The 6-EVF-120 is the 120 Ah member of the 12 V VRLA AGM series CHISEN publishes for telecom and base-station standby duty. Its published envelope is fixed and verifiable: 12 V nominal, 120 Ah at the C3 rate, a 407×170×240 mm case, 40 ± 0.2 kg, and φ20-M8 terminals. Float is 13.5 V across the six-cell string and equalise is 14.1 V, the same pair used across the whole 12 V VRLA range. Charge current is published at 24.0 A, which is exactly one fifth of capacity (120 Ah ÷ 5 = 24.0 A), so the charging spec is internally consistent. Design life is published as 2–5 years and cycle life as 350–600 cycles at 50–80 % depth of discharge.

For a network integrator, the practical question is not capacity but architecture: how many units sit in the string, what bus voltage the rectifier delivers, and what the run-time looks like on the worst night of the year. All of the figures below come from the factory model page, and every derived number is shown as arithmetic so it can be checked on a spreadsheet before a purchase order is raised.

Key Takeaways

  • The 6-EVF-120 publishes 12 V / 120 Ah at C3, 407×170×240 mm and 40 ± 0.2 kg — a size and weight that decides rack, cabinet and shipping decisions on its own.
  • One string of six cells at 13.5 V float and 14.1 V equalise gives a rectifier window that is standard for telecom outdoor cabinets, so the charger does not need special programming.
  • 24.0 A maximum charge current equals C/5 (120 Ah ÷ 5 = 24.0 A) — the charging stage stays inside the published envelope even on a long recovery after an outage.
  • Nominal energy is 12 V × 120 Ah = 1,440 Wh per unit; at 80 % usable depth of discharge that is 1,152 Wh (1,440 Wh × 0.8).
  • Published design life is 2–5 years, cycle life 350–600 — the float number is what a base-station site should be planned against.
  • Self-discharge is ≤3 %/month at 25 °C, i.e. 120 Ah × 3 % = 3.6 Ah per month, or roughly 5 mA continuous on float.
  • Working temperature is −15…50 °C, which matters for unheated roadside and rooftop cabinets.

§1 — 6-EVF-120 Quick Specifications

ParameterValueSource
Nominal voltage12 VModel page
Capacity120 AhModel page
Capacity rateC3Model page
Case dimensions L×W×H407×170×240 mmModel page
Weight40 ± 0.2 kgModel page
Terminalφ20-M8Model page
Float voltage13.5 VModel page
Equalise voltage14.1 VModel page
Cycle life350–600 (DoD 50–80 %)Model page
Maximum charge current24.0 AModel page
Discharge cutoff1.75 V/cellModel page
Self-discharge≤3 %/month at 25 °CModel page
Working temperature−15…50 °CModel page
Design life2–5 yearsModel page
Cell count6 cells (12 V ÷ 2 V = 6)Arithmetic
Nominal energy12 V × 120 Ah = 1,440 WhArithmetic
Usable energy at 80 % DoD1,440 Wh × 0.8 = 1,152 WhArithmetic
Energy density1,440 Wh ÷ 40 kg = 36 Wh/kgArithmetic
Specific charge current120 Ah ÷ 5 = 24.0 A (C/5)Arithmetic
this model page

§2 — The Pain: Telecom Backup Duty Is Unforgiving About the Details

A base station that loses power does not fail politely. The mast, the radio unit, the rectifier and the cooling fan all come up together after a grid interruption, and the site has to ride through until the generator starts or the utility supply returns. Three failures cause most of the field returns in this application, and none of them are visible in a catalogue.

The first is capacity mismatch. A 120 Ah unit is frequently ordered because someone read “12 V 120 Ah” from a competitor datasheet that quoted a 10-hour rate. The 6-EVF-120 is published at C3, meaning the capacity rating is taken at a three-hour discharge, which is the harder, shorter-discharge test. Sizing a cabinet from the label alone without the rate can leave the installer 15–20 % short on the hours promised to the operator. The published figure on the factory page is 120 Ah at C3, and that is the number to design against.

The second failure is the temperature coefficient nobody writes on the order form. Published capacity is measured at 25 °C. In an outdoor telecom cabinet in Lagos, Karachi or Cairo, internal temperatures regularly exceed 40 °C during the day, and float life is strongly shortened above the nominal band. The working temperature range of −15…50 °C is the safe envelope for the 6-EVF-120, but it is not the same as saying the battery will deliver full rated life in an unventilated cabinet in a hot climate. Site engineers need to read that distinction carefully before they commit.

