30 A) (Arithmetic).

The same discipline applies further up the size range. If your string is larger than 200 Ah per cell, move to the OPzS flooded range overview rather than scaling the numbers in this table proportionally — plate thickness, internal volume and electrolyte quantity change non-linearly with capacity. The OPzS2-500 2V500Ah cell is the next published step up, at 166 × 206 × 470 mm and 26.0 kg with electrolyte.

§4 — The Framework: Seven Hard Checks Before You Sign

Q1. Match the charger to the cell’s acceptance, not to the string. The maximum charging current of the OPzS2-150 is 30 A (Datasheet). A 24-cell string therefore accepts at most 720 A (24 × 30 A, Arithmetic). Most telecom float rectifiers are sized well below that, which is correct; a solar controller set to the array’s full output is where the limit gets breached.

Q2. Apply temperature compensation to the setpoint, not to the battery. The published compensation is −3 mV/°C/cell on float (Datasheet), so a cell at 35 °C needs its 2.23 V/cell float reduced by 0.036 V. On a renewable site the published coefficient is −4 mV/cell/°C and the float setpoint is 2.25 ± 0.005 V/cell. Controllers that ignore this are permanently overcharging the string in the hot season and permanently undercharging it in winter.

Q3. Design for the float life at the site’s real temperature. The 20+ year design figure is quoted at 20 °C (Datasheet). A cabinet in Chennai, on a roof in Lagos or an outdoor enclosure in Durban will not deliver that figure, and the honest way to plan a replacement interval is to take the 20 °C number and treat every 10 °C of ambient uplift as a materially shorter service life. Projects that publish a 20-year asset life for a string sitting in a 35 °C room have not done the arithmetic.

Q4. Plan the watering interval from the real charging regime. A cell that is floated at 2.23 V/cell at 25 °C and never equalised loses water slowly; a cell that is equalised at 2.35 V/cell twice a month in a hot climate loses water fast enough to need attention on a monthly cycle. Put the interval in the maintenance contract, and put the electrolyte density check (1.240 g/cm³ at 20 °C, Datasheet) on the same schedule. Each cell in the OPzS2-150 holds 4.0 kg of acid, so a 24-cell string carries 96.0 kg of electrolyte (24 × 4.0 kg, Arithmetic) that has to be topped up and eventually replaced.

Q5. Size the interconnects and torque them correctly. The terminal is a copper female insert M8 with a published torque of 10–12 N·m (Datasheet). Under-torqued terminals generate heat at the joint; over-torqued ones damage the insert. For a 24-cell string the interconnect carries the full string current, so the cable cross-section is set by that current and the 2400 A short-circuit current (Datasheet) determines how quickly the fault must be cleared.

Q6. Decide how many strings run in parallel, and how they will be equalised. Two parallel strings of 12 cells in series each will drift apart unless the charger has an equalising stage and the operator runs it. Parallel strings also multiply the water-top-up workload and the total string weight: 24 × 14.5 kg = 348.0 kg per 150 Ah string with electrolyte (Arithmetic).

Q7. Confirm the standards the cell is built to. A 2 V vented cell for stationary duty is normally specified against IEC 60896-11 and the equivalent DIN 40736 envelope, with IEC 61427 for the renewable cycling test, the Eurobat long life guide, BS 6290 part 4 and UL 1989 for the North American market. CHISEN production runs under ISO 9001 and ISO 14001 with GB/T 28001 occupational health and safety management, and the range is supplied with CE documentation, so the paperwork trail should exist before the first container is booked.

§5 — The Trust: What a Datasheet Must State — and What to Reject

The single most useful question a buyer can ask a supplier is: “which document is this number from?” A published datasheet answers five questions that quotations never answer. What is the capacity rate and the end voltage? For the OPzS2-150 it is 150 Ah at C10 to 1.80 V/cell at 20 °C, and the full curve to 240 hours is published alongside it. What is the weight with and without electrolyte? 10.5 kg and 14.5 kg — both numbers, because a shipping weight quoted without electrolyte tells you nothing about handling. What is the total height over the terminals? 409 mm, not the 354 mm body height, and the difference is exactly the kind of detail that stops a cabinet from being delivered. What is the maximum charging current? 30 A. What is the reference temperature for the internal resistance and for the float life? 20 °C for both, and both references matter more than the numbers themselves.

Against that standard, reject any quotation that quotes a float voltage above 2.23 V per cell for this model, or one that quotes a temperature compensation coefficient other than −3 mV/°C/cell, or one that quotes the 20+ year design life against 25 °C rather than 20 °C. The OPzS2-150 datasheet setpoints are 2.23 V/cell float, 2.35 V/cell equalising and −3 mV/°C/cell compensation, with the 20+ year design figure referenced to 20 °C. A supplier who quotes different numbers for the same model is either reading a different revision or inventing them.

Two further quality signals are worth checking on site. First, ask for the plant audit trail: paste mixing, grid casting, group assembly, formation and sealing are the process steps that decide whether a 150 Ah cell really holds 150 Ah in year five, and they are the difference between a manufacturer and a packer. Second, ask for the certification package — ISO 9001, ISO 14001, CE, UL and IEC documentation should arrive with the quotation, not three weeks after the deposit. CHISEN runs eight production bases with roughly 70 million kVAh of annual capacity, and the company profile is published on the CHISEN company page if you want to check the manufacturing scale behind a quotation before you commit a container.