The third failure is the string that was assembled without a real bus plan. A twelve-volt battery is six cells in series. At float that string presents 13.5 V, and during equalisation 14.1 V — 6 × 2.35 V = 14.1 V, and 6 × 2.25 V = 13.5 V. Rectifiers set for telecom outdoor cabinets are normally configured for a 13.5 V float bus with a 14.4–14.5 V boost stage. If the string is wired 12 V nominal into a bus that never reaches 14.1 V, the battery will not fully equalise, and stratification will build up in the cell stack over successive cycles. Publishers who quote the setpoints make this easy to verify; publishers who do not make it impossible.

§3 — The Choice: Matching the 6-EVF-120 to the Actual Site Load

Choosing between 12 V VRLA sizes is not a search for the biggest number. It is a comparison of how much energy sits on the shelf, how many strings the cabinet has to host, and how the cabinet is serviced. The 6-EVF-120 sits in the upper half of the 12 V AGM series, and it is worth being explicit about what that position buys and what it costs.

On energy per unit, the arithmetic is direct: 12 V × 120 Ah = 1,440 Wh nominal, and 1,440 Wh × 0.8 = 1,152 Wh usable at an 80 % depth of discharge, which is the normal design limit for an AGM product that must also be able to be charged and equalised regularly. The sibling 6-EVF-100 in the same 12 V series provides 12 V × 100 Ah = 1,200 Wh nominal, or 960 Wh usable — a shortfall of 1,152 Wh − 960 Wh = 192 Wh per cabinet. The 6-EVF-150 gives 12 V × 150 Ah = 1,800 Wh nominal, or 1,440 Wh usable, which is 1,440 Wh − 1,152 Wh = 288 Wh more than the 6-EVF-120.

On physical installation, the trade is sharper than the energy difference suggests. The 6-EVF-120 case is 407×170×240 mm and 40 ± 0.2 kg. The 6-EVF-100 measures 330×170×218 mm at 31.5 ± 0.2 kg, so the 6-EVF-120 is 77 mm longer, 22 mm taller and 8.5 kg heavier (40 − 31.5 = 8.5 kg). The 6-EVF-150 measures 483×170×240 mm at 48.5 ± 0.2 kg — 76 mm longer and 8.5 kg heavier again. In a two-battery cabinet, the 6-EVF-120 adds 17 kg of handling weight over the 6-EVF-100 configuration, and that is the number that decides whether a technician can change the unit on a ladder or needs a second person and a trolley.

The terminal design deserves attention too. The 6-EVF-120 uses φ20-M8 terminals, the same bolt pattern as the 6-EVF-150, while the 6-EVF-100 uses φ20-M8 as well. That continuity is useful for mixed fleets: the same cable lug and the same torque procedure apply across the two largest 12 V sizes, which simplifies spare-part stocking and reduces the number of tools a field crew carries.

For an importer building a cabinet, the practical conclusion is that the 6-EVF-120 is the size to choose when a single 12 V string must hold roughly one day of low-load standby plus the run-time needed for a generator start, and when the cabinet volume allows a 407 mm case depth. The full selection of 12 V VRLA sizes is listed on the full product range, and for a smaller cabinet the sibling model page shows the 50 Ah configuration with the same 13.5 V float and 14.1 V equalise setpoints.

§4 — The Framework: A Four-Step Method for Sizing and Qualifying a 6-EVF-120 Bank

Step 1 — Fix the load, not the label. Collect the measured DC load of the base station in watts at the site, including the rectifier, the radio, the cooling fan and any security or lighting circuits. Convert it to the battery side through the inverter or DC/DC stage, keeping the published efficiency of that stage as a separate line so it can be challenged later.

Step 2 — Work out the runtime from the published energy. Take the nominal energy of one 6-EVF-120 as 12 V × 120 Ah = 1,440 Wh. Apply the usable share: 1,440 Wh × 0.8 = 1,152 Wh. Then divide by the DC-side power draw. For a 300 W DC load, 1,152 Wh ÷ 300 W = 3.8 hours. For a 600 W load on the same single unit, 1,152 Wh ÷ 600 W = 1.9 hours. If two units are wired in parallel, the bank energy doubles to 2 × 1,440 Wh = 2,880 Wh, usable energy becomes 2,880 Wh × 0.8 = 2,304 Wh, and a 600 W load then runs for 2,304 Wh ÷ 600 W = 3.8 hours. Every one of these figures follows from the published 12 V / 120 Ah rating and a stated efficiency assumption — no manufacturer data beyond the model page is required.

Step 3 — Check the charging side against the published current. The maximum charge current for the 6-EVF-120 is 24.0 A, which equals 120 Ah ÷ 5. A rectifier sized for a 300 W DC load needs roughly 300 W ÷ 13.5 V = 22.2 A of float current, and 22.2 A sits just below the 24.0 A published ceiling. A rectifier sized for 600 W would demand 600 W ÷ 13.5 V = 44.4 A, which is above 24.0 A for a single unit and therefore requires two units in parallel on the charge side (2 × 24.0 A = 48.0 A) or a separate charger. This single calculation is the most common design error in telecom standby cabinets, and the 6-EVF-120 published charge current makes it checkable in one line.

Step 4 — Set the acceptance test before the shipment leaves. Agree the inspection protocol with the factory in writing: open-circuit voltage on every cell, the string voltage at float and at equalise, the measured weight against the 40 ± 0.2 kg published figure, and a case check against 407×170×240 mm. A bank that passes open-circuit voltage but sits 1.5 V below the 13.5 V float target under load is a bank that will not hold capacity through its service life, and the protocol should say so.

The same framework applies to the larger 12 V sizes, because the 6-EVF series shares the same float, equalise and cutoff setpoints throughout. The 6-EVF-150, for example, publishes 30.0 A of charge current (150 Ah ÷ 5 = 30.0 A) on a 483×170×240 mm, 48.5 kg case, so it charges faster but occupies more cabinet volume.

§5 — 6-EVF-120 Against the Neighbouring 12 V VRLA Sizes

ModelCapacityRateL×W×H mmWeightTerminalCharge currentFloatEqualizeCutoff
6-DMF-5252 AhC3224×135×17513.7 ± 0.2 kgφ11.8-M610.4 A13.5 V14.1 V1.75 V/cell
6-EVF-5050 AhC3230×140×18015.25 ± 0.2 kgφ11.8-M610.0 A13.5 V14.1 V1.75 V/cell
6-EVF-6060 AhC3258×170×16018.8 ± 0.2 kgφ14-M612.0 A13.5 V14.1 V1.75 V/cell
6-EVF-8080 AhC3259×170×21825.7 ± 0.2 kgφ16-M616.0 A13.5 V14.1 V1.75 V/cell
6-EVF-100100 AhC3330×170×21831.5 ± 0.2 kgφ20-M820.0 A13.5 V14.1 V1.75 V/cell
6-EVF-120120 AhC3407×170×24040 ± 0.2 kgφ20-M824.0 A13.5 V14.1 V1.75 V/cell
6-EVF-150150 AhC3483×170×24048.5 ± 0.2 kgφ20-M830.0 A13.5 V14.1 V1.75 V/cell

§6 — The Trust: Factory Capacity, Certification and Delivery

The 6-EVF-120 comes from a manufacturer running 8 production bases with an annual capacity of 70 million kVAh. That scale matters at this size specifically: a 120 Ah AGM cell is produced on continuous-cast lines and formed in a controlled humidity chamber, and the published weights of 40 ± 0.2 kg are the weights of finished, formed and tested product rather than of assembled containers. A tight ±0.2 kg tolerance on 40 kg is a 0.5 % band, which is the kind of consistency an importer can use as an incoming-goods check.

Certification covers CE, ISO 9001, ISO 14001, UL and IEC. ISO 9001 and ISO 14001 cover the quality and environmental management systems behind the published specification; UL and IEC cover the safety and performance framework that telecom buyers in North America, Europe and Asia typically require in a supplier file. CHISEN Battery is based in Hangzhou, China, and the export desk issues the model documentation, test certificates and packing data for the 6-EVF-120 against the same model page.

On delivery, the shipped configuration for the 6-EVF-120 is a 12 V, 120 Ah VRLA AGM unit in a 407×170×240 mm case at 40 ± 0.2 kg, with φ20-M8 terminals, float 13.5 V and equalise 14.1 V. CHISEN ships these batteries to importers and distributors in India, Nigeria, Kenya, Vietnam, the Philippines and Brazil, with container movements mainly from Ningbo and Shanghai, and onward shipments through Karachi, Lagos, Mombasa, Durban and Cairo to partner warehouses in Dubai, Hamburg and Rotterdam. Cubic volume rather than weight often sets the freight cost on a 40 kg battery, so the 407×170×240 mm case dimension is a freight number as much as an installation number. Buyers in Mexico, Indonesia, Pakistan, South Africa and the Middle East confirm the same figure on the packing list against the model page before the container is released.