§6 — FAQ

Q1. What is the rated capacity of the OPzS2-150 2V150Ah? 150 Ah at the 10-hour rate (15 A to 1.80 V/cell at 20 °C). The published table also gives 170 Ah at C24, 186 Ah at C48, 195 Ah at C72, 203 Ah at C100, 206 Ah at C120 and 210 Ah at C240 (Datasheet).

Q2. How many cells does a 48 V string need, and how much energy does it hold? 24 cells. 48 V × 150 Ah = 7,200 Wh nominal (Arithmetic). The string weighs 348.0 kg with electrolyte (24 × 14.5 kg) and 252.0 kg dry (24 × 10.5 kg), and carries 96.0 kg of acid (24 × 4.0 kg).

Q3. What float and equalising voltage should the charger use? Float 2.23 V/cell and equalising 2.35 V/cell, both referenced to 25 °C. On solar and wind sites use the higher 2.25 ± 0.005 V/cell float and 2.40 ± 0.01 V/cell equalising setpoint (Datasheet).

Q4. What temperature compensation does the cell need? −3 mV/°C/cell on float (Datasheet), applied to the setpoint. At 35 °C the float setpoint falls by 0.036 V per cell. Renewable controllers use the published −4 mV/cell/°C coefficient.

Q5. How long is the designed float life? 20+ years at 20 °C (Datasheet). Higher ambient temperatures reduce achievable service life, so site temperature has to be part of the replacement plan rather than a footnote.

Q6. What is the maximum charging current? 30 A per cell, which is 0.20 × C10 (Datasheet). For a 24-cell string the theoretical ceiling is 720 A (24 × 30 A, Arithmetic), and the charger should normally deliver far less.

Q7. Can this cell be installed without a permanent operator? It can be installed, but not forgotten. Flooded tubular cells need distilled-water top-up, electrolyte density checks, ventilation and periodic equalising. For an unmanned site, compare the published gel alternative instead.

Q8. What is the internal resistance and short-circuit current? About 1.2 mΩ fully charged at 20 °C (Datasheet) and a 2400 A short-circuit current (Datasheet). The string resistance of a 24-cell arrangement is 28.8 mΩ (24 × 1.2 mΩ, Arithmetic), and the 2400 A figure is what your DC fuse and disconnection arrangement must be able to interrupt.

Q9. How does the OPzS2-150 compare with the 100 Ah and 200 Ah cells? Same 103 × 206 mm footprint and the same 409 mm total height. The published differences are weight (10.5 kg dry and 14.5 kg wet against 8.0 kg and 12.6 kg for the 100 Ah cell, and 13.0 kg and 17.5 kg for the 200 Ah cell), charging limit (30 A against 20 A and 40 A), internal resistance (1.2 mΩ against 1.0 mΩ and 0.95 mΩ) and short-circuit current (2400 A against 1500 A and 2600 A). The OPzS2-150 2V150Ah model page carries the full data set.

Q10. Which standards and certifications apply? The flooded 2 V stationary cell is built to the IEC 60896-11 and DIN 40736 envelope, with IEC 61427 for renewable cycling, the Eurobat long life guide, BS 6290 part 4 and UL 1989 for the North American market. CHISEN supplies the range with CE documentation under ISO 9001 and ISO 14001 management systems, with GB/T 28001 occupational health and safety certification.

Expert Summary

The OPzS2-150 2V150Ah is a 2 V flooded tubular vented lead-acid cell with a published 150 Ah capacity at the 10-hour rate (15 A to 1.80 V/cell at 20 °C), rising to 210 Ah at the 240-hour rate; float 2.23 V/cell and equalising 2.35 V/cell at 25 °C with −3 mV/°C/cell compensation and a 20+ year design float life referenced to 20 °C; a body of 103 × 206 × 354 mm with 409 mm total height over the terminals; a weight of 10.5 kg without electrolyte and 14.5 kg with electrolyte, of which 4.0 kg is acid; a 30 A maximum charging current; about 1.2 mΩ internal resistance at 20 °C; and a 2400 A short-circuit current. A 24-cell 48 V string of these cells holds 7,200 Wh nominal, weighs 348.0 kg with electrolyte and presents 28.8 mΩ of internal resistance. The cell is the correct choice where a manned telecom DC plant, substation or renewable cabinet benefits from long float life and low cost per usable year; where site access is unattended, the published gel alternative trades a slightly different internal resistance and charging limit for the removal of the watering cycle.

Contact CHISEN — 24-Hour Response

If you are quoting a 2 V 150 Ah cell for a 48 V DC plant, a substation in Rotterdam or a solar cabinet outside Nairobi, ask for the complete OPzS2-150 datasheet, the string layout drawing and the certification package, and ask for them in writing: email sales@chisen.cn, or message the export desk on WhatsApp at +86 131 6622 6999 (https://wa.me/8613166226999). One line describing your bus voltage, backup time and site temperature is enough for us to return the string arithmetic, the charger setpoints and the nearest capacity in the flooded range — or the gel equivalent if nobody will ever top up water on that site.

Browse the full CHISEN lead-acid range and technical data at https://leadacidbattery.cn.

Related CHISEN Product Pages

  • OPzS2-150 2V150Ah model page — full published specification set