What is not published is stated as not published. Torque values for the φ20-M8 terminal, the full discharge curve at other temperatures, and the internal resistance at C3 are to be requested from the factory. Importer records, project references and order volumes for the 6-EVF-120 are not published either, and any supplier claiming them should be asked for documentation behind the claim rather than the claim itself.

§7 — FAQ

Q1: What are the published nominal voltage and capacity of the 6-EVF-120? The 6-EVF-120 is published at 12 V nominal and 120 Ah, with the capacity rated at the C3 rate (Model page).

Q2: What float and equalise setpoints does the manufacturer publish for the 6-EVF-120? Float 13.5 V and equalise 14.1 V for the complete six-cell string — 6 × 2.25 V = 13.5 V and 6 × 2.35 V = 14.1 V (Model page, Arithmetic).

Q3: What is the maximum charging current for the 6-EVF-120? 24.0 A, which is the published C/5 figure: 120 Ah ÷ 5 = 24.0 A (Model page, Arithmetic).

Q4: What are the case dimensions and weight of the 6-EVF-120? 407×170×240 mm and 40 ± 0.2 kg (Model page).

Q5: What terminal type and torque does the 6-EVF-120 use? The terminal is φ20-M8 (Model page). The tightening torque is not published and is to be requested from the factory.

Q6: How many cells does a 12V120Ah string contain and what bus voltage does it give? Six cells in series (12 V ÷ 2 V = 6), giving a 13.5 V float bus and a 14.1 V equalise bus (Arithmetic from Model page).

Q7: What is the published design float life of the 6-EVF-120 and at what temperature? Design life is published as 2–5 years, with a working temperature range of −15…50 °C and self-discharge ≤3 %/month measured at 25 °C (Model page).

Q8: How should an importer verify the 6-EVF-120 on delivery? Check the model marking against 12 V / 120 Ah, measure the weight against 40 ± 0.2 kg, measure the case against 407×170×240 mm, and record open-circuit voltage per cell plus the string voltage at float against the 13.5 V target (Model page, Arithmetic).

Q9: Which certifications does the CHISEN factory behind the 6-EVF-120 hold? CE, ISO 9001, ISO 14001, UL and IEC (company records).

Q10: How do I request a quotation or samples for the 6-EVF-120? Send the required quantity, destination port and the cabinet arrangement to sales@chisen.cn or jack@chisen.cn, or message the export desk on WhatsApp +86 131 6622 6999; sample and pricing requests are handled by the export desk directly.

Expert Summary

The 6-EVF-120 is a 12 V, 120 Ah C3 VRLA AGM unit built for telecom and base-station standby duty, and the factory publishes a complete specification rather than a marketing summary: 407×170×240 mm case, 40 ± 0.2 kg, φ20-M8 terminals, 13.5 V float, 14.1 V equalise, 24.0 A maximum charge current, 1.75 V/cell cutoff, ≤3 %/month self-discharge, −15…50 °C working range, 350–600 cycles and 2–5 years of design life. Each of those numbers converts directly into a design decision: 12 V × 120 Ah = 1,440 Wh nominal, 1,152 Wh usable at 80 % depth of discharge, 3.8 hours on a 300 W DC load, 1.9 hours on a 600 W DC load, 7.6 hours on two units in parallel, and a charge ceiling of 24.0 A that is exactly one fifth of capacity. The six-cell string produces a standard telecom bus, so the cabinet can run on conventional float/boost charging without special rectifier programming, and the 40 kg unit fits the 12 V cabinets used for outdoor cellular and microwave sites. Against the neighbouring sizes, the 6-EVF-100 at 31.5 kg gives 960 Wh usable and the 6-EVF-150 at 48.5 kg gives 1,440 Wh usable, so the 120 Ah step is the balance point for cabinets that must carry a full night of standby plus generator-start run-time without exceeding a two-battery footprint. CHISEN produces these cells across 8 bases with 70 million kVAh of annual capacity under CE, ISO 9001, ISO 14001, UL and IEC, and ships them to importer and distributor partners in Asia, Africa, the Middle East, Latin America and Europe from Ningbo and Shanghai. Unpublished items — terminal torque, temperature-corrected discharge curves, internal resistance — are identified as such in this article and are to be requested from the factory with the quotation, together with the test protocol that the buyer wants applied before shipment.